Sunteți pe pagina 1din 10

s Power Transmission

Power Transmissionand
andDistribution
Distribution
MediumVoltage
Medium VoltageComponents
Components

Major
Changes
IEC 60056
and
IEC 62271-
100
Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.1
s Power Transmission and Distribution
Major changes in IEC62271-100 regarding
Medium Voltage Components

MV CBs
Clause :3-Definitions

Non Sustained Disruptive Discharge (NSDD) Definition has been


added (3.1.126)
Restrike performance has been added (3.1.127)
Circuit Breaker class - E1,E2,M1,M2,C1,C2 Added.
Enclosure definition added (degree of protection) (3.5.123).
Critical Current definition modified. ( If the min. arcing time in test
duty T10,T30 or T60 is one half cycle or more)
Amplitude Factor : Definition added.(3.7.153)

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.2
s Power Transmission and Distribution
Medium Voltage Components
Major changes in IEC 62271-100 regarding MV
CBs
Classes. Definitions
Class Definitions Notes
Class M1 2000 operations Mandatory in IEC
60056. Difference is
only the class definition.
Class M2 10000 operations NEW. Classification for
extended special
services. Siemens has
always offered at least
10.000 operations.
Class E1 CB with basic electrical endurance not falling
into the category of class E2.
Class E2 CB designed so as not to require Siemens 3AH CBs are
maintenance of the interrupting parts of the maintenence- free for
main circuit during its expected operating life, the expected operating
and only minimal maintenance of its other life and under normal
parts ambient conditions.
Class C1 Circuit-breaker with low probabilty of restrike
during capacitive current breaking as
demonstrated by specific type tests.
Class C2 Circuit-breaker with very low probabilty of
restrike during capacitive current breaking as
demonstrated by specific type tests.

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.3
s Power Transmission and Distribution
Medium Voltage Components

Mandatory type tests -Table 7- IEC 62271-


100
Mandatory type tests Subclauses Remarks/Changes
Dielectric tests 6.2 No changes compared to IEC 60056
Radio interference 6.3 Not applicable for Medium voltage
voltage tests circuit-breakers. Refer to Subclause
6.3 IEC 60694. No changes
compared to IEC 60056.
Measurement of the 6.4 No changes compared to IEC 60056
resisitance of the main
circuit
Temperature-rise tests 6.5 No changes compared to IEC 60056
Short-time withstand 6.6 No changes compared to IEC 60056
current and peak
withstand current tests
Tightness tests 6.8 Subclause 6.8 of IEC 60694 is
applicable. Not applicable for VCBs
EMC Tests 6.9 Subclause 6.9 of IEC 60694 is
applicable. Only applicable for
secondary systems, like electronics.
Mechanical operation 6.101.2.1 to 2000 operations are mandatory. New
test at ambient 6.101.2.3 classification Class M2 10.000
temperature operations for extended mechanical
endurance.

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.4
s Power Transmission and Distribution
Medium Voltage Components

Mandatory type tests -Table 7- IEC 62271-


100
Mandatory type tests Subclauses Remarks/Changes
Short-circuit current 6.102 to Included. New definitions have been
making and breaking 6.106 introduced.
tests Making current
- 2.5 times for 50Hz and time constant 45
msec (Standard in IEC 60056).
- 2.6 for 60 Hz and time constant 45 msec
- 2.7 for special time constant circuit-breakers.
DC-Component
- DC-Component to be specified with time
constant. Standard time constant 45 msecs
was already defined.
- Special time constant for circuit breakers up
to 52 kV is 120 ms.
Capacitive current 6.111.5.1 New, but not applicable for medium voltage
switching tests: line- circuit-breakers
charging current breaking
tests (Ur>72,5 kV)
Capacitive current 6.111.5.2 Not mandatory in IEC 60056
switching tests: cable-
charging current breaking
tests (Ur< 52 kV)

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.5
s Power Transmission and Distribution
Medium Voltage Components
Major changes in IEC62271-100
Clause :4-Ratings
Preferred values of rated cable charging
breaking currents

Rated Cable
Rated Charging
voltage Breaking
current

3,6 10
7,2 10
12 25
24 31,5
36 50

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.6
s Power Transmission and Distribution
Medium Voltage Components

Major changes in IEC62271-100


Clause :6-Type testing

Capacitive current switching test : cable-charging current


breaking test for rated voltage up to 52kV is mandatory.

Test duties renamed as T10,T30,T60,T100S,T100a.


( Old.1,2,3,4,5).Physics have not changed. Basic Tests are
covered already by IEC 60056.

Power frequency recovery voltage to be maintained for 0.3sec


minimum.

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.7
s Power Transmission and Distribution
Medium Voltage Components

Major changes in IEC62271-100


Clause :6-Type testing

Clause 6.111 : Capacitive current switching Test


Class C1: Low probability of restrike
Class C2: Very low probability of restrike
Duties renamed as:
 LC1: Line charging current breaking test duty TD1
 LC2: Line charging current breaking test duty TD2
 CC1: Cable charging current breaking test duty TD1
 CC2: Cable charging current breaking test duty TD2
 BC1: Capacitor bank breaking test duty TD1
 BC2: Capacitor bank breaking test duty TD2

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.8
s Power Transmission and Distribution
Medium Voltage Components

Major changes in IEC62271-100


Clause :6-Type testing
Cable-charging tests
C1 C2

OPERATING TOTAL OPERATING TOTAL


CURRENT CURRENT
SEQUENCE OPERATIONS SEQUENCE OPERATI-ONS

1PH. 3PH. 1PH. 3PH.


LC1/CC1 O 24 24 10 to 40% O 48 24 10 to 40%
O & CO or
LC2/CC2 CO 24 24 100% 48 24 100%
CO
BC1 O 24 24 10 to 40% O 48 24 10 to 40%
O & CO or
BC2 CO 24 24 100% 120 80 100%
CO

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.9
s Power Transmission and Distribution
Medium Voltage Components

Table 21-Operating sequence for electrical endurance test on


class E2 circuit-breakers
Testing current
Number of Number of
(percentage of
Operating operating operating
rated short-circuit
sequences sequences sequences
breaking current)
(List1) (List2)
%
O 84 6
10 O-0.3s-CO 14 6
O-0.3s-CO-t-CO 6 4
O 84 12
30 O-0.3s-CO 14 6
O-0.3s-CO-t-CO 6 4
O 2 6
60
O-0.3s-CO-t-CO 2 8
100(symmetrical) O-0.3s-CO-t-CO 2 4
a) List 1 is preferred. List 2 may be used as an alternative for
circuit-breakers used for solidly earthed system.

Major changes IEC 60056 and IEC 62271-100 011023-Mi-Vergleich IEC 62271-100 und 60056.ppt
10.01/01.02.2018/S.10