Documente Academic
Documente Profesional
Documente Cultură
tan δ= IR/ IC
microvoids
Cracks
25/3/2019 REVA University 32
Types of partial Discharge
1. Corona or gas discharge- due to non uniform
field, sharp edge of electrodes etc.
2. Surface discharge- interfacing of different
dielectric material results over stress
4.Treeing channels
25/3/2019 REVA University 33
25/3/2019 REVA University 34
Partial Discharge Equivalent Circuit
• If there are any partial discharges in a dielectric material, these can
be measured only across its terminal.
• Figure shows a simple capacitor arrangement in which a gas filled
void is present. The partial discharge in the void will take place as
the electric stress in the void is er times the stress in the rest of the
material where er is the relative permittivity of the material.
• Due to geometry of the material, various capacitances are formed as
shown in Fig (a).
• Flux lines starting from electrode and terminating at the void will
form one capacitance Cb1 and similarly Cb2 between electrode B and
the cavity.
• Cc is the capacitance of the void. Similarly Ca1 and Ca2 are the
capacitance of healthy portions of the dielectric on the two sides of
the void. Fig. (b) shows the equivalent of 6.19 (a) where Ca = Ca1 +
Ca, and Cb = Cb1Cb2/(Cb1 + Cb2) and Cc is the cavity capacitance. In
35
general Ca >> Cb >> Cc.
Partial Discharge Equivalent Circuit
25/3/2019 REVAUniversity 28
Discharge Detection Methods
• Various methods are available for measuring
discharge detection especially for analyzing
Partial Discharge (PD).
1.Discharge Detection using ‘straight detectors’
2.Balanced detection methods
3.Narrow band &Wide band circuits
25/3/2019 REVAUniversity 28
1.Discharge Detection using ‘straight
detectors’
Input side
5. Fifty per cent flashover voltage – This is the voltage which has a
probability of 50% flashover when applied to a test object which
results loss of insulation strength temporarily.
Where,
Insulation coordination 6
0
Insulation Problem
• It occurs due to following
– Determination of line insulation
– Selection of Basic Impulse Insulation level (BIL)
and the insulation of other equipment
– Selection of lightning arrester.
Insulation coordination 6
1
• Lightning Impulse Withstand level (or) BIL
– Basic impulse level is established for each system
nominal voltage for different equipment. Various
equipment should have their BIL value above the
system protection level using lightning arresters by
a suitable margin.
• For voltage < 400kv
– If BIL is chosen correctly, the equipment will have
an adequate switching surge level
• For voltage > 400kv
– Switching surge magnitude are higher than the
lightning over voltage, then certain condition to
be adopted.
Insulation coordination 5
Ideal requirement for a protective devices :
• It should not usually flashover for power
frequency over voltages.
• The volt-time char of the devices must be lie
below the withstand voltage of insulation.
• It should be capable of discharging high
energy contained in surges and recover
insulation strength quickly.
• It should not allow power frequency follow on
current to flow.
Insulation 63
coordinati
Volt-Time Characteristics
• Proper insulation coordination would ensure
that the volt time char of the equipment will
lie above the volt time char of the protective
devices as shown.
64
• Case (i): Assuming the surge voltage rise is
shown in curve 1,
– The rate of rise of surge is less than thecritical
slope (curve X)
– The rod gap flashes and protects the transformer
insulation.
• Case (ii): Assuming the surge voltage rise is
shown in curve 2,
– The rate of rise of surge is greater than thecritical
slope (curve X)
– The rod gap cannot protects the transformer and
only surge arrester can protect the transformer.
Insulation 65
coordinati
Line Insulation
• The insulation of line is based on the consideration
of lightning and switching surges and power
frequency over voltages.
• The line insulation must be provided to prevent a
flash over due to power frequency and switching
surges and also considering rain, dust, insulator
pollution factor.
• Sometimes one or two disc in the string insulator
may be defective.
• So, lines upto 220kv, one extra disc must be provided
and for upto 400kv, twoextra disc must be provided.
Insulation 66
coordinati
• The line insulation is not directly related to the
insulation level of the stationequipment.
• But the impulse flash over of the line insulators
determines the highest surge voltage that can
travel into the station from a distance.
• Over head guard wires are used to protect the
line and should be kept at proper distance above
secondary line conductor.
Insulation 67
coordinati
Surge Arrester Selection
• The selection of surge arrester voltage rating for
EHVand UHVsystem depends on
– The rate of rise voltage
– Operating char
• The following types of arresters are used for this
purpose
– Silicon carbide arresters with spark gap
– Silicon carbide arrester with current limitinggap.
– Zinc oxide or gapless metal oxide arrester
Insulation 68
coordinati
• Advantage of ZnO arrester for EHVsystem
– Simple in consideration
– Flat V-I char over a wide current range
– The absence of a spark gap that produces steep
voltage gradients when sparking occurs.
• Disadvantage of ZnO arrester
– Continues flow of power frequencycurrent.
– Power loss is high.
Insulation 69
coordinati
Location of lightning arrester
• Lightning arrester should be installed on the
transformer terminal, considering the following
factor
– Shielding against the direct strokes
– BILof the transformer winding
– BIL of the circuit breaker, isolator and other
substation equipment.
– Residual discharge voltage of lightning arrester
– No of line entering into thesubstation
– Construction of over head line
– Layout of substations.
Insulation 70
coordinati
Equipment insulation level and insulation
coordination of substation
• The component of the substation are transformer,
circuit breaker, isolators, instrument transformer.
• Insulation coordination of substation involves the
number of location of surge arrester to be decided to
minimize the overall cost.
• To protect the transformer in high voltage substation,
the arrester must be provided between transformer
and circuit breaker.
• The protective level of the substation insulation
depends on,
– The station location
– The protective of arrester
– Line shielding used.
Insulation 71
coordinati
The Ideal requirements of a Protective Device in
HV and EHV Power Systems
1. The flashover voltage of a protective device is chosen such that
it will not operate for switching overvoltages and other power
frequency and its harmonic overvoltages.
2. For EHV systems, it may be economical to use a protective
device for limiting the overvoltages due to lightning as well as
switching surges to a particular level.
3. It should not usually flashover for power frequency
overvoltages.
4. The volt-time characteristics of the device must lie below the
withstand voltage of the protected apparatus or insulation. The
marginal difference between the above two should be adequate
to allow for the effects of distance, polarity, atmospheric
conditions, changes in the characteristics of the devices due to
various factors, etc.
5. It should be capable of discharging high energies contained in
surges and recover insulation strength quickly.
Selection criteria of surge arrester voltage rating for
EHV and UHV systems & Types of surge arrester.
Insulation coordination
74
THANK YOU