HUAWEI EMU

By Jefferson Simarmata

www.huawei.com

HUAWEI Confidential
The connection between EMU and BTS

RJ45
DB9

MON1 UEIU/UPEU
(RJ45)

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


Cable Power

Connect to SPARE1

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


DIP Switch on DEMU

SW1 - SW8

SW9 – SW16

SW17 – SW24

SW25 – SW32

SW_RST

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


Special Alarm
 Water Immersed Sensor
 Temperature and Humidity Sensor
 Smog
 Door Sensor----> Move to switch 9 (SW9)

Special Alarm

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


Special Alarm
Temp & Humi Smog

Water

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


External Alarm

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


How to find main fail, module rectifier fail and
Battery low voltage ??
Turn off one MCB AC Main, check all cable
output by Multimeter, which cable short/open
because this alarm, will be have 2 alarm
appear:
1st “Main fail “
2nd “Module rectifier fail” (already give label
before)
Check load current, go to
“configuration low load” and
set low load limit higher than
load current, check all cable
output by Multimeter, which
cable short/open because this
alarm give label “Battery low
voltage”
Hold until alarm appear, check all cable output by
Multimeter, which cable short/open because this
alarm give label “Module rectifier fail”
Return it back to normal:
Turn off one MCB AC Main

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


Configuration in LMT

Add DEMU board in subrack 2 slot 1

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


Configure DEMU board attributes

Gate Magnetism disabled because gate sensor move to Switch 9


Water Immersed in low level because sensor output NO (Normaly Open)

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


32 Switch can used

If sensor output NC (Normally Close), switch valid level High level


If sensor output NO (Normally Open), switch valid level Low level

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


Alarm auto clear permit

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


How to rename alarm ID in LMT base on alarm ID in IM2000 (1)
Use MML and run this command;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=1, SW=OPEN, AID=65384, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=19, SW=OPEN, AID=65420, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=20, SW=OPEN, AID=65422, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=21, SW=OPEN, AID=65424, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=2, SW=OPEN, AID=65386, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=3, SW=OPEN, AID=65388, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=4, SW=OPEN, AID=65390, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=5, SW=OPEN, AID=65392, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=6, SW=OPEN, AID=65394, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=7, SW=OPEN, AID=65396, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=8, SW=OPEN, AID=65398, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=9, SW=OPEN, AID=65400, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=10, SW=OPEN, AID=65402, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=11, SW=OPEN, AID=65404, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=12, SW=OPEN, AID=65406, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=13, SW=OPEN, AID=65408, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=14, SW=OPEN, AID=65410, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=15, SW=OPEN, AID=65412, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=16, SW=OPEN, AID=65414, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=17, SW=OPEN, AID=65416, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=18, SW=OPEN, AID=65418, PT=BOOL;

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


How to rename alarm ID in LMT base on alarm ID in IM2000 (2)

 In LMT open “Alarm Maintenance”, click “Query Alarm Configuration”

Start Alarm ID from:


65424

Start Alarm ID from:


65384

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


How to rename alarm ID in LMT base on alarm ID in IM2000 (3)
 After Query Alarm Configuration

Right click an alarm name and then “Set Environment Alarm Configuration”

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential


How to rename alarm ID in LMT base on alarm ID in IM2000 (4)
 Alarm name and alarm saverity after config;

HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential