Component Check

RS232 Cable
-Supplied

MJ10-22-CS25 (RJ11 to DB9 converter)


-Supplied

MJ10-22-CS35 (USB to Serial converter)


-Additional
Check physical connections

• Serial cable plugged into Port 1 on PLC


• Jumpers are set for RS232 communication

• Check part numbers


-Serial cable MJ10-22-CS25
-USB adapter MJ10-22-CS35

Port 1
USB programming cable

• Some of our units can be programmed


through a Mini-USB programming port
- (If equipped, IE- V1210/V1040/V570)
• No other hardware is required for USB
connection

Note that COM port 1 function is suspended when the USB


port is physically connected to the PC.
USB Driver

USB port supports only OS and project download.

• If requested to use Windows Update--do not


accept this option; "Skip obtaining driver software
from Windows Update".
• Install only the driver provided by VisiLogic.
• The USB cable must be disconnected during
the installation.
Driver Check
Check software settings

• Baud rate
- Standard-57600 baud
- Enhanced-115200 baud

• Check Device Manager to ensure


-Port has no errors or warnings
(PC port is confirmed here)

• Select “Get OPLC Info” button to


check/confirm PLC
Check for O/S updates

• Updates automatically
if required.

• Requires connection to
internet.
Has a new O/S been released?
You will receive one of 2 messages.

-Up to date.

-Updating files
Check & perform an O/S update
Updating an OS

• The System Upgrade Wizard will guide you through the


update of the OS
O/S Updating

– A Progress Bar will show you the operations and


current steps in progress
Finish Update of O/S

• Successful OS Update
O/S Update Not Required