Sub-System Intertripping
ABB Switzerland Ltd - 1
17-09-16
Consists of
Busbar Replica
Based on switchyard topology
Which CTs are located within one protection
zone. (BBP/EFP).
Which breakers do belong to one protection
zone (BFP,Intertrip).
Which Lines/Transformers cannot be switched
off due to Breaker bypass or 11/2 Breaker.
Triplogic
ABB Switzerland Ltd - 2
17-09-16
Busbar Replica
17-09-16
Triplogic
17-09-16
Building up a Replica
Topological elements:
Busbar
Isolators,Sectionalizers
Circuit Breaker
CT
Coupler_CT
Buscouplers,Tie-Breaker
Feeder
Junctions
ABB Switzerland Ltd - 6
17-09-16
Building up a replica
Busbar
I
II
Close
d
Isolat
or
CB Open
Isolat
CT Junction or
ABB Switzerland Ltd - 7
17-09-16
Building up a replica
Junctions
Ordinary connections.
17-09-16
Building up a replica
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 11
Start at a
busbar
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 12
Open Isolator,
end of prot. zone
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 13
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 14
Open Isolator,
end of prot zone
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 15
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 16
Closed Isolator,
continue
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 17
Open Isolator,
end of prot. zone
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 18
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 19
Coupler Breaker,
end of prot. zone
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 20
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 21
Open Isolator
end of protection zone
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 22
Breaker / CT arrangement
return
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 23
I
II
ABB Switzerland Ltd - 24
Breaker / CT arrangement
end of prot. zone
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 25
Coupler Breaker,
assigned 2nd time
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 26
Assign according CT
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 27
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 28
I
II
ABB Switzerland Ltd - 29
17-09-16
Building up a replica : Double Busbar
I
II
ABB Switzerland Ltd - 30
I
II
assigned ,
replica is updated/ready
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 32
Start at a busbar
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 33
Coupler Breaker,
end of prot. zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 34
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 35
Coupler Breaker,
end of prot. zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 36
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 37
Coupler Breaker,
end of prot. zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 38
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 39
Coupler Breaker,
end of prot. zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 40
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 41
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 42
Coupler Breaker,
end of prot. zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 43
Coupler Breaker,
assigned 2nd time
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 44
Assign according CT
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 45
Open Isolator,
end of protection zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 46
repeat procedure
for the next busbar
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 47
Coupler Breaker,
assigned 2nd time
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 48
Assign according CT
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 49
Coupler Breaker,
assigned 2nd time
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 50
Assign according CT
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 51
Feeder Node,
end of protection zone
17-09-16
Building up a replica : 1 1/2 Breaker
I
II
ABB Switzerland Ltd - 52
17-09-16
Dependencies
17-09-16
Dependencies
Busbar Protection:
Gets information which CT measurements are
located in one protection zone and should be
evaluated for the BBP algorithm.
Indicates which protection zone should trip due
to a busbar fault.
ABB Switzerland Ltd - 55
17-09-16
Dependencies
Breaker Failure:
After a breaker has the trip failed executing
command, the BFP will initiate an intertrip to the
associated protection zone.
A trip command initiated by the intertrip will
start the BFP function.
End-Fault:
A fault between an open Breaker and a CT
initiates an intertrip to the associated protection
zone.
ABB Switzerland Ltd - 56
17-09-16
Dependencies
External Protection:
Ext Tripping per Busbar (CU)
Ext. Tripping per Feeder (BU)
Transfer trip :
Due to a bypass of a CB
Feeder without a CB
ABB Switzerland Ltd - 57
17-09-16
Dependencies ITT/Replica Overview
CU Trip
ITT BBP
EXT
BU
BFP Trip
EFP BBP
ABB Switzerland Ltd - 58
EXT OCP
17-09-16
Intertripping (ITT)
Trip_Prot_Zone BBP
Prot_Zone_Of_CT
ITT BFP_Intert BFP
rip
EFP_Intertrip
EFP
one
EXT_CU
EXT_BU
17-09-16
ABB Switzerland Ltd - 60
17-09-16
REB500
The End !