BOP-2 ESTRUTURA

Exit menu using : afterwards the name of the last-accessed menu


blinks at the screen.
Navigate between the menus
Confirm selection:
Navigate inside the menu:
BOP-2 EXEMPLO COMISSIONAMENTO RPIDO

Step Action Step Action`

1 Connect the drive unit to 7 Using choose YES and


power press to reset
2 The following message
appears after drive start-up 8 `BUSY` should appear on
(CU-BUSY) the screen. After
3 Initiate basic start-up by completion of the rest
pressing , indicator starts operation
flashing 9 P1300 is displayed and
4 Using (press 4 times): the drive can be
Configure SETUP Menu: set up

5 To set the drive into RESET Note:


mode, press It is generally recommended, to set the frequency
converter to factory settings (Reset) first, before
6 Press to activate the commissioning.
RESET

Page 2
BOP-2 EXEMPLO COMISSIONAMENTO RPIDO

Step Action Note:

10 Control mode: Step 10:


a Press
Set here: 2 - V/f control with parabolic
characteristic
10 Select control mode
b using, then press Step 11:
IEC: Select kW and 50 Hz
11 Motor standard IEC/NEMA: NEMA: Select e.g..: HP and 60 Hz
a PNmotor in [kW] and
fNMotor in [Hz]
Step 12:
11 Using ( ) select rated Enter the rated motor voltage
b frequency and [kW]/ [HP],
then press
12 Motor Rated Voltage
a 12

11
12 Set motor rated voltage using
b ( )

Page 3
BOP-2 EXEMPLO COMISSIONAMENTO RPIDO

Step Handlung Note:

13 Motor Rated Current Step 14:


a Press
Input in kW or HP, see Step 11

13 Set motor rated current Step 15:


b using ( ) then press Now that the Motor data is entered, continue with
Motor identification Step 16
14 Motor Rated Power:
a Press

14 Set motor rated power using


b ( ) then press

15 Motor Rated Speed


a Press
14 13
15 Select motor rated speed
b using ( ) then press 15

Page 4
BOP-2 EXEMPLO COMISSIONAMENTO RPIDO

Step Action
Step 16
16 Motor Identification
a Press The Motor Identification (Mot Id) is a procedure in
which the necessary parameters for a better and
more precise control are calculated.
16 Using ( ) select STIL
For the selected control mode (p1300 = 2) the
b ROT
Motor Identification is not necessary.

Page 5
BOP-2 EXEMPLO COMISSIONAMENTO RPIDO

Step Action Step 17


17 Interconnection Macro 12: Two-wire control with Method 1
a Press Factory setting for converters without PROFIBUS or
PROFINET interface.
17 Using ( ) select Makro
b Std ASP Terminal assignment:

18 Minimum speed:
a Press

18 Using ( ) set minimum


b speed

19 Ramp-up time
a Press

19 Using ( ) select ramp-


b up time

Page 6
BOP-2 EXEMPLO COMISSIONAMENTO RPIDO

Step Action Step 21


20 Ramp-down time After step 21 the application-specific adjustments
a Press are done.

21 Using ( ) select ramp- Step 22d


b down time
The basic setup is completed.

22 Completing quick
a commissioning
Press
22 Using ( ) select YES
b

22 c Wait