Switches
New modulating and multi-stage
furnaces are more complex and
require that installation instructions and
procedures be followed so that the
furnace will operate as it was designed
to do.
0.6”WC
Magnahelic
After attaching the gauge properly, call for
heat and observe the gauge pressure.
Magnahelic
Note: There are some extreme cases where
the switch is closed but no electrical circuit is
made. This can be caused by a coating on
the switch contacts which does not allow
good conductivity. This can be verified with
your ohmmeter or voltmeter.
If the pressure reading is lower
than the makepoint, a problem
exists that does not allow
enough combustion air to flow.
Some causes for this are:
RTI
(read the instructions!)