Sunteți pe pagina 1din 41

Power System Analysis and Design, 6e Glover, Overbye, Sarma

Chapter 2:
Fundamentals

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible 0
website, in whole or in part.
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Review of Phasors
Goal of phasor analysis is to simplify the analysis of constant
frequency ac systems

v(t) = Vmax cos(wt + qv)


i(t) = Imax cos(wt + qI)

Root Mean Square (RMS) voltage of sinusoid

1T Vmax
 v(t ) dt 
2
T0 2

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 1
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Phasor Representation
Euler's Identity: e jq  cosq  j sin q

Phasor notation is developed by rewriting


using Euler's identity
v(t )  2 V cos(wt  qV )
v(t )  2 V Re e j (wt qV ) 
(Note: V is the RMS voltage)

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 2
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Phasor Representation, cont’d


The RMS, cosine-referenced voltage phasor is:
V  V e jqV  V qV
v(t )  Re 2 Ve jw t e jqV
V  V cosqV  j V sin qV
I  I cosq I  j I sin q I

(Note: Some texts use “boldface” type for


complex numbers, or “bars on the top”)
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 3
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Advantages of Phasor Analysis


Device Time Analysis Phasor
Resistor v(t )  Ri (t ) V  RI
di (t )
Inductor v(t )  L V  jw LI
dt
1t 1
Capacitor 
C0
i (t ) dt  v(0) V 
jw C
I

Z = Impedance  R  jX  Z 
R = Resistance
(Note: Z is a
X = Reactance complex number but
X
Z = R2  X 2  =arctan( ) not a phasor)
R
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 4
Power System Analysis and Design, 6e Glover, Overbye, Sarma

RL Circuit Example

V (t )  2 100cos(w t  30)
f  60Hz
R  4 X  wL  3
Z  42  32  5   36.9
V 10030
I  
Z 536.9
 20  6.9 Amps
i(t)  20 2 cos(w t  6.9)
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 5
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Complex Power
Power
p(t )  v(t ) i (t )
v(t) = Vmax cos(w t  qV )
i (t) = I max cos(w t  q I )
1
cos cos   [cos(   )  cos(   )]
2
1
p(t )  Vmax I max [cos(qV  q I ) 
2
cos(2w t  qV  q I )]
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 6
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Complex Power, cont’d


Average Power
1
p (t )  Vmax I max [cos(qV  q I )  cos(2wt  qV  q I )]
2
1T
Pavg  
T0
p (t )dt

1
 Vmax I max cos(qV  q I )
2
 V I cos(qV  q I )

Power Factor Angle =  =qV  q I


© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 7
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Complex Power
S  V I  cos(qV  q I )  j sin(qV  q I ) 
 P  jQ
(Note: S is a complex number but not a phasor)
 V I *

P = Real Power (W, kW, MW)


Q = Reactive Power (var, kvar, Mvar)
S = Complex Power (VA, kVA, MVA)
Power Factor (pf) = cos
If current leads voltage then pf is leading
If current lags voltage then pf is lagging
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 8
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Complex Power, cont’d


Relationships between real, reactive and complex power
P  S cos 

Q  S sin    S 1  pf 2

Example: A load draws 100 kW with a leading pf of 0.85.


What are  (power factor angle), Q and S ?
  -cos 1 0.85  31.8
100kW
S   117.6 kVA
0.85
Q  117.6sin(31.8)  62.0 kVar
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 9
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Conservation of Power
 At every node (bus) in the system
– Sum of real power into node must equal zero
– Sum of reactive power into node must equal zero
 This is a direct consequence of Kirchhoff’s current law, which
states that the total current into each node must equal zero.
– Conservation of power follows since S = VI*

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 10
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Conservation of Power Example


Earlier we found
I = 20-6.9 amps

S  V I *  10030  206.9  200036.9 VA


  36.9 pf = 0.8 lagging
SR  VR I *  4  20  6.9 206.9
2
PR  1600W  I R (Q R  0)
SL  VL I *  3 j  20  6.9 206.9
2
Q L  1200 var  I X (PL  0)
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 11
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Power Consumption in Devices


Resistors only consume real power
2
PResistor  I Resistor R
Inductors only consume reactive power
2
Q Inductor  I Inductor X L
Capacitors only generate reactive power
2 1
QCapacitor   I Capacitor X C XC 
wC
2
VCapacitor
QCapacitor   (Note-some define X C negative)
XC
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 12
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Example
First solve
basic circuit

400000 V
I   4000 Amps
1000 
V  400000  (5  j 40) 4000
 42000  j16000  44.920.8 kV
S  V I *  44.9k20.8 4000
 17.9820.8 MVA  16.8  j 6.4 MVA
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 13
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Example, cont’d
Now add additional
reactive power load
and re-solve

Z Load  70.7 pf  0.7 lagging


I  564  45 Amps
V  59.713.6 kV
S  33.758.6 MVA  17.6  j 28.8 MVA

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 14
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Power System Notation


Power system components are usually shown as
“one-line diagrams.” Previous circuit redrawn
17.6 MW 16.0 MW
28.8 MVR -16.0 MVR

59.7 kV 40.0 kV

17.6 MW
16.0 MW
28.8 MVR
16.0 MVR

Generators are Transmission lines


Arrows are used
are shown as a
shown as circles to show loads
single line
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 15
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Reactive Compensation
Key idea of reactive compensation is to supply reactive
power locally. In the previous example this can
be done by adding a 16 Mvar capacitor at the load
16.8 MW 16.0 MW
6.4 MVR 0.0 MVR

44.94 kV 40.0 kV

16.8 MW
16.0 MW
6.4 MVR
16.0 MVR
16.0 MVR

Compensated circuit is identical to first example with


just real power load
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 16
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Reactive Compensation, cont’d


 Reactive compensation decreased the line flow from 564
Amps to 400 Amps. This has advantages
– Lines losses, which are equal to I2 R decrease
– Lower current allows utility to use small wires, or
alternatively, supply more load over the same wires
– Voltage drop on the line is less
 Reactive compensation is used extensively by utilities
 Capacitors can be used to “correct” a load’s power
factor to an arbitrary value.

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 17
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Power Factor Correction Example


Assume we have 100 kVA load with pf = 0.8 lagging,
and would like to correct the pf to 0.95 lagging
S  80  j 60 kVA   cos 1 0.8  36.9
1
PF of 0.95 requires desired  cos 0.95  18.2
Snew  80  j (60  Qcap )
60 - Qcap
 tan18.2  60  Qcap  26.3 kvar
80
Qcap  33.7 kvar
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 18
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Distribution System Capacitors

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 19
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Balanced 3 Phase () Systems


 A balanced 3 phase () system has
– three voltage sources with equal magnitude, but with an
angle shift of 120
– equal loads on each phase
– equal impedance on the lines connecting the generators to
the loads
 Bulk power systems are almost exclusively 3
 Single phase is used primarily only in low voltage, low
power settings, such as residential and some commercial

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 20
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Balanced 3 – No Neutral Current

I n  I a  Ib  I c
V
In  (10  1   1  
Z
S  Van I an
*
 Vbn I bn
*
 Vcn I cn
*
 3 Van I an
*

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 21
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Advantages of 3 Power
 Can transmit more power for same amount of wire (twice
as much as single phase)
 Torque produced by 3 machines is constant
 Three phase machines use less material for same power
rating
 Three phase machines start more easily than single phase
machines

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 22
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Three Phase – Y Connection


 There are two ways to connect 3 systems
– Wye (Y)
– Delta ()

Wye Connection Voltages


Van  V  
Vbn  V   
Vcn  V   

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 23
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Y Connection Line Voltages


Vcn Vab
Vca
-Vbn
Van
Vbn
(α = 0 in this case)
Vbc
Vab  Van  Vbn  V (1  1  120
 3 V   30
Line to line voltages are
Vbc  3 V   90 also balanced
Vca  3 V   150
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 24
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Y Connection, cont’d
 Define voltage/current across/through device to be phase
voltage/current
 Define voltage/current across/through lines to be line
voltage/current

j
VLine  3 VPhase 130  3 VPhase e 6

I Line  I Phase
S3  3 VPhase I Phase
*

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 25
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Delta Connection
For the Delta
phase voltages equal
line voltages

For currents
Ic Ia  I ab  I ca
Ica
 3 I ab   
I b  I bc  I ab
Ib Iab Ic  I ca  I bc
Ibc
Ia S3  3 VPhase I Phase
*

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 26
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Three Phase Example


Assume a -connected load is supplied from a 3
13.8 kV (L-L) source with Z = 10020

Vab  13.80 kV
Vbc  13.8 0 kV
Vca  13.80 kV

13.80 kV
I ab   138  20 amps
 
I bc  138  140 amps I ca  1380 amps
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 27
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Three Phase Example, cont’d


I a  I ab  I ca  138  20  1380
 239  50 amps
I b  239  170 amps I c  2390 amps

S  3  Vab I ab
*
 3  13.80kV  138 amps
 5.7 MVA
 5.37  j1.95 MVA
pf  cos 20   lagging

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 28
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Δ-Y Transformation
To simplify analysis of balanced 3 systems:
1) Δ-connected loads can be replaced by
1
Y-connected loads with ZY  Z 
3
2) Δ-connected sources can be replaced by
VLine
Y-connected sources with Vphase 
330

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 29
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Δ-Y Transformation Proof

From the  side we get


Vab Vca Vab  Vca
Ia   
Z Z Z
Vab  Vca
Hence Z 
Ia
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 30
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Δ-Y Transformation, cont’d


From the Y side we get
Vab  ZY ( I a  I b ) Vca  ZY ( I c  I a )
Vab  Vca  ZY (2 I a  I b  I c )
Since Ia  I b  I c  0  I a   I b  I c
Hence Vab  Vca  3 ZY I a
Vab  Vca
3 ZY   Z
Ia
1
Therefore ZY  Z
3
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 31
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Three Phase Transmission Line

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 32
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Analysis


 Per phase analysis allows analysis of balanced 3 systems
with the same effort as for a single phase system
 Balanced 3 Theorem: For a balanced 3 system with
– All loads and sources Y connected
– No mutual Inductance between phases

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 33
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Analysis, cont’d


 Then
– All neutrals are at the same potential
– All phases are COMPLETELY decoupled
– All system values are the same sequence as sources. The
sequence order we’ve been using (phase b lags phase a
and phase c lags phase a) is known as “positive”
sequence; later in the course we’ll discuss negative and
zero sequence systems.

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 34
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Analysis Procedure


To do per phase analysis
1. Convert all  load/sources to equivalent Y’s
2. Solve phase “a” independent of the other phases
3. Total system power S = 3 Va Ia*
4. If desired, phase “b” and “c” values can be
determined by inspection (i.e., ±120° degree phase
shifts)
5. If necessary, go back to the original circuit to
determine line-line values or internal  values.

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 35
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Example


Assume a 3, Y-connected generator with Van = 10 volts
supplies a -connected load with Z = -j through a
transmission line with impedance of j0.1 per phase. The
load is also connected to a -connected generator with
Va″b″ = 10 through a second transmission line which also
has an impedance of j0.1 per phase.

Find
1. The load voltage Va′b′
2. The total power supplied by each generator, SY and S

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 36
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Example, cont’d

First convert the delta load and source to equivalent


Y values and draw just the "a" phase circuit
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 37
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Example, cont’d

To solve the circuit, write the KCL equation at a'


1
(Va  10)(10 j )  Va (3 j )  (Va 
' ' '
   j  
3
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 38
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Example, cont’d


To solve the circuit, write the KCL equation at a'
1
(Va  10)(10 j )  Va (3 j )  (Va 
' ' '
   j  
3
10
(10 j  60)  Va' (10 j  3 j  10 j )
3
Va'  0.9  volts Vb'  0.9  volts
Vc'  0.9 volts '
Vab  1.56 volts

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 39
Power System Analysis and Design, 6e Glover, Overbye, Sarma

Per Phase Example, cont’d


*
 Va  Va 
'
Sygen  3Va I a*  Va    5.1  j 3.5 VA
 j 0.1 
 ' *
" Va
"
 Va
Sgen  3Va    5.1  j 4.7 VA
 j 0.1 

© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in
whole or in part. 40

S-ar putea să vă placă și