Roofing

Chapter 6
ROOFS ARE CONSTRUCTED WITH THE PRIMARY
FUNCTION OF PROVIDING THE BUILDING OCCUPANTS
PROTECTION
Galvanized Iron Sheet
--G.I. SHEET IS EITHER:
PLAIN
CORRUGATED
G.I. SHEET is either:
PLAIN G.I. SHEET IS WIDELY USED FOR
ROOFING, GUTTER, FLASHING, DOWN SPOUT,
RIDGE, HIP ROLL AND MANY OTHER
TINSMITHING WORK.
STANDARD COMMERCIAL SIZE:
90cm x 240cm / 36 x 8

CORRUGATED G.I. SHEET IS COMMONLY


USED FOR ROOFING AND SIDING MATERIALS.
STANDARD COMMERCIAL SIZE:
80cm x 1.5m to 3.6m / 32 x 5to 12
5
32 12

LENGTH IN METERS AND FEET
STANDARD
GAUGE THICK WEIGTH OF GALVANIZED IRON SHEET
NO. CM. 1.5 M. 1.8 M. 2.1 M. 2.4 M. 2.7 M. 3.0 M. 3.60 M.
5 FT. IN KILOGRAMS
6 FT. 7 FT 8 FT. 9 FT. 10 FT. 12 FT.
14
GAUGE .203
THICK 22.36 26.83 LENGTH
31.30 IN METERS
35.78 AND FEET 44.72
40.25 53.66
1.5 M. 1.8 M. 2.1 M. 2.4 M. 2.7 M. 3.0 M. 3.60 M.
15NO. CM.
.180 20.25 24.30 28.35 32.40 36.45 40.50 48.60
5 FT. 6 FT. 7 FT 8 FT. 9 FT. 10 FT. 12 FT.
16 14 .163
.203 18.44
22.36 27.76
26.83 25.39 35.78
31.30 29.02 40.25
32.64 44.72
36.27 53.66
43.52
17 15 .180
.147 20.25
16.43 24.30
19.72 28.35
23.00 32.40
26.29 36.45
29.58 40.50
32.86 48.60
39.43
16 .163 18.44 27.76 25.39 29.02 32.64 36.27 43.52
18 .132 14.73 17.67 20.62 23.56 26.51 29.45 35.34
17 .147 16.43 19.72 23.00 26.29 29.58 32.86 39.43
19 18 .117
.132 13.03
14.73 15.63
17.67 18.24 23.56
20.62 20.84 26.51
23.45 29.45
26.05 35.34
31.27
20 19 .117
.102 13.03
11.32 15.63
13.58 18.24
15.85 20.84
18.11 23.45
20.38 26.05
22.64 31.27
27.17
20 .102 11.32 13.58 15.85 18.11 20.38 22.64 27.17
21 .094 10.43 12.52 14.60 16.69 18.78 20.86 25.03
21 .094 10.43 12.52 14.60 16.69 18.78 20.86 25.03
22 22 .086
.086 9.62
9.62 11.54
11.54 13.46 15.38
13.46 15.38 17.31
17.31 19.23
19.23 23.08
23.08
23 23 .079
.079 8.73
8.73 10.47
10.47 12.22
12.22 13.96
13.96 15.71
15.71 17.45
17.45 20.94
20.94
24 24 .071
.071 7.91
7.91 9.49
9.49 11.07
11.07 12.66
12.66 14.24
14.24 15.82
15.82 18.29
18.29
25 .064 7.03 8.43 9.84 11.24 12.65 14.05 16.86
25 26 .064
.056 7.03
6.19 8.43
7.43 9.84
8.66 11.24 11.14
9.90 12.65 12.38
14.05 14.86
16.86
26 27 .056
.051 6.19
5.76 7.43
6.91 8.66
8.06 9.90 10.37
9.22 11.14 11.52
12.38 13.82
14.86
27 28 .048
.051 5.33
5.76 6.39
6.91 7.46
8.06 8.52
9.22 9.59
10.37 10.65
11.52 12.78
13.82
29 .043 4.90 5.88 6.86 7.84 8.82 9.80 11.76
28 .048 5.33 6.39 7.46 8.52 9.59 10.65 12.78
30 .041 4.48 5.37 6.27 7.16 8.06 8.95 10.74
29 .043 4.90 5.88 6.86 7.84 8.82 9.80 11.76
THE THICKNESS OF GALVANIZED IRON SHEET IS
30 .041 4.48
MEASURED IN5.37
TERMS6.27 7.16 NUMBER
OF GAUGE 8.06 8.95 14 TO
FROM 10.74
BEFORE MAKING AN ESTIMATE OF
CORRUGATED G.I. ROOFING SHEETS, THE
FOLLOWING IMPORTANT DATA SHOULD BE
CONSIDERED FIRST.
1.Verify the specifications
for
a.) Side Lapping
1- corrugation
use 0.70m
2 corrugations
use 0.60m
b.) End Lapping
2. The length of G.I. sheet is proportionally
Standard joint; use
adjusted by the spacing of purlins
from 25-30 cm
(refer to table 6-2)
ex. In 1.5 m (5) the spacing of purlins i
0.60 m.

3. A good roofing design are those that


EFFECTIVE WIDTH
COVERING
NUMBER OF
SIDE LAPPING PURLINS
LENGTH NAILS OR
SPACING
FEET-METER RIVETS
CM.
1 2 PER SHEET

6 1.80 .70 .60 .75 .14

7 2.10 .70 .60 .60 .18

8 2.40 .70 .60 .70 .18

9 2.70 .70 .60 .60 .22

10 3.00 .70 .60 .67 .22

12 3.60 .70 .60 .66 .26

EFFECTIVE COVERING OF G.I. ROOFING SHEETS


PURLINS SPACING AND NUMBER OF
FASTENERS PER SHEET
Procedures in Estimating G.I. Roof
Sheet and its Accessories
Procedures in Estimating G.I. Roof Sheet and its
Accessories

1.Determine
the number of sheets per row:

2. Determine the combination of roofing sheets:

3. Find the number of order by the result in Step


1 of Step 2
NUMBER OF PIECES
MATERIALS
PER KILOGRAM

1. Find the number of rivets or G.I. ROOF NAILS 120

nails for total sheet G.I. RIVETS 180

G.I. WASHERS 126

Take note: LEAD WASHERS 75


QUANTITY OF ROOF ACCESSORIES IN
KILOGRAMS
UMBRELLA NAILS
120

NUMBER OF
SIZE OF SIZE OF G.I. STRAP
PURLINS STRAP IN ONE
INCHES INCHES PLAIN
2. To convert to kilogram refer to table 6- SHEET

3 2 X 3 1 X 9 384

2 X 4 1 X 10 342

2 X 5 1 X 11 312

3. Solve the no. of plain G.I. sheets 2 X 6 SIZE AND


1 X 12 288
QUANTITY OF STRAPS IN
ONE PLAIN G.I. SHEET
required for anchor strap with the aid of

table 6-4
SOLUTION

A. Corrugated G.I. Sheet
C. G.I. Washers
1.Dividethelengthofthegutterbythe
effectivecoveringofonesheet.RefertoTable6-2 1.Doublethenumberofrivets;
under1corrugationthevalueis.70. 960x2=1,920pcs.
Divide:
14.00m.=20sheetsinonerow 2.Converttokilograms.RefertoTable6-3forG.I.washers
70 Divide: SUMMARY
1,920=15.24say15.5kilograms
2.Thelengthoftherafteris6.00meters.Thus, 126
acombinationof3.60m.and2.70m.longG.I. 20 pcs. 32 x 12 ft. corr
Sheetor12ft.x9ft. D. Plain G.I. Strap on 2 x 3 Purlins sheet
Order:
20pcs.32x12corrugatedG.I.sheetand 3.Totalnumberofrivets=960pieces
20 pcs. 32 x 9
20pcs.32x9corrugatedG.I.sheet 5.5 kg. G.I. rive
15.5 kg. G.I. was
2.RefertoTable6-4.Usinga2x3purlins,
B. Rivets Divide:
960=2.5piecesplainG.I.sheet 13.0 kg. lead was
3.RefertoTable6-2.Fora12ft.and9ft.long 384 2.5 pcs. plain G.I. s
roofsheet,
Multiply: E. Lead Washers
For12ft.long:20x26=520pieces
For9ft.long:20x22=440 4.Thenumberofrivetsisthenumberofleadwasher=960
Totalrivets.960pieces
2.RefertoTable6-3Forleadwashers;
2.Converttokilograms.RefertoTable6-3, Divide:
Divide: 960=12.8say13kilograms
9.60pieces=5.3say5.5kilograms 75
180
SOLUTION

A. Corrugated G.I. Sheets B. Umbrella Nails



Determine the number of roof sheet. Determine the number of umbrella
Refer to Table 6-2, Using 2 nails for the 12 ft. and 9 ft. roof
corrugations; sheets. Refer to Table 6-2;
Divide: Multiply :
18.00 m = 30 pcs. 60 pcs. of 1 ft. x 26 = 1,560 pieces
.60 60 pcs. of 9 ft. x 22 = 1,320 pieces
Total...2,880 pieces
The length of the rafter is 6.00
meters or a combination of 3.60 and Convert to kilograms. Refer to
2.70 meters. (12 and 9) roof sheet Table 6-3;
(see Table 6-5) multiply each sheet Divide:
length by the result of step -1. 2,880 = 24 kilograms of umbrella nail
120
30 pcs. 32 x 12 ft. and
30 pcs. 32 x 9 ft. G.I. roof sheets.

Take note that this is only one side


of the roof. For two sides, double the
quantity.
2 x 30 = 60 pcs x 32 x 12 ft
A. Corrugated G.I. Sheet

1.Determinethenumberofroofsheet.RefertoTable6-2;
Divide:
12.90m.=21.5say22pcs.
.60

2.Determinethelengthoftherafter=4.80m.or16ft.RefertoTable6-5.For16ft.itrequiresacombinationof10ft.
and7ft.or9ft.and8ft.Thus,Order:
22pcs.of32x10ft.and
22pcs.of32x7ft.roofingsheets

3.Again,takenotethatthisisonlyforonesideoftheroof.Toincludetheotherside,doublethequantity.
2x22=44pcs.of32x9and
2x22=44pcsof32x8roofsheets.

B. Roof Nails and Lead Washers

4.Solveforthequantityofroofnails.RefertoTable6-2;
For3.00m.(10ft.)sheet:44x22=968pcs.
For2.10m.(7ft.)sheet:44x18=792pcs.
Totalroofnails1,760pcs

2.Convert1,760pcs.intokilograms.RefertoTable6-3;
Divide:
1,760=14.7say15kilosG.I.roofnails
120

1760=23.5say24kilosleadwashers.
75
SOLUTION

A. Roofing Sheets B. G.I. Rivets



Determine the number of roofing sheet in one row along Determine the number of rivets. Refer to Table 6-2;
the 18.00 m. length of the gutter. Refer to Table 6-2 for 2 Multiply:
- side lap corrugation. For 12 ft. sheet: 60 x 26 = 1,560 pcs.
Divide: For 9 ft. sheet: 60 x 22 = 1,320 pcs.
18.00 m. = 30 pcs. Total number of rivets2,880 pcs.
.60
Convert to kilograms: Refer to Table 6-3;
Determine the length of the rafter. For a 6.00 meters Divide:
long, choose a combination of 12 ft. and ft. roof sheet. 2,880 = 16 kilograms
See Table 6-5, 180
C. G.I. and Lead Washers
30 pcs. of 32 x 12 ft. and
30 pcs. of 32 x 9 ft. corrugated G.I. sheet Double the number of rivets = 2880 x 2 = 5,760 pcs.
Refer to Table 6-3,
Take note that the above quantity is only for one side of Divide:
the roof. To include the other side double the quantity. 5760 = 45.7 say 46 kilograms
2 x 30 = 60 pcs. 12 ft. and 126
2 x 30 = 60 pcs. 9 ft. roofing sheets
Lead washer is the same number as the rivets. Refer to
Considering that the roof is a hipped type, wastage on Table 6-3
cutting can not be avoided, hence add 5% allowance if Divide:
the angle of the hip is 45 and 10 if not 45. The 2,880 pcs. = 38.4 say 39 kilograms
percentage allowance shall be multiplied to the total 75
number of sheets. Get a longer sheet to avoid excessive
waste in cutting. Thus, D. Plain G.I. Anchor Strap

60 + 60 = 120 pcs. x 5% = 6 pcs. of 12 ft. Refer to Table 6-4. The Size of G.I. strap on a 2 x 4
purlins is 1" x 10" .
Order : 66 pcs. 32 x 12 ft. and
60 pcs. 32 x 9 ft. corrugated G.I. sheets Number of strap is equal to the number of rivets =
2,880.
Solve for the number of plain sheet. Refer to Table 6-4.
Divide:
Gutter, Flashing, Ridge, Hipped and Valley Roll

TINSMITHING WORK
THE PRIMARY CONSIDERATION IN TINSMITHING WORK IS
ECONOMY WHICH SIMPLY MEAN:
TO UTILIZE EVERY INCH OF THE TIN SHEET.
Estimating Procedures :

1.Determine the total length of the gutter


in meter.
2.Divide this length by 2.35 meter to find
the number of gutter required. (2.35 m.
is the effective length of one gutter.)
3.Find the total width of one gutter. ( see
the detailed plan.)
4.Divide .90 meter (36 inches width of
one plain G.I. sheets by the result of
step-3 to find out how many gutter
could be made out from one plain G.I.
sheet. The fractional value or extra cut
will be reserved for other smaller parts.
5.Divide the result of step-2 by the result
of step-4. the result is the required
number of G.I. sheets.
SOLUTION

Find the total length of the


gutter. This 37.5 centimeters excess cut from
one plain G.I. sheet could be set aside
Length = 2 (18.00 ) + 2 momentarily to be considered in
( 10.00 ) making other roof accessories such as
= 36.00 + 20.00 flashing, downspout, anchor strap for
L = 56.00 meters. riveting etc. Thus, only one gutter at
2.40 m (8 ft.) long could be made out
Divide the length by 2.35 from one plain G.I sheet.
meters the effective length of
one gutter. Therefore, order :

56.00 = 23.82 say 24 pcs. 24 pcs. 90 cm. x 240 cm.(36 x 8 ft.)
2.35 Plain G.I. sheet.

The total width of the gutter is


52.5 centimeters (see cross
section of gutter). Subtract 52.5
from 90 centimeters the
standard width of one plain G.I
sheet.
EFFECTIVE LENGTH IN
ITEM
METERS
GUTTER 2.35
FLASHING 2.30
RIDGE ROLL 2.20
VALLEY ROLL 2.30
HIPPED ROLL 2.20
BAR (.25) PER SOLDER
SOLDERING LEAD
JOINT
MORIATIC ACID 10 CC PER SOLDERING LEAD

ROOF ACCESSORIES

COMMERCIAL SIZE
EFFECTIVE WIDTH COVERING
CORRUGATION
IN. / FT. METER

1 2
26 X 8 .650 X 2.40 .46 M. .31 M.
29 X 8 .725 X 2.40 .53 M. .38 M.

CORRUGATED PLASTIC ROOF


SHEET
SOLUTION 9 pcs. = 4.5 say 5 pcs. plain G.I.
sheet
A. ) Gutter 2

Find the total length of the roof B.) Flashing
gutter. From Figure 6-8, the total
length is =20 meters. Determine the total length of the
flashing. From Figure 6-8,
Refer to Table 6-6. Divide this length Multiply:
by the effective length of one gutter. 4 x 4.50 m. = 18 meters

20 m = 8.5 say 9 pcs. gutter Find the number of flashing. Refer to
2.35 Table 6-6;
Divide :
Determine the total width of one 18 m. = 7.8 say 8 pcs.
gutter. From Figure 6-8, the total 2.30
width is = 45 cm. Divide the width of
the plain G.I. sheet by 45 cm. Width of plain G.I. sheet divided by
width of flashing
90 cm.= 2 pcs 90 cm = 2 pcs. of flashing in one plain
45 G.I. sheet
45
This simply mean that 2 pcs. gutter
could be made out from one plain G.I. Divide the result of step 2 by step 3.
sheet. Thus, divide the result of step to find the number of plain sheet
C.) Ridge Roll

Find the total length of the ridge roll


= 10 meters.
Refer to Table 6-6, for ridge roll;
Divide :

10.00 m. = 4.5 pcs. ridge roll


2.20 Summary

Determine how many ridge roll can For Gutter ; 5 pcs. 90 cm. x
be made out from one plain G.I sheet. 240 cm. plain G.I. sheet
Flashing ; 4 pcs. 90 cm.
90 cm. = 2 pcs. x 240 cm. plain G.I. sheet
45 cm. Ridge Roll ; 2 pcs. 90 cm. x
240 cm. plain G.I. sheet
Divide step- 1 by step 2 tofind the Total ; 11 pcs. plain
number of plain G.I. sheet required. G.I. sheets

4.5= 2.25

Order 2 pcs. .90 m x 2.40 m. (36 x


8) plain G.I. sheet. Get the balance of
.25 from the excess cut of gutter.

Asbestos Roofing
DIFFERENT KINDS OF ASBESTOS
ROOFING
1. STANDARD CORRUGATED SHEET
2. 4-V CORRUGATED SHEET
3. KANALETAS
4. PLACA ROMANA
5. TENCOR CORRUGATED SHEET
6. ARDEX LIGHTWEIGHT CORRUGATED SHEET
Estimating Procedures:

1. The number of corrugated asbestos roofing is


determined by dividing the gutter length by
the effective width covering of one sheet.
2. In finding the number of flashing, gutter,
ridge, hip and valley roll, divide the total
length by the effective length of the
accessories.
3. Other parts such as ridge end cap, apron
flashing, gutter corner, down spout and
fittings are determine by direct counting.
They are already made according to factory
standard sizes.
SOLUTION
D.) Flashing
A.) Standard Corrugated Sheet

1.Findthetotallengthoftheflashing(seefigure)
1.Findthetotallengthofthegutter.

2x26.00m.=52.00meters. 3.00m.x4sides=12meters

2.RefertoTable6-8.Divide52.00metersbytheeffective 2.RefertoTable6-8,Foroutsideflashing
widthofonesheet: Divide:

52.00m.=62pcs.standardasbestossheet.
12.00m=5.25say6pcs.outsideflashing
.838
2.286
B.) Gutter
E.) Ridge End Cap
1.Thetotallengthoftheridgerollis=26.00m.Referto
Table6-8,dividebytheeffectivelengthofgutter. 1.FromFigure6-9byactualcount,thereare2
piecesridgeendcap.Thus,order2pcs.
2x26.00m.=22.26pcs.
2.336m.

C.) Ridge Roll

1.Thetotallengthoftheridgeis=26.00meters.Referto
Table6-8forridgeroll.
Divide:
Summary
26.00m.=31.0ridgeroll
62pcs.1.20x3.00Standardcorrugatedsheet
.838 23pcs.standardgutter
31pcs.standardridgeroll
6pcs.standardflashing
TECHNICAL DATA FOR ESTIMATING ASBESTOS ROOFING

1.20 X 3.00
LENGTH
M.
END LAPPING : BELOW 20 DEGREES .30 M.
ABOVE 20 DEGREES .15 M.
EFFECTIVE WIDTH .838 M.
RIDGE ROLL EFFECTIVE LENGTH .838 M.
GUTTER EFFECTIVE LENGTH 2.336 M.
OUTSIDE FLASHING 2.286 M.
HIP ROLL 1.676 M.

STANDARD CORRUGATED SHEETS



CORRUGATED SHEET
TECHNICAL DATA
STANDARD LENGTH 2.438 METERS
EFFECTIVE WIDTH .965 METERS

RIDGE ROLL EFFECTIVE LENGTH .965 METERS


OUTSIDE FLASHING EFFECTIVE 2.286 METERS
LENGTH
KANALETAS

LENGTH IN
ITEM
METERS
LENGTH 7.315 M.
EFFECTIVE WIDTH .885 M.
EAVES FLASHING .885 M.
OUTSIDE FLASHING EFFECTIVE LENGTH 2.40 TO 3.00 M.
PLACA ROMANA
ITEM
LENGTH IN
METERS
STANDARD LENGTH .812 METERS
EFFECTIVE LENGTH .600 METERS
STANDARD WIDTH 1.180 METERS
EFFECTIVE LENGTH 1.100 METERS
END LAP .200 METERS
SIDE LAP .080 METERS
RIDGE ROLL EFFECTIVE LENGTH 1.100 METERS
OUTSIDE FLASHING EFFECTIVE LENGTH 2.286 METERS
RIDGE FLASHING EFFECTIVE LENGTH 1.100 METERS
EAVES FLASHING EFFECTIVE LENGTH 1.100 METERS
TENCOR CORRUGATED SHEET
ITEMS LENGTH IN METERS
STANDARD LENGTH
LAPPING
2.44 M.
.15 OR .30 M.
EFFECTIVE LENGTH 2.29 OR 2.14 M.
STANDARD WIDTH .748 M.
EFFECTIVE WIDTH .675 M.
OUTSIDE FLASHING 1.50 TO 3.00 M.
MINUS LAPPING .15 M.
RIDGE ROLL .953 M.
ARDEX CORRUGATED SHEET
MEASUREMENT
ITEM
STANDARD SUPER
STANDARD WIDTH .52 M. 1.05 M.
EFFECTIVE WIDTH .45 M. .97 M
NOMINAL LENGTH .75 TO 3.15 M. 2.40 TO 3.60 M.
RIDGE ROLL EFFECTIVE
.95 M. .95 M.
LENGTH
OUTSIDE FLASHING 1.50 TO 2.00 M. 1.50 TO 3.00 M.
SIDE LAPPING .15 M. .15 M.
COLORBOND KLIP-LOK
is a corrosion resistant zinc coated steel sheet prepainted steel ribbed
tray roofing and walling with the following special features.
1. Concealed fastening
2. Lock action rib design
3. Attractive fluted rays
4. Near flat roof slopes
5. Less supports-wider spaced
6. Strong lightweight steel
7. Custom cut long lengths
Colorbond Klip-lok
STEEL BASE THICKNESS 0.60 MM

TOTAL COATED THICKNESS 0.63 MM

WEIGHT PER METER LENGTH OF PANEL 2.66 KG.

WEIGHT PER COVERED AREA 6.55 KG / M

LENGTH AVAILABLE UP TO 15 METERS


LONGER LENGTH THROUGH SPECIAL ORDER UP
35 METERS
TO
OVERALL WIDTH .427 M.

EFFECTIVE WIDTH COVERAGE .406 M.


RECOMMENDED FASTENERS
(TWO FASTENERS REQUIRED PER
CLIP)
FASTENING OVER
SUPPORT MEMBER NORMAL FASTENING INSULATION UP TO 100 MM
(4)
STEEL UP TO 3/32 (2.5MM) NO. 10-16 X 5/8 WAFER HEAD SELF NO. 10-16 X 7/8 (22 MM) WAFER HEAD
THICK DRILLING AND TAPPING SCREW SELF DRILLING AND TAPPING SCREW

STEEL 3/32 TO 3/16 2.5 5 MM NO. 10-24 X 5/8 WAFER HEAD SELF NO. 10-24 X 7/8 (22 MM) WAFER HEAD
THICK DRILLING AND TAPPING SCREW SELF DRILLING AND TAPPING SCREW

NO. 10-24 X 7/8 (22 MM) HOLE FOR NO.


NO. 10-24 X 5/8 WAFER HEAD THREAD
STEEL OVER 3/16 (5MM THICK) 10-24 X 7/8 WAFER HEAD SELF
CUTTING SCREW. DRILL 4.5 MM
DRILLING AND TAPPING SCREW

2 X 9 G (50 X 3.75 MM) COUNTER 2 1/2 X 9 G (60 X 3.75 MM) COUNTER


SUNK HEAD G.I. SPIRAL NAIL OR NO. 10- SUNK HEAD G.I. SPIRAL NAIL OR NO. 10
HARDWOOD
12 X 1 (25 MM) TYPE 17 WAFER HEAD 12 X 1 3/4 (45 MM) TYPE 17 WAFER
SELF DRILLING WOOD SCREW HEAD SELF DRILLING WOOD SCREW

NO.10-12 X 1 3/4 (45MM) TYPE 17


NO. 10-12 X 1 3/4 TYPE 17 WAFER
SOFTWOOD WAFER HEAD SELF DRILLING WOOD
HEAD SELF DRILLING WOOD SCREW
SCREW
BANAWE HORIZONTAL METAL
TILE
Technical Data
NOMINAL WIDTH .228 M.

EFFECTIVE WIDTH COVERAGE .204 M.

LENGTH 12.19 M.

MINIMUM ROOF SLOPE 15 DEGREES


MARCELO ROOFING
SYSTEM
Technical Data
WIDTH 1.14 M.
LENGTH 1.11 M.
EFFECTIVE WIDTH COVERAGE .95 M.
EFFECTIVE AREA COVERAGE PER
.92 SQ. M.
SHEET
NUMBER OF FASTENER PER SHEET
15 PCS. PER SHEET
FIRST ROW
SUCCEEDING ROWS 10 PCS. PER SHEET
AVERAGE NO. OF FASTENERS PER
12 PCS. PER SHEET
SHEET
COLORBOND
CUSTOM ORB
Technical Data

NORMAL WIDTH .86 M.


EFFECTIVE COVERAGE .76 M.
LENGTH 1.35 M.
LONGER LENGTH SPECIAL ORDER
MAXIMUM RECOMMENDED LENGTH
FOR
CONTINUOUS SHEET WITHOUT
EXPANSION JOINTS 24 M.
MILANO LONGSPAN STEEL
BRICKS
Technical Data
STEEL BASE THICKNESS
0.40 MM.
(NO. 26)
TOTAL COATED THICKNESS 0.46 MM
WEIGHT PER SQ. M. 4.53 KG.
WEIGHT PER LENGTH 3.44 KG.
EFFECTIVE COVERAGE 0.67 M.
LENGTH UP TO 6.00 M.
LONGER LENGTH SPECIAL ORDER
RECOMMENDED ROOF
10 MIN.
SLOPE
COLORBOND TREMDEX
HI-TEN
Technical Data
STEEL BASE THICKNESS 0.40 M.

TOTAL COATED THICKNESS 0.46 M.

WEIGHT
PER UNIT AREA 4.28 KG. / SQ. M.

PER UNIT LENGTH 3.26 KG. / SQ. M.


NORMAL WIDTH 0.83 M.
EFFECTIVE WIDTH
0.76M.
COVERAGE
AVAILABLE LENGTH UP TO 15 M.
LONGER LENGTH SPECIAL ORDER
MINIMUM SLOPE
SINGLE SHEET 3 DEGREES
ROOF WITH END LAP 5 DEGREES
Fasteners :
For Hardwood: Use Type 17 self drilling
wood screw No. 12 x 50 mm. hexagonal
head with neoprene washer.
For Softwood: Add 12 mm to length of
screw.
There should be four fasteners per
sheet at all supports.
For side lap fastener, use Type S point
self drilling screw No. 10 x 16 mm.
hexagonal head with neoprene washers.
Teks self drilling screw to steel support
up to 4.5 mm. thick use No. 12 x 45
BRICK TILE ROOFING
Technical Data :
WEIGHT PER PLACE
DESCRIPTION NUMBER REQUIRED
IN KILOGRAMS
MARCEILLE TYPE (FLAT) 3.60 14.0 PER SQ. M.
ONDULA TYPE (WAVY) 4.00 15.0 PER SQ. M.
SR. ( STANDARD RIDGE) 2.80 2.5 PER LN. M.
HALF MARCEILLE 2.00 1.0 PER LN. M.
JRT 1 3.00 13.0 PER SQ. M.
JRT 2 3.75 4.0 PER SQ. M.
JRT 3 3.20 1.0 PER LN. M.
JRT 4 3.20 1.0 PER LN. M.
JRT 5 2.20 4.0 PER LN. M.
SRT 1 4.00 13.0 PER SQ. M.
SRT 2 2.20 1.0 PER LN. M.
SRT L 2.25 1.0 PER LN. M.
SRT R 2.25 1.0 PER LN. M.
JSR 1 2.00 1.0 PER LN. M.
JSR 2 3.00 4.0 PER LN. M.
SRT U 1.75 25.0 PER SQ. M.
SRT T 1.50 25.0 PER SQ. M.