Columns:

Are compression members which are subjected to concentric axial


compressive forces. These are to be found in trusses and as a lateral
bracing members in frame building. Short columns are sometimes
referred to as to as struts or stanchions.
P
Beam-Columns:
Are members subjected to combined axial compressive
and bending stresses; These are found in single storey
of multi-storey framed structures. These are treated
independently in this course (chap. 12 in your text book). P

Columns Theory:
Stocky columns (short) fail by yielding of the material at
the cross section, but most columns fail by buckling at P P
loads for less then yielding forces. (a) (b)
C-1
For slender columns, Euler (1759) predicted the critical buckling load (P cr)
also known as Euler Buckling Load as:
Pcr
2 EI
Pcr 2 (C 1)
L
where: E = Young Modulus of Elasticity.
I = Minor moment of Inertia.
L = Unbraced length of column.

Derivation of Euler Buckling Load: y y


2
d y M
2
Pcr Pcr x
dx EI
P x
y" cr y 0 L
EI
where:
Solution of this differential equation:
Pcr
y = A cos (cx) + B sin (cx) c , A and B are constants.
EI C-2
From boundary conditions:
y = 0 @ x = 0, and
y = 0 @ x = L, we get (A = 0) and (B sin cL = 0)

if B 0, then cL = n where n = 0, 1, 2, 3

cL =
Note: The critical buckling load
Pcr
L is a function of the section
EI
2EI properties (A, L, r) and
Pcr 2 ---- Euler Buckling Critical Load
L the modulus of elasticity
2E Ar 2
for material, and is not a
L2 where: r = minor radius of gyration
2EA function of the strength or

L / r 2 grade of the material.
2
Pcr E
Fcr (C 2)
Ag L
r
2

C-3
Example C-1
Find the critical buckling load for W 12 x 50, supported in a pinned-pinned
condition, and has an over-all length of 20 feet?

Solution:
2E
Fcr
Lr 2
rmin = ry = 1.96 inch (properties of section).

2 29000
Fcr 19 ksi

2012 2
1.96
Pcr = Fcr A = 19.1 x 14.7 = 280.8 kips
Note:
The steel grade is not a factor affecting buckling,
also note Fcr << Fy.
C-4
For short (stocky) columns; Equation (C-2) gives high values for
(Fcr), sometimes greater then proportional limit, Engessor (1889)
proposed to use (Et) instead of (E) in Euler formula:
2 Et I
Pcr 2
(C 3)
L
where:
Et = Tangent Modulus of Elasticity
Et < E
When (Fcr) exceeds (Fpl), this is called
Inelastic Buckling, constantly variable
(Et) need to be used to predict (Fcr)
in the inelastic zone.
Shanley (1947), resolved this inconsistency.
C-5
Depending on (L/r) value the column buckling
strength was presented as shown by Shanley.

Residual Stresses:-
Due to uneven cooling of hot-rolled sections,
residual stresses develop as seen here.

The presence of residual stresses in almost all


hot-rolled sections further complicates the issue
of elastic buckling and leads towards inelastic
buckling.

C-6
The Euler buckling formula (C-1) is based on:
where:
1 Perfectly straight column. (no crookedness).
K = Effective length factor.
2 Load is concentric (no eccentricity).
(Kl) = Effective length.
3 Column is pinned on both ends.
(Kl/r) = Effective slenderness ratio.
The Previous conditions are
very difficult to achieve in a realistic
building condition, especially the free
rotation of pinned ends. Thus an
effective slenderness factor is
introduced to account for various end
conditions:
Thus:
2E 2E t
Fcr , or Fcr C 4
KL r 2 Klr 2
see commentary
(C C2.2) (page 16.1-240)
C-7
AISC (Chapter E) of LRFD code stipulates:
Pu (factored load) c Pn
where:
Pu = Sum of factored loads on column.
c = Resistance factor for compression = 0.90
Pn = Nominal compressive strength = Fcr Ag
Fcr = Critical buckling Stress. (E3 of LFRD)

a) for
Kl
4.71 E
Fy
or F e 0.44Fy
r
Fy

Fcr 0.658 Fe
Fy E - 3.2

b) for
Kl
4.71 E
Fy
or F e 0.44Fy
r
Fcr 0.877Fe E - 3.3
where:
2E
Fe E - 3.4

KL 2
r C-8
The above two equations of the LRFD
code can be illustrated as below:
where:

Kl Fy
c
r E

The code further stipulates


that an upper value for column
should not exceed (200).
For higher slenderness ratio,
Equation (E-3.3) controls and
(Fy) has no effect on (Fcr).

C-9
Example C-2
Determine the design compressive strength (cPn) of W 14x74 with an
untraced length of (20 ft), both ends are pinned, (A-36) steel is used?
Solution: Fy

Fcr 0.658 Fy (0.658)1.178 x 36
Fe

Kl =1 x 20 x 12 = 240 in
rmin = ry = 2.48 0.611 36 21.99 ksi
Kl 240
c Pn = 0.9 x Fcr x Ag = 0.9 x (21.99) x 21.8
96.77 200 (0k)
r 2.48
max.
= 433.44 kips (Answer)
2E 2 x2900
Fe 2
30.56 ksi
Kl (96.77) 2
Also from (table 4-22) LFRD Page 4-320
r
c Fcr = 19.75 ksi (by interpolation)
0.44 Fy = 0.44 x 36 =15.84 ksi c Pn = c Fcr Ag = 430.55 kips
Fe 0.44 Fy Equ. E-3.2 (much faster)
(controls) C-10
For must profiles used as column, the
buckling of thin elements in the section
may proceed the ever-all bucking of
the member as a whole, this is called
local bucking. To prevent local bucking
from accruing prior to total buckling.
AISC provides upper limits on width to
thickness ratios (known as b/t ratio) as
shown here.

See AISC (B4)


(Page 16.1-14)

See also:
Part 1 on properties
of various sections.
C-11
Depending on their ( b/t ) ratios (referred to as ) ,
sections are classified as:
a) Compact sections are those with flanges fully welded
(connected) to their web and their:
p (AISC B4)
b) Non compact Sections:
p r (B4)
c) Slender Section:
> r (B4)

Certain strength reduction factors (Q) are introduced for slender


members. (AISC E7). This part is not required as most section
selected are compact. C-12
Example C-3
Determine the design K x L x 1 x 24 x 12
54.55
compressive strength rx 5.28 (controls)
(c Pn) for W 12 x 65 K yLy 1 x 8 x 12
31.79
column shown below, ry 3.02
(Fy = 50 ksi)?
2E 2 x29000
Fe 96.2 ksi
Solution: Kl
2
(54.55) 2


r
A) By direct LRFD
Fe 0.44 Fy ( 22 ksi) Equ. (E 3.2)
From properties: 50

Ag =19.1 in2 Fcr 0.658 Fy 96.2


rx = 5.28 in
0.8045 x 50 40.225 ksi
ry = 3.02 in

c Pn = 0.9 x Fcr Ag = 0.9 x 40.225 x 19.1 = 691.5 kips C-13


B) From Table (4.22) LRFD
Kl
Evaluate = = 54.55
r max

Enter table 4.22 (page 4 318 LRFD)


cFc = 36.235 ksi (by interpolation)
Pn = Fc x Ag = 692.0 kips

C) From (Table 4.1 LRFD)


K xL x 1x24
(KL)y 13.7 ft
rx 1.75
ry
Enter table (4.1 ) page 4.17 LFRD with (KL)y = 13.7
Pn = 691.3 kips (by interpolation).
C-14
Example C-4 P P
Find the maximum load capacity C C

(Pn) of the W 14 x 53 (A-36) 10 ft.

column shown in figure ? 25 ft. B

15 ft.

Solution: A A

x
x-axis Lx = 25 ft, kx = 0.8, rx = 5.89 in. x x
x

y-axis
Section (AB) Ly = 15 ft, ky = 0.8, ry = 1.92 in.
Section (BC) Ly = 10 ft., ky = 1.0, ry = 1.92 in.
Kl 0.8 25 12
41 Enter table (4-22) , Fc = 24.1 ksi
r x 5.98
Kl
max
0.8 15 12 Column capacity Pn = Fcr Ag = 24.1 x 15.6 = 376 kips
75
r y 1.92 (controls)
C-15
Design with Columns Load Table (4) LFRD:-
A) Design with Column Load Table (4) LFRD:
The selection of an economical rolled shape to resist a given
compressive load is simple with the aid of the column load tables.
Enter the table with the effective length and move horizontally until
you find the desired design strength (or something slightly larger). In
some cases, Usually the category of shape (W, WT, etc.) will have
been decided upon in advance. Often the overall nominal
dimensions will also be known because of architectural or other
requirements. As pointed out earlier, all tabulated values correspond
to a slenderness ratio of 200 or less. The tabulated unsymmetrical
shapes the structural tees and the single and double-angles
require special consideration and are covered later.

C-16
EXAMPLE C - 5
A compression member is subjected to service loads of 165 kips dead load
and 535 kips live load. The member is 26 feet long and pinned in each end.
Use (A572 Gr 50) steel and select a W14 shape.

SOLUTION Calculate the factored load:


Pu = 1.2D + 1.6L = 1.2(165) + 1.6(535) = 1054 kips
Required design strength cPn = 1054 kips
From the column load table for KL = 26 ft, a W14 145
has design strength of 1230 kips.

ANSWER
Use a W14 145, But practically W14 132 is OK.

C-17
EXAMPLE C - 6
Select the lightest W-shape that can resists a factored compressive load P u of
190 kips. The effective length is 24 feet. Use ASTM A572 Grade 50 steel.
SOLUTION
The appropriate strategy here is to fined the lightest shape for each nominal
size and then choose the lightest overall. The choices are as follows.
W4, W5 and W6: None of the tabulated shape will work.
W8: W 8 58, cPn = 205 kips
W10: W10 49, cPn = 254 kips
W12: W12 53, cPn = 261 kips
W14: W14 61, cPn = 293 kips
Note that the load capacity is not proportional to the weight (or cross-
sectional area). Although the W8 58 has the smallest design strength of
the four choices, it is the second heaviest.
ANSWER Use a W10 49. C-18
Example C-7
Select the lightest W 10 section made of
A 572-Gr50 steel to resist a factored load
of (600 kips) ?
Solution:
Assume weak axis (y-y) controls buckling:
Enter design tables of AISC (Section 4) with KyLy = 9 ft.
Select W 10 x 54 (capacity = 625 k > 600 k OK)
Check strong axis buckling strength:

Enter table for W10 x 54 with (KL)eq. = 10.53 ft.


Capacity = 595.8 kips (by interpolation) N.G.
Select W10 x 60 capacity = 698 kips for KyLy = 9 ft.
capacity = 666 kips for (KL)eq. = 10.5 ft. C-19
B) Design for sections not from Column Load Tables:
For shapes not in the column load tables, a trial-and-error approach must be used.
The general procedure is to assume a shape and then compute its design strength. If
the strength is too small (unsafe) or too large (uneconomical), another trial must be
made. A systematic approach to making the trial selection is as follows.
1) Assume a value for the critical buckling stress Fcr. Examination of AISC Equations
E3-2 and E3-3 shows that the theoretically maximum value of Fcr is the yield stress Fy.

2) From the requirement that cPn Pu, let


Pu
A
cAgFcr Pu and g cFcr

3) Select a shape that satisfies this area requirement.


4) Compute Fcr and cPn for the trial shape.
5) Revise if necessary. If the design strength is very close to the required value,
the next tabulated size can be tried. Otherwise, repeat the entire procedure,
using the value of Fcr found for the current trial shape as a value for Step 1
6) Check local stability (check width-thickness ratios). Revise if necessary.
C-20
Example C-8
Select a W18 shape of A36 steel that can resist a factored load of 1054 kips.
The effective length KL is 26 feet.

Solution:
Try Fcr = 24 ksi (two-thirds of Fy):
Pu 1054
Required gA 48 . 8 in 2

c Fcr 0.9( 24)


Try W18 x 192:
Ag = 56.4 in2 > 48.8in2
KL 26(12)
111.8 200 (OK)
rmin 2.79

2E 2 x29000
Fe 22.9 ksi
2
Kl 111.8 2


r
Fe 0.44 Fy (15.84) LRFD Equ. E . 3.2 C-21
Fy

36

Fcr 0.658 Fe Fy 0.658 x36 0.532 x 36
22.9


18.64 ksi
cPn 0.9 A gFcr 0.9 x 56.4 x 18.64 943kips 1054 k
(N.G.)

Try Fcr 18.64 ksi (the value just computed for the W18 x 192) :
Pu 1054
Required A g 62.83 in2
cFcr 0.9(18.64)
Try W18 x 234 :
A g 68.8 in2 . 62.83 in 2
KL 26(12)
109.5 200 (OK)
rmin 2.85
C-22
2E 2 29000
Fe 23.87ksi
Klr 2 109.5 2

Fe 0.44Fy Use LFRD (Equ.E - 3.2)


Fy

36

Fcr 0.658 Fy 0.658 x 36 0.532 x 36 19.15 ksi


Fe 23.87


cPn 0.9 A gFcr 0.9 x 68.8 x 19.15 1185 kips 1054 k (OK)

This shape is not in the column load tables, so the width - thickness
ratios must be cheacked :
bf 95
2.8 15.8 (OK)
2t f 36
h 253
13.8 42.2 (OK)
tw 36

Answer Use a W18 x 234


C-23
The effective length factor (K) was introduced in page (C-7) for six ideal conditions,
these are not encountered in practical field conditions. LRFD commentary provides
both real conditions and standard ideal conditions (C-C2.2) (page 16.1-239 to 242)
Braced Frames: Unbraced Frames:
No lateral movement is allowed Lateral movement possible
(0.5 < K < 1.0) (sideway prevented) (1.0 < K < 20.0) (sideway allowed)

a) Diagonal
bracing

b) Shear Walls
(masonry,
reinforcement concrete
or steel plate)
C-24
Ic /L c where
GA
Ig /L g A is top of column
Ic /L c where
GB
Ig /L g B is bottom of column

* For fixed footing G = 1.0


* For pinned support G = 10.0 C-25
Example C 9:-
In the rigid frame shown below, Determine Kx for columns
(AB) & (BC). Knowing that all columns webs are in the plane.

Solution:

W12 x 96
12'
Column (AB): W24 x 55 W24 x 68
A

W12 x 120
Joint (A): 12'
W24 x 55 W24 x 68

Ic /L c B
GA

W12 x 120
Ig /L g 15'

833/12 1070/12 1586 C



1350/20 1830/18 169.2 20' 20' 18'

0.94

C-26
For joint B,:-
Ic /L c 1070/12 1070/15 160.5
G 0.95
Ig /L g 169.2 169.2

From the alignment chart for sideways uninhibited, with GA = 0.94 and GB = 0.95,
Kx = 1.3 for column AB.
Column (BC):

For joint B, as before,


G = 0.95
For joint C, at a pin connection the situation is analogous to that of a very
stiff column attached to infinitely flexible girders that is, girders of zero
stiffness. The ratio of column stiffness to girder stiffness would therefore
be infinite for a perfectly frictionless hinge. This end condition is only be
approximated in practice, so the discussion accompanying the alignment
chart recommends that G be taken as 10.0.
From the alignment chart with GA = 0.95 and GB = 10.0, Kx = 1.85 for column BC.
C-27
When an axially loaded compression member becomes unstable overall (that
is, not locally unstable), it can buckle in one of three ways, as shown in
figure.
1. Flexural buckling. We have considered this type of buckling up to now. It
is a deflection caused by bending, or flexure, about this axis corresponding
to the largest slenderness ratio (Figure a). This is usually the minor
principal axis the one with the smallest radius of gyration. Compression
members with any type of cross-sectional configuration can fail in this way.

2. Torsional buckling. This type of failure is caused by twisting about the


longitudinal axis of the member. It can occur only with doubly symmetrical
cross sections with very slender cross-sectional elements (Figure b).
Standard hot-rolled shapes are not susceptible to torsional buckling, but
members built up from thin plate elements may be and should be
investigated. The cruciform shape shown is particularly vulnerable to this
type of buckling. This shape can be fabricated from plates as shown in the
figure, or built up from four angles placed back to back.
C-28
3. Flexural-torsional buckling. This type of failure is caused by a combination
of flexural buckling and torsional buckling. The member bends and twists
simultaneously (Figure c). This type of failure can occur only with
unsymmetrical cross sections, both those with one axis of symmetry such
as channels, structural tees, double-angle shapes and equal-leg single angles
and those with no axis of symmetry, such as unequal-leg single angles.

The AISC Specification requires


an analysis of torsional or flexural-
torsional buckling when appropriate.
Section E3 of the Specification covers
double-angle and tee-shaped members,
and Appendix E3 provides a more
general approach that can be used for
any unsymmetrical shape.
C-29
When length exceeds requirements for
a single section, built-up compression
section are used as shown below:

The code provides details for built-up


section under LRFD EG.

C-30
Example C 10 :- Calculate the capacity of the built-up column shown below.
Lx = Ly = 25 ft, Kx = 1.6, Ky = 1.0 Fy = 42 ksi ?
Solution:-

Ixx 2 110 8x 21 (5 0.25) 2 440.5 in4
Iyy 27.25 7.35(5 0.953) 2

( 121 21 83 ) 298 in4
A g 2 7.35 4 22.70 in2
Ixx 440.5
rx 4.41 in
A 22.70
Iyy298.0 From table 4.22 page 4.321
ry 3.62 in
A 22.70 cFcr = 18.3 ksi
K xlx 1.6 25 12
108.84 (controls)
rx 4.41 Design Nominal Strength = cFcr Ag
K yl y 1.0 25 12 =18.3 x 22.70
82.90
ry 3.62 = 415.4 kips. C-31
The effective length factor (K) was introduced in page (C-7) for six ideal conditions,
these are not encountered in practical field conditions. LRFD commentary provides
both real conditions and standard ideal conditions (C-C2.2) (page 16.1-239 to 242)
Braced Frames: Unbraced Frames:
No lateral movement is allowed Lateral movement possible
(0.5 < K < 1.0) (sideway prevented) (1.0 < K < 20.0) (sideway allowed)

a) Diagonal
bracing

b) Shear Walls
(masonry,
reinforcement concrete
or steel plate)
C-23
Ic /L c where
GA
Ig /L g A is top of column
Ic /L c where
GB
Ig /L g B is bottom of column

* For fixed footing G = 1.0


* For pinned support G = 10.0 C-24
Example C 8 :-
In the rigid frame shown below, Determine Kx for columns
(AB) & (BC). Knowing that all columns webs are in the plane.

W12 x 120W12 x 120W12 x 96


Solution:
12'
Column (AB):
W24 x 55 W24 x 68
A
Joint (A):
12'
W24 x 55 W24 x 68
Ic /L c B
GA
Ig /L g 15'
833/12 1070/12 1586 C

1350/20 1830/18 169.2 20' 20' 18'
0.94

C-25
For joint B,:-
Ic /L c 1070/12 1070/15 160.5
G 0.95
Ig /L g 169.2 169.2

From the alignment chart for sideways uninhibited, with GA = 0.94 and GB = 0.95,
Kx = 1.3 for column AB.
Column (BC):

For joint B, as before,


G = 0.95
For joint C, at a pin connection the situation is analogous to that of a very
stiff column attached to infinitely flexible girders that is, girders of zero
stiffness. The ratio of column stiffness to girder stiffness would therefore
be infinite for a perfectly frictionless hinge. This end condition is only be
approximated in practice, so the discussion accompanying the alignment
chart recommends that G be taken as 10.0.
From the alignment chart with GA = 0.95 and GB = 10.0, Kx = 1.85 for column BC.
C-26