Sunteți pe pagina 1din 47

SITE POWER FOR NOKIA PROJECT

Connections Guide Presentation


PRSB 15 KW BASIC TRAINING

System Description
Outdoor Solution
Indoor Solution
Optional Kits
FP 1500
MCU

2
Cabinet types

Indoor site support cabinet


Indoor battery extension
Outdoor site cabinet with fan ventilation
Outdoor site cabinet with air-con cooling
Outdoor battery extension
Height variants:
1,3m
2m
Approvals:
NEBS approved
Non NEBS approved

3
Product Tree Eltek Outdoor
Outdoor
System

Flatpack PRSB 15kW/ Flatpack PRSB 15kW/ Rectifier


48V outd AC 2m 48V outd fan 2m FlatPack 1500 Options
CS7214000 CS7215000 CS7213300

LTE kit
2m outdoor cabinet with 2m outdoor cabinet with (PDU, 23-19 adapter)
airconditioning fans and filter CS7213700
CS7214001.00 CS7215001.00
BTS breaker
Power Core incl. Power Core incl. (3-pole 63A)
DC-distribution DC-distribution CS7213600
CS7213001.00 CS7213001.00
OVP 3-phase
Controller Unit Controller Unit
CS7213400
CS7213100.00 CS7213100.00
Battery shelf kit OD
Battery shelf kit OD Battery shelf kit OD (Batt tray, cabling, fuse)
(Batt tray, cabling, fuse) (Batt tray, cabling, fuse) CS7213800
CS7213800.00 CS7213800.00
Plinth kit
CS7213410
Temperature sensor Temperature sensor

CS7213900.00 CS7213900.00 Heater Kit


4 CS7213420
Description

Up to 10 Flatpack 1500 rectifiers (5 1U PR)


System voltage: 48 VDC
Input voltage:
Single 110 VAC
2 220 VAC L 110Vac + L 110Vac
3 208 VAC ( )
3 230 VAC ( )
3 400 VAC+N ( Y )
Output power 15 kW
Room for up to 4 battery shelves, 600Ah
Protection: Inside the rectifiers
Soft start
High voltage disconnect above 310 VAC

5
Outdoor Solution - Description

6
System Description
ve DC Load Terminals (BTS MCBs)
On top of each load breaker, 25 mm 2 (70 mm2)

ve Battery Terminals +ve DC Load Terminals


Bus bar, 35 mm2 Common positive bus bar, 70 mm2

+ve Battery Terminals


Common positive bus bar, 70 mm2

DC Earth (TE) terminal, M6

AC Earth (PE) terminal, M6

AC Mains Terminals

Terminals for GMT 10A Load+ FAN


Fuses, 1.5 mm 2

CON 5, Alarm Terminals


1.5 mm2 (Front access)

MCU Ctrl. Unit, and


7 CON 4, Monitoring Terminals
(Back MCU)
Outdoor Solution

Full aluminium
construction for extended
life time
Fan ventilation
IP 55 design cabinet
IP 54 after installation of
fan and filter
Operating temperature
-40C to +50C
Internal Heater
as optional kit

8
Outdoor Solution Top cover

TOP HAT:
Unlock from inside and
Lift to open.

Cable entries:
Drill a hole for each cable.

9
Outdoor solution AC input

CNG005/06 /3pcs

CNG005/07

CNG001/03

Din rail 180 mm

Cable Loom 105163

10
Internal AC Distribution

Remove cover to access

Possible configurations:
1 110V (L + N)
2 220V (L 110Vac + L 110Vac)
3 208Vac
3 230Vac
3 400Vac

Note: For 3 400Vac () connection


Please secure the NEUTRAL first.

L1, L2, L3, N from AC entry located on the top of the cabinet

11
Internal AC Distribution

12
Load & Battery Connections

13
Load & Battery Connections

14
Battery String Outdoor Kit

15
Load & Alarm Connections
8 load connections 10A max

GMT Fuses 1A to 10A

Alarms connections relays 1 to 6

16
Low Power Load Connections

17
Battery Termination

Battery breaker alarm


termination

Battery breaker location Max


4 per system (4 battery
Strings)

Temperature Cable

Black Cable is positive (+)


Blue Cable is Negative (-)

18
Ground Connection

Make your Ground connection here

Connection cable coming from AC load


Center. Usually provided by the
Utility company

All internal ground connections


Are factory ready.

19
Indoor cabinet Solution

2000 mm height
600 x 600 mm foot
print
IP 20
Adjustable feets
Standardized fixings
Easy access

20
Product Tree Eltek Indoor
Indoor
System

Flatpack PRSB 15kW/ Rectifier


48Vdc indoor 2m FlatPack 1500 Options
CS7213000 CS7213300

2m indoor cabinet BTS breaker


(3-pole 63A)
CS7213002.00 CS7213600
Power Core incl. OVP 3-phase
DC-distribution CS7213400
CS7213001.00

Controller Unit Battery shelf kit ID


(Batt tray, cabling, fuse)
CS7213100.00 CS7213200
Battery shelf kit ID
(Batt tray, cabling, fuse)
CS7213200.00

Temperature sensor

CS7213900.00

Cabinet front cover


21 CS7213500.00
Indoor cabinet Solution

22
Indoor Solution

23
Indoor Solution

All the connections are similar to


the outdoor solution cabinet
Cable entry on top of the cabinet
AC terminal located at the right
hand side of the cabinet

Load breakers and fuses

Alarms connections

24
Indoor solution AC input

25
Battery Termination

26
Ground Connection

Make your Ground connection here

27
Optional kits

Kit for 1 Battery


string + shelf
indoor

Kit for 1 Battery


bank + shelf
outdoor

28
Optional kits

Kit for Heater


Outdoor Cabinet

Control unit Heater Unit

29
System Schematics

30
Flatpack 1500

Maximum output power: 1500W


Input voltage: 85-310 Vac
Automatic disconnect at input voltages > 312 Vac
Output voltage: 48 Vdc
Efficiency: 91%
Output current: 31.25 Amps
Hold-up time: 20ms
Wide temp. range: -40C to 70C (-40F to +158F) without de-rating the output power
Dimensions: 214 x 243 x 41.5mm (8.8 x 9.8 x 1.64) (wxdxh)
Fan cooling; two-speed fan control
Vertical or horizontal mounting
Hot swap (output diode protection)
Automatic de-rating of output power at low input voltage and/or high ambient
temperatures
Easy and quick mounting and removal

31
Flatpack 1500

High power density (650mW/cm3)

Voltage Range ( 43 60 VDC )

Fan cooled, mounted horizontally in (1U height)

Mains input protected from under voltage, over voltage, and surge

Near unity power factor (>.99) and high efficiency (>90%) with Blocking diode

Operable in standalone mode or, controlled by MCU microprocessor control unit

CE marked, UL / CSA recognition. NEBS Level 3 Certified

System sizes up to 600 amperes

MTBF: > 213,600 hours Telcordia Issue I, method III (a)

32
Flatpack 1500
FP 1500
FP 700
The Rectifier will
Shutdown operation
when AC is Below
85 VAC

1600

1400

1200 The Rectifier will


Output Power (W)

disconnect itself from


1000 185 the AC source above
312 VAC
800

600
150
400

200
85 312
0
33 0 50 100 150 200 250 300 350
Input Voltage (VAC) Automatic reconnect at 300VAC
Flatpack 1500

The Rectifier will


Start to derate
output power at 70
C

1600
Maximum Available Power (Watts)

1400

1200

1000 The Rectifier will


Continue to output
800 power up to 95 C

600

400

200

0
34 60 65 70 75 80 85 90 95 100

Ambient Temperature (deg C)


Flatpack 1500
Flatpack Modularity Integrated Handle for Extraction

Handle Design
Hook-shaped for optimum grip
Easy rectifier extraction
Locks from view for finished look
Release Mechanism
Metal spring for positive handle ejection
Metal detent for positive handle retention
Durable and reliable

35
Flatpack 1500
Flatpack Front

LED Status Dual Fan Cooling Rectifier Model


Indicators Number

Output Current Output Voltage


Bargraph Adjustment Operational
36 Information
Flatpack 1500
Rectifier Mounting Shelves

Modular Configuration 48 VDC


60A Maximum Per Shelf
30A Redundant
With two rectifiers installed
37
Flatpack 1500
Rectifier Mounting Shelves
Universal mounting 19, ETSI (21), or 23 standards 1U Ea.

1.75

DIMENSIONS WEIGHT
Width: 439 mm (17.3) 2.4 kg (5.3 lbs) Per Shelf
Depth: 293 mm 8.0 kg (17.6 lbs) -
(11.55)
With two rectifiers installed
Height: 43 mm (1.75)

38
MCU Controller
Main Features
Hot Plug-in MCU unit
Front panel LCD and keypad for on-site service (local operation)
Menu driven operation via WinPower Silver
Battery monitoring and testing without site attendance (history up to 10
previous tests)
Advanced or simple battery test
System voltage: 24 VDC/ 48 VDC/ 60 VDC
Temperature Compensated Charge Voltage for increased battery lifetime
Slow current walk-in
Password protected access levels
Alarm/event log with time and date (up to 255 events)
Site text / ID for identification of each individual system
Battery Cable Voltage Drop Compensation
Battery Temperature Measurement
Output Voltage Measurement
Load Current Measurement
Battery Current Measurement
Rectifier Current Measurement
Load/Battery Disconnect
Real Time Clock
Battery Boost Charging
39
MCU Controller

Operating Temperature -20C - +55 C

RS-232 for PC connection or remote monitoring Modem / SNMP / TCP-IP


Up to 11 configurable alarm relay outputs for traditional remote monitoring
4 configurable digital inputs for monitoring of other equipment on site
Battery monitoring and testing (manual & automatic)
Windows based software for easy access and configuration (WinPower Silver)
Current limited Battery Recharge

40
MCU Controller

RS-232 LCD Status


Interface Display LEDs

Up & Enter
Down Select
Select

41
MCU Controller

Battery current limit [A] = 0.3*C10


Battery Current (A)

Float current

Mains OK Mains failure Mains OK, Recharge Mains OK

Load current

Mains

42
MCU Controller

55.5

55
Output Voltage [Vdc]

54.5

54
Slope

53.5

53

52.5
Min Comp, volt Max Comp, Volt
o
Temperature T [ C]

43
MCU Controller
Available Alarms
The following are standard alarm trigger events and can be mapped to the
available alarm relays.

High battery alarm 1


High battery alarm 2
Low battery alarm 1
Low battery alarm 2
LVD 1 (for load or battery disconnect)
LVD 2 (for load or battery disconnect)
LVD 3 (for load or battery disconnect)
Battery fuse alarm
Rectifier alarm (one rectifier failure)
Critical rectifier alarm
(More than one rectifier have failed)
Mains alarm
Battery test alarm
Battery pre-alarm
Battery fault alarm
Common alarm
Load fuse alarm
Symmetry alarm
High temperature alarm 1
High temperature alarm 2
44
MCU Controller
Winpower software interface
The software application must be installed on your PC. A
Com port must be free from use by other applications. A
Custom serial cable is required to interconnect from the
PC to the MCU See the illustration below for connection
details. Use the provided cable.
cable Set default Com port
settings to: Baud 9600, Bits 8, Parity None, Stop Bits 1,
Flow Control None.

45
MCU - controller
Options for remote monitoring & control
Potential free relays (6 or 11 form C contacts)
WinPower Silver through RS232
Modem with call-back functionality
SNMP
direct connection to TCP/IP network
connection using micro-wave
Web browser Adapter

46
MCU - controller
Web Browser Interface
TCP-IP protocol
Web Browser access
No special Software
Password protected
Output Voltage Control
Alarm Notification
Charge Current limited
System Capacity alarm
Multiple sessions

47

S-ar putea să vă placă și