INALA TECHNOLOGIES

TEST PROCEDURE:
ECS (E1/ETH), SAM2, SAM1.5 & ACCESS

VERSION 1.0
1|
TESTING SUMMARY
1. Set up SAM2.
2. Set up ECS (E1/Eth) communication controller.
3. Test communication to SAM1.5 or SAM2 unit via ECS (E1/Eth) coms Controller
4. Test communication to Access Control unit via ECS (E1/Eth) coms Controller

2 | SAM Training
SAM2 SET UP – VIA RS232

3|
SAM2 – RS232
RS232 Communication Test;
• Connect a straight RS232 cable between the Lap Top and the
SAM2 RS232 port(DB9 Connector on front panel
• Open SAM2 ECT

• Select “Com Port” and double click on “Password”

4 | SAM Training
SAM2 – SET UP VIA RS232 CONTINUED
RS232 Communication Test; Cont;
• Active communication will be shown on the
bottom left as indicated with the RED circle
until it says “received”
1. Click on “Load Config” and select the
applicable config file.
2. Click on “Update SAM” and wait until SAM
has been updated – This can be seen on
the bottom left as indicated with the RED
circle until it says “received”
3. Click on “Sync Time”
4. Click on “Get Config” and ensure that
SAM2 shows you the current date and
time.
5. Capture SAM2 Serial number.
6. Click on “Update”
7. Click on “Set Config”

5 | SAM Training
SAM2 – SET UP VIA RS232 CONTINUED
RS232 Communication Test; Cont;
1. Click on “Alarm Configuration” tab
2. Select “RS485” under “Coms Config”
3. Click on “Set”
4. Click on “Get Config”
5. Click on “Set Config”

• Check that “Intruder” alarm is number “9”


• Check that “Movement” alarm is number “11”

Close SAM2 ECT

6 | SAM Training
ECS (E1/ETH) COMMUNICATION CONTROLLER
SET-UP

7|
ECS(E1/ETH) COMS CONTROLLER – SET UP
ECS(E1/ETH) Coms Controller Set up;
• Connect a Straight RS232 cable the Lap Top and the
ECS(E1/ETH) Coms Controller diagnostics port.
• Open ECS(E1/ETH) ECT

• Insert “User name” and “Password”


• Select “Serial Communication and click on “Login”

8 | SAM Training
ECS(E1/ETH) CONTROLLER – SET UP
ECS(E1/ETH) Set Up:
1. Click on “Find” to connect to unit
• Check that the units has the latest Firmware
version being “4.0.1.8”
• If Not on latest version, upgrade to latest
version
1. Click on “Down Load”
2. Capture the IP address as indicated
3. Click on “Set”
4. Click on “Site Inventory”

9 | SAM Training
ECS(E1/ETH) COMS CONTROLLER – SET UP
ECS(E1/ETH) Set Up:
1. Capture ECS(E1/ETH) Coms Port setup as
per screen print
2. Click on “Set” on the “Network” tab once
done.

10 | SAM Training
TESTING COMMUNICATION TO THE SAM OR
ACCESS CONTROL UNIT
VIA THE ECS(E1/ETH) COMMUNICATION CONTROLLER

11 |
LAPTOP – SET UP
Laptop Set Up:
Your Laptop IP address needs to be changed so
that it is within range of the coms controller
1. Connect LAN cable between the Coms
controller and the Laptop
2. Open Network settings
3. Click on “Local area Connection”
4. Click on “Properties”
5. Select “Internet protocol Version
4(TCP/IP).
6. Click on “Properties”
7. Click on “Use the following IP Address”
8. Capture the IP address – IP address will be
the same as the Coms controller except
the last digit must differ
9. The Subnet mask and gateway IP must be
the same as the coms controller
10. Click on “OK”

12 | SAM Training
SAM2 COMMUNICATION TEST
VIA THE ECS(E1/ETH) COMMUNICATION CONTROLLER

13 |
SAM2 – COMMUNICATION TEST VIA ECS2
COMMUNICATION CONTROLLER – “RS485”
RS485 Communication Test;
• Connect a LAN cable between the Lap Top and the
ECS(E1/Eth) LAN port
• Open SAM2 ECT

• Select “TCP” and insert the IP address of the ECS(E1/Eth) and


Port 301 and double click on “Password”

14 | SAM Training
SAM2 – COMMUNICATION TEST VIA ECS2
COMMUNICATION CONTROLLER – “RS485”
RS485 Communication Test; Cont;
• Active communication will be shown on the
bottom left as indicated with the RED circle
until it says “received”

15 | SAM Training
SAM1.5 COMMUNICATION TEST
VIA THE ECS2 COMMUNICATION CONTROLLER

16 |
SAM1.5 – COMMUNICATION TEST VIA ECS2
COMMUNICATION CONTROLLER – “RS485”
RS485 Communication Test;
• Connect a LAN cable between the Lap Top and the
ECS(E1/Eth) LAN port
• Open SAM2 ECT

• Select “TCP” and insert the IP address of the ECS(E1/Eth) and


Port 301 and double click on “Password”

17 | SAM Training
SAM1.5 – COMMUNICATION TEST VIA ECS2
COMMUNICATION CONTROLLER – “RS485”
RS485 Communication Test; Cont;
• Active communication will be shown on the
bottom left as indicated with the RED circle
until it says “received”

18 | SAM Training
ACCESS CONTROL COMMUNICATION TEST
VIA THE ECS2 COMMUNICATION CONTROLLER

19 |
ACCESS CONTROL – COMMUNICATION TEST VIA
ECS2 COMMUNICATION CONTROLLER – “RS485”
RS485 Communication Test; Cont;
1. Click on “TCP” and insert IP address of
the ECS(E1/Eth).
2. Click on “Connect”
3. Click on “Logon”
4. Click on “Open Door”
5. Click on “Get Version”
6. Click on “Get Time”
7. Click on “Log off”
8. Click on “Exit”

• Responses should be received as


indicated in the Red circle

20 | SAM Training
CLICK TO EDIT MASTER TITLE STYLE

THANK YOU