Sunteți pe pagina 1din 9

Protection Application Bus PT selection

Handbook scheme
ABB Group - 1 -
15-Sep-17
Bus PT selection scheme

BUS-I

BUS-II

89A 89B
PT-I PT-II
ABB Group - 2 -
15-Sep-17
Bus PT selection scheme

FOR FFR

V1 V2 V2 V1
A

B
FOR DISTANCE RELAY
C
VN VL

OPEN DELTA VOLTAGE

PT SUPPLY FROM BUS-I


ABB Group - 3 -
15-Sep-17
Bus PT selection scheme

OPEN DELTA VOLTAGE

VN VL V2 V1
V1 V2
A

B FOR FFR

FOR DISTANCE RELAY

PT SUPPLY FROM BUS-II


ABB Group - 4 -
15-Sep-17
Bus PT selection scheme

BUS-II
BUS-I
INT-1
INT-2
VR1

FOR FFR VY1 TO FFR


[PT-I]
VB1

VR2

VY2 TO DIST. RELAY


FOR DIST. RELAY
[PT-I] VB2

VN

V
TO E/F RELAY
OPEN DELTA
VOLTAGE [PT-I] Vo

FOR FFR
[PT-II]

FOR DIST. RELAY


[PT-I]

OPEN DELTA
VOLTAGE [PT-II]

VR

VY
METERING CORE
TO METERING
[PT-I] VB

VN

METERING CORE
[PT-II]
ABB Group - 5 -
15-Sep-17

TO BLOCK DIST. RELAY


Bus PT selection scheme
ISOLATOR-BUS-I
+M -M
89a
121 122

89b

211 212

R
113 114
Y
FOR FFR TO FFR
115 116
B
223 224
VR1
225 226
VY1
FROM BUS FOR DIST. 317 318 TO DIST.
PT-I RELAY VB1 RELAY
315 316
VN

V
OPEN DELTA 313 314 TO E/F
VOLTAGE Vo RELAY
311 312

427 428
FOR METERING
CORE 425 426
423 424

221 222
ISOLATOR-BUS-II TO BLOCK
DIST. RELAY 227 228

89a
117 118 121 122

89b

211 212

113 114
FOR FFR
115 116

223 224

225 226
FROM BUS FOR DIST. 317 318
PT-II RELAY
315 316

OPEN DELTA 313 314


VOLTAGE
311 312

427 428
FOR METERING
CORE 425 426
423 424
ABB Group - 6 -

117 118

221 222
TO BLOCK
227 228 DIST. RELAY
15-Sep-17
Bus PT selection scheme
89A (MAIN BUS-I ISO)
+M -M
89a
121 122

89b

211 212 VR1


113 114
89C (TRANSFER BUS ISO) VY1 SELECTED VOLTAGE
89a 115 116 FOR FFR
VB1
89b 311 312
VR2
89a
313 314
89b VY2
315 316 SELECTED VOLTAGE
89a VB2
220KV BUS-I FOR PROTN.
89b 317 318
VOLTAGE VN2 FEEDER CONTROL PANEL

VR
423 424
VY SELECTED VOLTAGE
425 426 FOR METERING IN
VB
CONTROL PANEL
427 428
VN
V
SELECTED VOLTAGE
223 224
Vo FOR E/F RELAY
225 226 (OPEN DELTA VOLTAGE)

TO BLOCK TRANSFER BUS


DIST. RELAY 221 222
89B (MAIN BUS-II ISO) MAIN BUS-II

MAIN BUS-I
89a
117 118 121 122
89A 89B 89C
89b

211 212

113 114 52

115 116
89L
311 312

313 314

FROM 315 316


89A-TBC *
ADJACENT PNL 317 318
220KV BUS-II SINGLE LINE DIAGRAM
VOLTAGE
BUS-C
BUS-D
BUS-A
BUS-B

BUS-E

423 424

425 426
89C-TBC *
427 428

223 224

89B-TBC * 225 226


TO BLOCK DIST. RELAY
221 222 DURING CHANGE OVER
ABB Group - 7 -

NOTE:-
* - COMMON TRANSFER BUS COUPLER BAY ISOLATOR CONTACTS FOR ALL LINE AND TRAFO. FEEDERS
15-Sep-17

TO ADJACENT PNL
Bus PT selection scheme
NORMAL TRANSFER
89A (MAIN BUS-I ISO)
+M -M

89a
11 21

89B (MAIN BUS-II ISO) 11 21

89a
16 17 11 21

89A-TBC *
11 21

89a

89B-TBC * VR1
89a VY1
TO FFR
VB1
* - COMMON ISOLATOR CONTACTS VR2
12 13 VY2 TO DIST &
14 15 VB2 BACKUP
O/C RELAY
16 17 VN2
VR
22 23 VY
FROM BUS PT-1 24 25 VB TO METERING
18 28 VN
V
12 13 TO BACKUP
Vo E/F RELAY

14 15
22 23
24 25
26 27

22 23
24 25
26 27

22 23
24 25
FROM BUS PT-2
18 28

12 13

14 15
16 17
ABB Group - 8 -

22 23
24 25
26 27
TO BLOCK DIST. RELAY BURING CHANGE OVER TO BLOCK DIST. RELAY BURING CHANGE OVER
26 27 26 27
15-Sep-17
ABB Group - 9 -
15-Sep-17
Bus PT selection scheme