Protection
100% Generator Stator & Ground
Fault
Numerical Generator
Directional Time and Instantaneous
Over Current Relay
Local Breaker Backup
RAGEK
Complete stator earth-fault protection for unearthed
or high impedance earthed generators
RAGEK 95%
Earth-fault protection covering 95% of the stator winding
Two stage measuring of filtered fundamental frequency neutral
point voltage
Each stage has delayed output with three make contacts and
red indicating flag
Dimension: 4U 24C
RAGEK 100%
Earth-fault protection covering 100% of the stator winding
Measures filtered fundamental frequency neutral point voltage
to protect 95% of the stator winding
Measures filtered third harmonic neutral point voltage to
protect 95-100% of the stator winding
1% generator third harmonic voltage enables full protection
Delayed outputs with three make contacts and red indicating
flag - the 95-100% function is supervised by generator voltage
or current
Dimension: 4U 42C
RXTUG 22H
RXTUG 22H is used for auxiliary voltage supply of electronic
relay circuits. It is suitable for use where up to 15 W
continuous output power is required, e.g. for the supply of
protective relays or other automation equipment.
The RXTUG 22 can be powered from any dc voltage source
24 V to 250 V. When redundant power supplies are needed,
parallel operated RXTUG 22H may be used with isolating
diodes e.g. RTXE.
RXEDK
It is Time over/undervoltage relay and protection assembly
It is single or multiple RXEDK 2H phase elements measuring
two-stage overvoltage or combined over and undervoltage
protection for system voltage supervision and various single
relay element neutral point or broken delta overvoltage
applications for earthfault detection.
RXEG 21
RXTDA1
The RXTDA 1 diode unit is used to provide a relay with either
a directional function or transient protection and delay on
dropout and for blocking in the control circuits.
RXMA1
NUMERICAL GENERATOR
PROTECTION
This protection scheme uses the relay
REG 316*4
This relay is used for the following protection
Definite time overcurrent (undercurrent) (optionally with inrush detection)
Instantaneous overcurrent (undercurrent)
Voltage-controlled overcurrent
Inverse time overcurrent
Directional overcurrent protection with definite or inverse time characteristic
Negative phase sequence current
Definite time overvoltage (undervoltage)
Stator earth fault (95%)
Rotor earth fault
Instantaneous overvoltage (undervoltage) with peak value evaluation
Voltage balance
316*4
RXIDK 2H
RXIDK is a time-overcurrent relay
mainly used as short-circuit and
earth fault protection on all types of
objects in the network.
RXPDK23H
It is used for Directional Overcurrent
Protection.