FAST SWITCH TRANSFER FUNCTION

• ACCIDENT SWITCH: implemented automatically in two


situations
i. Bus voltage loss start: when 3 phase(L-L or L-N
selectable) voltages of bus are lower than set point
and last longer than delay time as well as working
breaker is closed and the incomer voltage is lower
than normal voltage. The device start series or
simultaneous switch
ii. The working breaker mis-trip: when some reasons
(including manual mis-operation) cause the working
breaker mis-trip, the device implement series switch
FAST SWITCH TRANSFER FUNCTION
• FAULT SWITCH: Switching started by protection contact or analog value
• Protection contact from: diff protection, generator & T/F protection output etc
• Analog value includes:
i. Frequency difference actuate
ii. Frequency difference no current actuate
iii. Reverse power actuate
iv. Reverse power frequency difference actuate
v. frequency voltage quality actuate
• FAULT SWITCH: service supply trip first then backup supply connected upon
preset condition or adjustable delay
• Fault switch mode: transfer mode can be serial or simultaneous
FAST SWITCH TRANSFER FUNCTION
• MANUAL SWITCH: started by manual operation & complete automatically
• When local/remote manual switch signal received, switching b/w working and
reserve line starts
• Manual switch mode can be:
i. Series switching
ii. Simultaneous switching
iii. Auto-parallel switching
iv. Semi-automatic parallel
v. Parallel failed turned to series
vi. Parallel failed turn to simultaneous
FAST SWITCH TRANSFER FUNCTION
• Fast switch transfer scheme utilizing different switching modes as follow
i. series switching mode
ii. Simultaneous switching mode
iii. Auto-parallel switching mode
iv. Semi-automatic parallel switching mode
v. Paralleling failed turn to series switch
vi. Paralleling failed turn to simultaneous switch
FAST SWITCH TRANSFER FUNCTION
• Series switching mode: works as follow
i. Trip working breaker first
ii. Confirm working breaker opening (aux contact and current used as signals)
iii. After confirming working breaker opening, close the backup breaker
FAST SWITCH TRANSFER FUNCTION
• SIMULTANEOUS SWITCH MODE: works as follow:
i. Trip working breaker
ii. At process of tripping working breaker, send command of backup
breaker closing
iii. Assure working breaker open first and backup breaker closed
after a settable closing delay time
• working breaker may fail to trip and both working and reserve
supply will become parallel creating a looped network
• If looped network is not allowed in system, a decoupling function
can be set along with a decoupling time
• If a looped network situation happens switch proceeds as follow:
i. Transfer switch waits for the set de-coupling time
ii. After expiry of decoupling time, trip the breaker that just closed
in
FAST SWITCH TRANSFER FUNCTION
• AUTO-PARALLEL SWITCH MODE: works as follow:
i. First close backup breaker based on synchronization
ii. Confirm closing of backup breaker
iii. After confirming of backup breaker closing, trip the working breaker
automatically
• Auto parallel switch mode: supports decoupling function
• Synchronization : can be same frequency or difference frequency synchronization
• Auto parallel switch mode: only supported for manual scheme of fast transfer
switch
FAST SWITCH TRANSFER FUNCTION
• SEMI AUTOMATIC PARALLEL SWITCH MODE:
Works as follow:
i. First close backup breaker based on synchronization
ii. After backup breaker is closed, trip the working breaker manually
iii. Semi automatic parallel switch mode: only works in manual fast transfer
FAST SWITCH TRANSFER FUNCTION
• Parallel failed turn to series mode: works as follow:
i. Switch according to auto parallel mode if conditions of parallel switch mode
satisfied
ii. Else switch according to series switch mode
• this switch mode used only for normal manual switch mode
FAST SWITCH TRANSFER FUNCTION
• Paralleling failed turn to simultaneous mode
i. Switch according to auto parallel mode if conditions of parallel switch mode
satisfied
ii. Else switch according to simultaneous switch mode
• This switch mode only used in normal manual switch mode.
RESERVE SUPPLY AUTO PUT IN
FUNCTION
• “Fast transfer” occurs for three conditions:
i. fault switch (protection relay contact or analog value)
ii. Accident switch (bus voltage loss/breaker mis-trip)
iii. Manual switch
• Above three switching types can be accomplished with the device in “Reserve supply auto
put in function”
RESERVE SUPPLY AUTO PUT IN
FUNCTION
• Reserve supply auto put in function: can be configured in different schemes for
one bus breaker and four incoming breakers.
• Three states of auto put in function:
i. Charging state/Monitoring state: device enters into monitoring state when
incomer & bus voltage and every breaker state is normal.”Auto switch” lamp on
panel blinks for 10 seconds and then becomes steady.
ii. Auto switch Operation state: operation begins if “accident condition” (bus
voltage loss or working breaker mis trip) or “fault signal” (protection start signal
of working breaker) is received. If transfer conditions are satisfied after signal
receipt, then working breaker transfer with backup breaker automatically. After
transfer, device enters “acknowledge reset” state. The device enters
“monitoring state” for next transfer operation only after receipt of local/remote
reset and a delay of 10 seconds.
RESERVE SUPPLY AUTO PUT IN
FUNCTION
• Manual switch operation state:
• When the breaker state is satisfied for manual switch condition, the
“manual switch” lamp normal bright, and the Reserve auto-transfer
device enter the manual switch operation and monitor state. Under
this state, if local or remote manual switch signal is gathered, working
breaker will transfer with backup breaker automatically. If the
operation fails, the device enter waiting affirm reset state. It may not
enter charging state to ready for next transfer until delay 10s and
remote or local reset operation is received. If the operation succeeded,
the device reset automatically after 200ms.
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
LINKAGE OPEN AND CLOSE FUNCTION
• Linkage open function: a control strategy of device to “ trip the work supply” and
“close the reserve supply”.
• Linkage close function: a control strategy of the device after reserve supply
transfer is finished
• Linkage open& close function: depends on locale situation
• This scheme mainly used to put in or remove some specific power supplies or load
branches
• This switch scheme also used to control the flow and rule of the switch
• Soft switches (settable in set point independently) for linkage open & close
function
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
PROTECTION FUNCTIONS
• Dedicated incomer & bus linkage(coupler) over current protection function
• Main functions as follows:
i. Bus linkage O/C protection segment 1
ii. Bus linkage O/C protection segment 2
iii. Bus O/C instantaneous trip protection
iv. #1,#2 &#3 incomer O/C protection
v. #1,#2 &#3 incomer O/C instantaneous trip protection
vi. Incomers and bus voltage loss alarm protection
vii. Incomer PT disconnection alarm
viii. Bus PT disconnection alarm
ix. 2 segments low voltage unloading protection
• Value, delay time & soft switch of each protection can be set independently in
protection set point
PROTECTION FUNCTIONS
• Bus linkage o/c protection segment 1: if this function is active then:
- Trip bus breaker after set time delay if bus linkage(coupler) current is larger
than segment 1 set point current
• Bus linkage o/c protection segment 2:if this function is active then:
- Trip bus breaker after set time delay if bus linkage(coupler) current is larger
than segment 2 set point current
• Bus o/c instantaneous trip protection:
- When bus breaker changes from open to close state, the instantaneous(haste)
protection is open for 5 seconds
- -if during above period, the instantaneous protection is put in and the bus
linkage current is greater than set point current, then bus breaker is tripped
after set time delay
PROTECTION FUNCTIONS
• Incomer O/C protection function: device provides incomer 1, incomer 2
and incomer 3 O/C protection function
• This function operated according to actual running of main bus
connection
• Same logic for o/c protection of the 3 No incomers
• Soft strap is devoted
• Incomer O/C protection works as follows:
- If incomer current >set point, then incomer is tripped
- When device is in “backup transfer monitor state” or “normal transfer
condition detecting” state, if O/C detected in any phase and direction
of current is into the bus(this indicates a zone fault), then fast transfer
function will be blocked during protection tripping. This is to ensure
that reserve transfer does not occur considering the incoming tripping
as “mis-trip”.
PROTECTION FUNCTIONS
• Incomer O/C instantaneous trip function: same
logic for all three incomers
• When incomer state changes from open to close , the instantaneous
protection is opened for 5 seconds ( to avoid inrush?)
• If during above period (the 5 seconds period?), the instantaneous o/c
protection is enabled, then trip each incomer after set delay time
PROTECTION FUNCTIONS
• Incomer & bus voltage loss alarm protection:
- Alarm signal issues after set time delay if voltage of incomer or bus is less that
set point
• Incomer PT disconnection alarm:
- If each incomer PT secondary disconnection” soft switch “ is put in( enabled?)
and incomer voltage less than 70 % of Un, then after 10 seconds delay,PT
disconnection alarm signal sent out by device
• Bus PT disconnection alarm
- If bus PT disconnection alarm is put in. if the incomer breaker is closed and the
incomer voltage is normal or incomer has current, if bus voltage is less than
70% of Un, then bus PT disconnection alarm sent out.
PROTECTION FUNCTIONS
• TWO segments low voltage unloading protection function:
- The low voltage unloading function segment 1 and segment
2 are put in
- When switching is finished, the low voltage unloading
function is opened for 10 seconds
- If during above period , bus voltage is detected lower than
set point value and lasts for the time setting, then some
unimportant loads are tripped off to recover bus voltage
- There is a soft strap switch for low voltage unloading
function
- Can be set independently for segment 1 and segment 2
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
Post reclose after actuation function
• Post reclose after actuation or startup post
reclose function : send post reclose signal
pulse to protection system after switched or
operated only. Time of pulse can be set.
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
Reserve supply auto put lock in fault
• Automatic fault lock function: works based on “power direction lock” and
“voltage unbalance lock”
• Device finds out whether fault is in the protected area through the test of bus
voltage, incomer current etc.
- If fault is within protected area, the device blocks/locks the switching function
to avoid inputting reserve supply on fault point
Reserve supply auto put lock in fault
• Automatic fault lock based on power direction : when detected 3 phase current
of power feed lines is any phase into the bus and if:
- the phase current magnitude > “maximum load current value” and
- At least one L-L voltage of bus < “low voltage latch value” (recommended:60~70%
of Un)( then it means fault is in protected area?).so:
- Device immediately locks all switch start criteria (including protection signal &
analog signal) and starts “fault lock timer”.
- If fault current disappears or “changes direction” before “automatic fault
identification time set point”, the device immediately opens (enables?) all switch
criteria otherwise the device automatically exit the monitor state until the system
is back to normal state.
• Automatic lock based on power direction also applies to condition when bus
voltage drops suddenly due to large motors starting
• Settings of “automatic fault identification time set point” is chosen based on two
criteria:
- no local bus protection installed
- local bus protection installed or no risk of bus fault.
Reserve supply auto put lock in fault
• “automatic fault identification time set point” setting for no local bus protection
-value should be large enough than set time of far backup protection of the supply
feeder to achieve selectivity
- This is to allow far backup protection of the incomer to operate for bus faults if
there is no local bus protection
- Since majority bus faults are permanent faults, so auto transfer device should exit
the monitor state before far backup protection time. this exiting of SID-40B is
necessary to ensure that reserve switching does not occur once fault is cleared by
far backup protection.
Reserve supply auto put lock in fault
• automatic fault identification time set point”
setting for local bus protection installed
- Value of “automatic fault identification time” in such case should be bigger
than the load branch protection relay trip time along with use of bus bar
protection relay signal as blocking signal for automatic switch lock
function
Reserve supply auto put lock in fault
• Automatic fault lock based on voltage unbalance
-bus voltages are balanced for fault points on branch circuits outside
the protection area
• this fault lock works as follows:
-confirm working breaker tripped on fault
-check whether voltage is balanced
- If unbalance rate > 20% Un then lock following three fast transfer
criteria immediately until all three phases are balanced:
i: fast switch ( fault switch, accident switch, manual switch)
ii. Capture motor group withstand voltage criteria
iii. Synchronize/first phase capture criteria
- Residual voltage switch and long delay switch are not locked
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
EVENT RECORD FUNCTION
• Device has record function of :
i. Remote signal event
ii. Protection event
iii. Wave record event
iv. Operation event
v. Self check event
• User can inquire record info like “action time” and “event name”
through “event record” on LCD
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
Transferring record wave function
• Wave record function
• Wave recording begins once transfer is started (20 cycles before & 50
cycles after switch start up)
• Each total wave recording time is 1.5 sec and total twice
• Device storage is up to 12 groups of record data
• Recorded data content includes:
- Bus voltage & current
- Incomer voltage & current
- Digital input info
SID-40 MAIN FUNCTIONS
• Fast switch function
• Reserve supply auto put in function
• Linkage open and linkage close function
• Protection function
• Post re-close after actuation function
• Reserve supply auto put in fault lock function
• Even record function
• Transferring record wave function
• Communication, print, GPs time function
Communication, print, GPs time function

• Device communication functions:


- Two Ethernet interfaces
- Four RS485 serial interfaces
- 2 N0 Ethernet + 2 N0 RS485 for communication to SCADA
- - 1 N0 RS485 for print
- 1 No Rs485 for GPS time adjusting
SI-40B Control strategy

• Mode 1: the two incomers supply to bus simultaneously, bus coupler is open, bus1 and bus2 reserve for
each other.
• Mode 2: bus coupler is closed or system with only one bus but without bus coupler, one incomer is
supplying and the other is as reserve supply.
• When working incomer fails, fast transfer is the optimal mode in order to make interruption time least. If
the state of system does not allow this switch mode, choose other mode whose speed is slower a little.
SI-40B Control strategy
• SID-40B control strategy for initiating reserve supply transfer is based on four
schemes
i. Fast transfer rule
ii. Capture motor group withstand voltage rule
iii. Capture first point in phase coincidence rule
iv. Residual voltage switch rule
v. Long delayed time switch rule
FAST SWITCH STATEGY
• FAST SWITCH STATEGY: in case of loss of normal supply, “fast switching” will start
up and close output immediately if:
i. Δ⏀ & Δf b/w bus & reserve supply are within setting scope and
ii. Ubus> “fast switch low voltage lock value”
• Bus voltage & freq decay time and decay rate depends on bus load and found
from field tests
• More the load on the bus, slow will be voltage & freq decay rate of bus
• Bus volt & freq decay rate increases as time elapses
• Good choice is to close reserve supply in first 0.3 sec. during this time bus
voltage and decay rate is slower and it is safe for the bus equipments when
Δ⏀ is within 60 degree.
• When Δf =1Hz average, Δ⏀ b/w bus & incoming reserve increases to 36
degree based on inherent switching time of 100msec
• When SID-40B gives out closing signal, Δ⏀ (fast transfer angle setpoint)
should be less than 20 degree.
Capture motor group withstand
voltage rule
• As normal supply fails, the bus residual voltage and frequency starts to decay
depending on connected load
• The angle Δ⏀ b/w bus voltage & reserve supply starts to increase
• Vg : bus residual voltage, VR: reserve supply voltage
• Δ U = UR – UG increases with time
Capture motor group withstand
voltage rule
Capture motor group withstand
voltage rule
• Vector difference Δ U = UR – UG b/w bus residual voltage and reserve supply
increases continually
• Ugo is normal bus voltage with normal supply connected and 𝛅0 is
corresponding angle
• As working supply is removed from Bus , bus voltage changes from Ugo to
Ug1,Ug2… and angle changes from 𝛅0 to 𝛳1, 𝛳12,….
• The corresponding voltage difference Δ U = UR – UG changes from Δ U1
to Δ U12,… etc
• The goal here is to close the reserve supply when Δ U and Δ 𝛳 between bus
residual voltage and reserve supply are within set point windows
• This is to ensure that voltage across the bus loads is lower than the voltage
withstand rating (110~120%) of motors.
• The voltage across the motor loads on closing the reserve supply depends on
the motor group impudence “Xm”.
Capture motor group withstand

voltage rule
When reserve supply is connected only part of the Δ U is dropped across bus
loads as per the bus load impedance “XM”.
• SID-40B closes the reserve supply at point when Δ U is such that voltage across
the loads < withstand voltage of motors
Capture motor group withstand
voltage rule
• Generally normal supply line impedance “XG” and reserve supply line impedance
“XB” are known. So bus motor group impedance XM can be calculated
continuously.
• Initially with working supply connected to bus , Value of XM is calculated as below:

• When normal supply is disconnected, XM calculated at that point is recorded..


From that recorded XM and known XB, the Maximum voltage Δumax is
calculated. When the XM is such that voltage drop across motors will be less
than withstand voltage of motors, then reserve supply breaker is closed.
SI-40B Control strategy
• SID-40B control strategy for initiating reserve supply transfer is based on four
schemes
i. Fast transfer rule
ii. Capture motor group withstand voltage rule
iii. Capture first point in phase coincidence rule
iv. Residual voltage switch rule
v. Long e delayed time switch rule
Capture first point in phase coincidence rule
• Principles:
- When working supply is cut off by fault,the bus residual voltage phasor will rotate
in lag direction relative to reserve voltage vector
- The swtiching of reserve supply is carried out when phase angle difference is zero
b/w residual bus voltage and reserve supply
- The closing time of reserve breaker depends of variation rate of phase angle
difference Ψ
- Uby: reserve supply
- Us : bus voltage
- Ψ : angle difference b/w bus & reserve voltage
- d Ψ/dt: angular rate of change
Capture first point in phase
coincidence rule
• First phase coincidence rule works as follows:
- During vector rotation of residual bus voltage, find the time when angle difference
b/w bus and reserve is zero and then output reserve closing command according
to breaker closing time.
- Bus during this whole process, bus voltage drops to 30~40% and loads fed by
contactors will be cut off while some other motors will self start.
- First phase coincedence will cause supply cutoff to most loads .
- First phse coincedence is a back up for capture withstand voltage scheme.
Capture first point in phase
coincidence rule
• First phase coincedence switching scheme is used in following scenarios:
i. Incapable of completing voltage withstand switching scheme because of very
large initial power angle
ii. When freq of bus residual voltage drops fast but the breaker closing time is too
large , then it is difficult to comple capture voltage withstand scheme
iii. Working supply and reserve supply belong to completely indepdendt system
and there is not only difference of phase angle bus also freq difference
iv. When the scheme requires synchronizing due to presence of high capacity
working supply on the bus and possible mode of transfer is “fast speed auto
parallel transfer”
SI-40B Control strategy
• SID-40B control strategy for initiating reserve supply transfer is based on four
schemes
i. Fast transfer rule
ii. Capture motor group withstand voltage rule
iii. Capture first point in phase coincidence rule
iv. Residual voltage switch rule
v. Long delayed time switch rule
Residual voltage switch rule

• This mode works as follow:


-the three line voltages fall to ≤ residual voltage set point value (20~40% of rated
value)
- The low voltage lasts longer than set point time
• Residual voltage switch scheme is a backup of 1st phase coincedence switching
scheme
• When working supply is cut by protection and neither fast transfer , capture
withstand voltage and 1st pahse coincedence can be carried out by device,
then close reserve supply according to residual voltage switch scheme
• Residual voltage switching scheme does not look for angle difference and freq
difference.
• Since swiching is carried out at fairly low residual voltage so most loads will be
cut off by low voltage protection causing supply interruption
SI-40B Control strategy
• SID-40B control strategy for initiating reserve supply transfer is based on four
schemes
i. Fast transfer rule
ii. Capture motor group withstand voltage rule
iii. Capture first point in phase coincidence rule
iv. Residual voltage switch rule
v. Long delayed time switch rule
Long delayed time switch rule

• If in the “assigned time” ,switching cannot be carried out by device by any of


preceding four mentioned schemes, the reserve supply switching carried out
by long delayed time switch rule
• This switching scheme used only as standby mode and will not work under
normal situations
• General this mode adopted when fault happens many times in short time
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
System set points

PARAMETER RANGE DEFAULT EXPLANATION


Rated Frequency [50 Hz, 60 Hz] 50Hz For Rated Frequency setting

Switch Direction [Unidirectional Switch, Bi-directional To choose unidirectional


Bi-directional Switch] Switch switch (only transfer
from work supply to backup
supply) or
Bi-directional Switch (switch
each other between
work supply and backup
supply) when accident
switch and fault switch.
Bus Linkage Breaker [020 -- 200]ms 60ms For setting bus linkage
Closing Time breaker real closing time,
must be strictly in accordance
with the actual
situation to ensure a good
closing angle
1DL Breaker Closing [020 -- 200]ms 60ms For setting breaker 1DL real
Time closing time, must be
strictly in accordance with the
actual situation to
ensure a good closing angle
2DL Breaker Closing [020 -- 200]ms 60ms For setting breaker 2DL real
Time closing time, must be
strictly in accordance with the
actual situation to
ensure a good closing angle.
System set points

PARAMETER RANGE DEFAULT EXPLANATION


3DL Breaker Closing [020 -- 200]ms 60ms For setting breaker 3DL real
Time closing time, must be
strictly in accordance with the
actual situation to
ensure a good closing angle
4DL Breaker Closing Time [020 -- 200]ms 60ms For setting breaker 4DL real
closing time, must be strictly
in accordance with the actual
situation to
ensure a good closing angle.
Check Time of Trip [020 -- 999]ms 200ms The setting time used for
check breaker status,
failed switch if the status not
checked during the
setting time. The fitted setting
is 1.5--2 times real
closing time
Pulse Of Trip [020 -- 999]ms 200ms For setting output signal time,
which can be
applied by user customize
Volt. Type of Input Line 1 [Ua, Ub, Uc, Uab, Ua For setting the type of
Ubc, Uca] incomer voltage, which can
be applied by user customize
System set points

PARAMETER RANGE DEFAULT EXPLANATION


Leading Angle of Input [0°, +30°, -30°] 0° For setting the leading angle
Line 1 between incomer and
bus voltage since star-delta
convert work incomer
voltage, which can be applied
by user customize
Volt. Type of Input Line [Ua, Ub, Uc, Uab, Ua For setting the type of
2 Ubc, Uca] incomer voltage, which can
be applied by user customize
Leading Angle of Input [0°, +30°, -30°] 0° For setting the leading angle
Line 2 between incomer and
bus voltage since star-delta
convert work incomer
voltage, which can be applied
by user customize
which can be applied by user
customize
Volt. Type of Input Line [Ua, Ub, Uc, Uab, Ua For setting the type of
3 Ubc, Uca] incomer voltage, which can
be applied by user customize
Leading Angle of Input [0°, +30°, 0° For setting the leading angle
Line 3 -30°] between incomer and
bus voltage since star-delta
convert work incomer
voltage, which can be applied
by user customize
System set points

PARAMETER RANGE DEFAULT EXPLANATION


TA of Input Line 1 [None, Having] Having To set TA connection between
line 1 and device,
for distinguish switch
abnormal and prevent
mistrip since the connection
of auxiliary contacts mistake,
which can be applied by user
customize
TA of Input Line 2 [None, Having] Having -d0-

TA of Input Line 3 [None, Having] Having -d0-

Branch No Current [5.0% – 99.9%] 10% For distinguish switch


Setting abnormal and prevent
mistrip since the connection
of auxiliary contacts
mistake , and when bus start
loss voltage, to
determine whether the work
line has current ,
which can be applied by user
customize
Voltage Loss Set of Line [40.0 – 90.0] %Un 80.0%Un Used for setting alarm of
backup loss power,
which can be applied by user
customize
System set points

PARAMETER RANGE DEFAULT EXPLANATION


Voltage Loss Set of bus [40.0 – 90.0] %Un 70.0%Un Used for setting alarm of bus
loss power, and
accident switch actuate,
which can be applied by
user customize
Delay of Acking Voltage [0.02 – 10.00]S 0.3S The delay ids used for ensure
Loss loss power when
accident switch actuate for
prevent mistrip, which
can be applied by user
customize
Normal-volt. Set of Line [60.0 -- 95.0] %Un 90.0%Un For distinguish whether
backup voltage normally
for charging condition, which
can be applied by
user customize
Normal-volt. Set of Bus [60.0 -- 95.0] %Un 90.0%Un For distinguish whether bus
voltage normally for
charging condition, which can
be applied by user
customize
Delay of Acking [0.02 – 10.00]S 0.05S The delay for distinguish
Nor-volt whether voltage
normally for charging
condition, which can be
applied by user customize
System set points

PARAMETER RANGE DEFAULT EXPLANATION


Allowable Frequency [0.020Hz –2.000Hz] 0.20Hz For distinguish whether bus
Variation of Acking voltage normally for
Nor-volt charging condition, which can
be applied by user
customize
Delay of Simul Closing [0.00 – 0.1]S 0.02S To ensure trip before closing
prevent loop circuit
when simultaneous switch
which can be applied
by user customize
Clamp of Decoupling [Off, On] On The soft switch of decoupling
function when
Simultaneous switch mode
and parallel switch
mode, which can be applied
by user customize
Delay of Decoupling [0.02 – 5.00]S 0.20S Delay of decoupling, to
prevent system power off,
which can be applied by user
customize
Clamp of Linkage Close [Off, On] Off The on-off clamp of linkage
close function, which
can be applied by user
customize
System set points

PARAMETER RANGE DEFAULT EXPLANATION


Delay of Linkage Close [0.02 – 10.00]S 1.00S The delay set-point of closing
the reserve supply
outlet to the linkage close
outlet
Low-volt. Lock [70.0 -- 90.0] %Un 80.0%Un Low-volt. lock set-point of
Set-point of Linkage linkage close
Close
Clamp of Linkage Open [Mode 1, Mode 2, Mode Off Linkage open function mode
3, Off] selection and the
on-off clamp, which can be
applied by user
customize
Time Set-point of [0.02 -- 99.99] S 0.05S The delay set-point of
Linkage Open Start tripping the work switch to
the linkage open outlet
Time Set-point of [0.02 -- 0.05S Used in linkage open mode 3,
Linkage Open 99.99] S the delay set-point
to ensure linkage open outlet
success
System set points
PARAMETER RANGE DEFAULT EXPLANATION
Output Pulse Width of [0.02 -- 0.02S Pulse width of the output
Linkage Open 99.99] S signal of linkage open
Freq. Set-point of [40.00 – 49.00Hz Used in linkage open mode 1,
Linkage Open 60.00] Hz the parallel catch
switch blocking if the
frequency lower than
set-point when close the
reserve supply before the
linkage open outlet. After the
linkage open outlet
success, open all the
principles, see “Switch
principle set-point” for detail.
Freq. Diff. Set-point of [0.50 – 20.00Hz Used in linkage open mode 1,
Linkage Open 50.00] Hz the parallel catch
blocking if the frequency
difference higher than
set-point when close the
reserve supply before the
linkage open outlet
Volt. Set-point of [20.0 – 80.0%Un Used in linkage open mode 1,
Linkage Open 95.0] Hz the parallel catch
blocking if the voltage lower
than set-point when
close the reserve supply
before the linkage open
outlet. After the linkage open
outlet success, open
all the principles, see “Switch
principle set-point”
for detail.
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
Manual switch set points
PARAMETER RANGE DEFAULT EXPLANATION
Manual Switch Way [Off , Simul Switch , Auto Parallel For choose manual switch
Series Switch , Auto way or exit manual
Parallel , Semiauto switch, which can be
Parallel , Parallel & applied by user customize
Simul, Parallel & Series]
Fast Switch [On ,Off] On The soft switch of fast
switch when series
switch
or simultaneous switch,
which can be applied by
user customize
Endurance Voltage [On ,Off] On The soft switch of
Switch endurance voltage switch
when series switch or
simultaneous switch,
which can be
applied by user customize
Sync. Catch Switch [On ,Off] On The soft switch of sync.
catch switch when series
switch or simultaneous
switch, which can be
applied by user customize
Manual switch set points
PARAMETER RANGE DEFAULT EXPLANATION
Residual Voltage [On ,Off] On The soft switch of
Switch residual voltage
switch when
series switch or
simultaneous switch,
which can be
applied by user
customize
Long Delay Switch [On ,Off] Off The soft switch of long
delay switch when
series
switch or
simultaneous switch,
which can be
applied by user
customize
Time of Loop Closing [000 – 99.99]S 0.50S Loop circuit running
time when paralleling
switch
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Fault Switch Way [Off, Simul Switch Series Switch For choose fault
, switch way or exit
Series Switch] fault switch,
which can be
applied by user
customize
Fast Switch [On ,Off] On The soft switch of
fast switch when
fault switch,
which can be
applied by user
customize
Endurance Voltage [On ,Off] On The soft switch of
Switch endurance voltage
switch when
fault switch, which
can be applied by
user
customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Sync. Catch Switch [On ,Off] On The soft switch of
sync. catch switch
when fault
switch, which can
be applied by user
customize
Residual Voltage [On ,Off] On The soft switch of
Switch residual voltage
switch when
fault switch, which
can be applied by
user
customize
Long Delay Switch [On ,Off] Off The soft switch of
long delay switch
when fault
switch, which can
be applied by user
customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Clamp of Reverse-power [On ,Off] Off The criteria of the reverse-
Starting power starting fault switch,
which can be applied by user
customize
Delay of Reverse-power [0.00 – 10.00]S 0.10S The soft switch of reverse-
Starting power starting delay
when Fault switch, to confirm
fault, avoid
disoperation delay, which can
be applied by user
customize
Current Set-point of [5.0% – 999.9%] 10% The current set-point of
Reverse-power Starting reverse-power starting
criteria in fault conditions,
which can be applied
by user customize. Generally
set to be 10% of the
rated secondary current, this
setting must be
greater than the rated
secondary settings when the
work bus hang generator or
power branch.
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Clamp of [On ,Off] Off The criteria of the
Reverse-power Freq. reverse-power freq. diff.
Diff. Starting starting
fault switch, which can be
applied by user
customize
Delay of Reverse-power [0.00 – 10.00]S 0.05S The soft switch of
Freq. Diff. Starting reverse-power freq. diff.
starting
when Fault switch, to
confirm fault, avoid
disoperation delay, which
can be applied by user
customize
Current Set-point of [5 .0%– 999.9%] 10% The current set-point of
Reverse-power Freq. reverse-power freq. diff.
Diff. Starting starting criteria in fault
conditions, which can be
applied by user customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Freq. Diff. Set-point of [0.00 – 10.00]Hz 0.25Hz The freq. diff. set-
Reverse-power Freq. point of reverse-
Diff. Starting power freq.
diff. starting criteria in
fault conditions, which
can
be applied by user
customize
Clamp of Freq. Diff. [On ,Off] Off The criteria of freq.
Starting diff. starting fault
switch,
which can be applied
by user customize
Freq. Diff. Set-point of [0.02 – 10.00]Hz 0.4Hz The freq. diff. set-
Freq. Diff. Starting point of freq. diff.
starting criteria in
fault conditions, which
can be applied
by user customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Delay of Freq. Diff. [0.00 – 10.00]S 0.05S The soft switch of
Starting freq. diff. starting
when Fault
switch, to confirm
fault, avoid
disoperation delay,
which can be applied
by user customize
Low-volt. Lock [20.0 - 80.0] %Un 50.0%Un The low-volt. lock set-
Set-point of Freq. Diff. point of freq. diff.
Starting starting
criteria in fault
conditions, which can
be applied
by user customize
Clamp of Freq. Diff. [On ,Off] Off The criteria of freq.
Un-current Starting diff. un-current
starting fault
switch, which can be
applied by user
customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Freq. Diff. Set-point of [0.00 – 0.25Hz The freq. diff. set-point of
Freq. Diff. Un-current 10.00]Hz freq. diff. un-current
Starting starting criteria in fault
conditions, which can be
applied by user customize
Delay of Freq. Diff. [0.00 – 10.00]S 0.02S The soft switch of freq.
Un-current Starting diff. un-current starting
when Fault switch, to
confirm fault, avoid
disoperation delay, which
can be applied by user
customize
Low-volt. Lock [0.0 - 99.9] %Un 50.0%Un The low-volt. lock set-
Set-point of Freq. Diff. point of freq. diff.
Un-current Starting un-current starting
criteria in fault
conditions,
which can be applied by
user customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Current Set-point of [5.0 %- 99.9 %] 10% The un-current set-
Freq. Diff. Un-current point of freq. diff.
starting
criteria in fault
conditions, which can
be applied
by user customize
Clamp of F&V Quality [On ,Off] Off The criteria of F&V
Starting quality starting fault
switch,
which can be applied
by user customize
Set-point of Freq. [0.020Hz - 10.000Hz] 0.50Hz The freq. diff. set-
Quality point of F&V quality
starting criteria in
fault conditions, which
can be applied
by user customize
Fault switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Set-point of Volt. [0.000%Un - 5.0%Un The voltage set-
Quality 30.000%Un] point of F&V quality
starting
criteria in fault
conditions, which
can be applied
by user customize
Delay of F&V [0.000S - 10.000S] 0.05S The soft switch of
Quality F&V quality starting
Starting when fault
switch, to confirm
fault, avoid
disoperation delay,
which can be
applied by user
customize
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
Accident switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Bus Voltage Loss [Off, Simul Switch, Series Switch For choose accident
Switch Series Switch] switch way or exit
Way fault
switch, which can be
applied by user
customize
Breaker Mis-trip Way [All switches, incomer Incomer The soft switch of
switches, Off] Switches function which input
all switches (or
incomer switches) or
exit all switches,
which can be applied
by user customize
Fast Switch [Off, On] On The soft switch of fast
switch when accident
switch, which can be
applied by user
customize
Accident switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Endurance Voltage [Off, On] On The soft switch of
Switch endurance voltage
switch when
Accident switch,
which can be applied
by user
customize
Sync. Catch Switch [Off, On] On The soft switch of
sync. catch switch
when
accident switch, which
can be applied by user
customize
Residual Voltage [Off, On] On The soft switch of
Switch residual voltage
switch when
accident switch, which
can be applied by user
customize
Accident switch set points

PARAMETER RANGE DEFAULT EXPLANATION


Long Delay Switch [Off, On] Off The soft switch of long
delay switch when
accident switch, which
can be applied by user
Bus Voltage Loss [0.00 – 10.00]S 0.2S The delay to ensure
Switch Delay bus loss power when
accident
switch to prevent mis-
trip, which can be
applied
by user customize
Delay of Mis-trip [0.00 – 5.00]S 0.01S The delay to actuate
accident switch by
mis-trip to
prevent mis-trip,
which can be applied
by user
customize
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
SWITCH CRITERIA SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Switch Time Limit [10 -- 600] S 30S To distinguish the longest
switch process since
abnormal condition (example.
All criteria exit), if
switch process exceed the
scope, then record
switch failed, which can be
applied by user
customize
Parallel Max Volt. Diff. [1.0 -- 20.0] %Un 5.0%Un For setting volt. diff. allowed
which refer to sync.
catch Switch criteria when
paralleling switch,
which can be applied by user
customize
Parallel Max Freq. Diff. [0.1 -- 2.0]Hz 0.50Hz For setting freq. diff. allowed
which refer to sync.
catch Switch criteria when
paralleling switch,
which can be applied by user
customize
SWITCH CRITERIA SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Parallel Max Angle [0.0 -- 60.0]° 10.0° For setting angle diff.
Diff. allowed when
paralleling
switch, which can be
applied by user
customize
Fast Switch Freq. Diff. [0.10 – 2.00] Hz 1.50Hz For setting Freq. diff.
allowed which refer to
fast
Switch criteria, which
can be applied by user
customize
Fast Switch Block [30.0 -- 80.0] %Un 60.0%Un For setting block vol.
Volt. which refer to fast
switch
criteria, which can be
applied by user
customize
SWITCH CRITERIA SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Fast Switch Angle Diff. [0.0 -- 60.0]° 20.0° For setting angle diff.
allowed which refer to
fast
switch criteria, which
can be applied by user
customize
Endurance Freq. Diff. [0.5 -- 15.00]Hz 3.00Hz For setting freq. diff.
allowed which refer to
endurance voltage
switch criteria, which
can be
applied by user
customize
Endurance Block Volt. [10.0 -- 80.0] %Un 60.0%Un For setting block volt.
which refer to
endurance
voltage Switch criteria,
which can be applied
by
user customize
SWITCH CRITERIA SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Volt. Set-point of [1.00 – 1.40] Un 1.10Un For setting endurance
Endurance vol. which refer to
endurance voltage
switch criteria, which
can be
applied by user
customize
Sync. Catch Volt. Diff [0.5 -- 15.00] Hz 6.00Hz For setting freq. diff.
allowed which refer to
sync.
catch switch criteria,
which can be applied
by user
customize
Sync. Catch Lock Volt. [10.0 -- 80.0] %Un 40.0%Un For setting block volt.
which refer to sync.
catch
voltage switch criteria,
which can be applied
by
user customize
SWITCH CRITERIA SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Volt. Set-point of [10.0 -- 40.0] %Un 20.0%Un For setting residual
Residual Volt volt. which refer to
residual
voltage switch criteria,
which can be applied
by
user customize
Delay Set-point of [0.00 -- 5.00]S 1.00S For setting residual
Residual Volt. volt. delay which refer
to
residual voltage
Switch criteria, which
can be
applied by user
customize
Delay Set-point of [2.00 -- 20.00]S 5.00S For setting delay
Long which refer to long
Delay delay switch
criteria, which can be
applied by user
customize
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Low-volt. Unload 1 [Off, On] Off The soft switch of
low-volt. unload 1
section
function, which can
be applied by user
customize
Low-volt. Unload 1 [40.0 – 90.0] %Un 70.0%Un The vol. setting of
Volt. low-volt. unload 1
protection,
which can be
applied by user
customize
Low-volt. Unload 1 [0.10 -- 10.00] S 1.00S The delay setting of
Delay low-volt. unload 1
protection,
which can be
applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Low-volt. Unload 2 [Off, On] Off The soft switch of
low-volt. unload 2
section
function, which can
be applied by user
customize
Low-volt. Unload 2 [40.0 – 90.0] %Un 70.0%Un The vol. setting of
Vol. low-volt. unload 2
protection,
which can be
applied by user
customize
Low-volt. Unload 2 [0.10 -- 10.00] S 2.00S The delay setting of
Delay low-volt. unload 2
protection,
which can be
applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Bus Breaker Over [Off,On] Off Bus breaker over
Current Haste current haste,
which can be
applied by user
customize
Bus Breaker Over [01.00 – 99.99]A 5.00A Bus breaker over
Current Haste current haste
Current current, which can
be applied by user
customize
Bus Breaker Over [0.1 – 3.0]S 0.20S Bus breaker over
Current Haste Time current haste time,
which can be
applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Bus Breaker Over [Off, On] Off Bus breaker over
Current 1 current 1, which
can be applied
by user customize
Bus Breaker Over [01.00 – 99.99]A 6.00A Bus breaker over
Current 1 Current current 1 current,
which can be
applied by user
customize
Bus Breaker Over [0.10 -- 10.00] S 0.20S Bus breaker over
Current 1 Time current 1 time,
which can be
applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Bus Breaker Over [Off, On] Off Bus breaker over
Current 2 current 2, which
can be applied
by user customize
Bus Breaker Over [01.00 – 99.99]A 5.00A Bus breaker over
Current 2 Current current 2 current,
which can be
applied by user
customize
Bus Breaker Over [0.10 -- 10.00] S 0.50S Bus breaker over
Current 2 Time current 2 time,
which can be
applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line Voltage Loss [01.00 -- 10.00S The delay setting of
Alarm Delay 99.99] S Line Voltage Loss
Alarm,
which can be
applied by user
customize
Bus Voltage Loss [01.00 -- 99.99] S 10.00S The delay setting of
Alarm Bus Voltage Loss
Delay Alarm,
which can be
applied by user
customize
Bus 1 Voltage Loss [ On ,Off] Off The soft switch of
Alarm Bus 1 Voltage Loss
Alarm
function, which can
be applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Bus 2 Voltage Loss [Off, On] Off The soft switch of
Alarm Bus 2 Voltage Loss
Alarm
function, which can
be applied by user
customize
Line 1 Voltage Loss [ On ,Off] Off The soft switch of
Alarm Line 1 Voltage Loss
Alarm
function, which can
be applied by user
customize
Line 2 Voltage Loss [ On ,Off] Off The soft switch of
Alarm Line 2 Voltage Loss
Alarm
function, which can
be applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line 3 Voltage Loss [ On ,Off] Off The soft switch of
Alarm Line 3 Voltage Loss
Alarm
function, which can
be applied by user
customize
Bus 1 TV Line-break [ On ,Off] Off The soft switch of
Alarm Bus 1 TV
disconnection
Alarm
function, which can
be applied by user
customize
Bus 2 TV Line-break [ On ,Off] Off The soft switch of
Alarm Bus 2 TV
disconnection
Alarm
function, which can
be applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line 1 TV Line-break [ On ,Off] Off The soft switch of Line
Alarm 1 TV disconnection
Alarm
function, which can be
applied by user
customize
Line 2 TV Line-break [ On ,Off] Off The soft switch of Line
Alarm 2 TV disconnection
Alarm
function, which can be
applied by user
customize
Line 3 TV Line-break [ On ,Off] Off The soft switch of Line
Alarm 3 TV disconnection
Alarm
function, which can be
applied by user
customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Auto Fault Lock Voltage Off Voltage unbalanced lock means after
unbalanced lock, Power cutting off
consumption direction the working supply, lock three kinds
lock, Multiple lock, Off] fast transfer
when the three phase voltage of
incomer bus is
unbalanced, the slow transfer
function is available
if the conditions are satisfied; power
consumption
direction lock means lock auto switch
function
when the current is larger than the
largest load
current and flow to the bus ; multiple
lock means
input both voltage unbalanced lock
and power
consumption direction lock; off means
output both
voltage unbalanced lock and power
consumption
direction lock.
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Auto Fault Lock [0.10 -- 10.00] S 0.10S Auto fault lock
Delay delay to confirm
the fault reserve
supply is discharged
Fault Low-voltage [10.00 – 90.00] Un 70.0%Un Low-voltage set-
Set-point point in power
consumption
direction lock
Line 1 Max Load [00.50 – 5.00A Line 1 max load
Current 99.99]A current, which can
be applied by
user customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line 2 Max Load [00.50 – 5.00A Line 2 max load current,
Current 99.99]A which can be applied by
user customize
Line 3 Max Load [00.50 – 5.00A Line 3 max load current,
Current 99.99]A which can be applied by
user customize
Line 1 Over-cur. [ On ,Off] Off Line 1 over-cur. haste
Haste function, which can be
function applied by user customize
Line 1 Over-cur. [ On ,Off] 6.00A Line 1 over-cur. haste current
Haste set-point, which can
Current Set-point be applied by user customize
Line 1 Over-cur. 0.1– 0.20S Line 1 over-cur. haste time
Haste 3.0]A set-point, which can be
Time Set-point[ applied by user customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line 2 Over-cur. [ On ,Off] Off Line 2 over-cur. haste
Haste function, which can be
Function applied by user customize
Line 2 Over-cur. [01.00 – 99.99]A 6.00A Line 2 over-cur. haste current
Haste set-point, which can
Current Set-point be applied by user customize
Line 2 Over-cur. 0.1– 0.20S Line 2 over-cur. haste time
Haste 3.0]S set-point, which can be
Time Set-point[ applied by user customize
Line 3 Over-cur. On ,Off] Off Line 3 over-cur. haste
Haste function, which can be
Function applied by user customize
Line 3 Over-cur. [01.00 – 99.99]A 6.00A Line 3 over-cur. haste current
Haste set-point, which can
Current Set-point be applied by user customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line 3 Over-cur. [0.1 – 0.20S Line 3 over-cur. haste time
Haste 3.0]S set-point, which can be
Time Set-point[ applied by user customize
Line 1 Over-cur. [ On ,Off] Off Line 1over-cur. function,
Function which can be applied by
user customize
Line 1 Over-cur. [01.00 – 6.00A Line 1 over-cur. cur. set-point,
Cur. 99.99]A which can be
Set-point applied by user customize
Line 1 Over-cur. [0.10 – 99.99]S 0.50S Line 1 over-cur. time set-
time point, which can be
set-point applied by user customize
Line 2 Over-cur. [ On ,Off] Off Line 2 over-cur. function,
Function which can be applied by
user customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Line 2 Over-cur. [01. 00 – 6.00A Line 2 over-cur. cur. Set point,
Cur. Set point 99.99]A which can be applied by user
customize
Line 2 Over-cur. [0. 10 – 99.99]S 0.50S Line 2 over-cur. time set
time point, which can be
set-point applied by user customize
Line 3 Over-cur. [ On ,Off] Off Line 3 over-cur. function,
Function which can be applied by
user customize
Line 3 Over-cur. [01.00 – 6.00A Line 3 over-cur. Cur. Set point,
Cur. 99.99]A which can be
Set-point applied by user customize
Line 3 Over-cur. [0. 10 – 99.99]S 0.50S Line 3 over-cur. time set
time point, which can be
set-point applied by user customize
PROTECTION SET POINT

PARAMETER RANGE DEFAULT EXPLANATION


Open Time of [0.10 -- 99.99] S 5.00S The time of post reclose
Post-reclose pulse after actuate, which
can be applied by user
customize
SID-40B PARAMETERS SET POINTS
• Following set points
i. System set points
ii. Manual switch set points
iii. Fault switch set points
iv. Accident switch set points
v. Switch criteria set point
vi. Protection set point
vii. Scheme expand set point