Sunteți pe pagina 1din 16

LOAD SHEDDING OPERATION

GENERAL OVERVIEW
SYSTEM

PT TECHNICAL SOUTH EAST ASIA


1

SAMPOERNA KARAWANG PROJECT


13 - 07 - 2017
LOAD SHEDDING OPERATION

First we are need to know how general Single Line Diagram


(SLD) which allows us to monitor electrical power consumtion
factory and the feeder status CB
For the single line we can view by press the button on HMI

PT TECHNICAL SOUTH EAST ASIA


Screen which is will sow the SLD screen

The Single Line Diagram at HMI only show for general SLD

2
LOAD SHEDDING OPERATION

SLD Overview

PT TECHNICAL SOUTH EAST ASIA


3
LOAD SHEDDING OPERATION
Load shedding operation it’s sequence command for open
feeder during one of source power loss / fault to prevent the overload
for the Gas Engine Generator
Load shedding command have 3 group step for the shedding

PT TECHNICAL SOUTH EAST ASIA


command :
Group 1 : Group 2 : Group 3 :
- Feeder 52F2 - Feeder 52F5 - Feeder 52F7
- Feeder 52F4
- Feeder 52F6
- Feeder Chiller 1,2,3,4
- Feeder Compressor

4
LOAD SHEDDING OPERATION

Load Shedding System (LSS) for the overview press the


button LSS at the bottom tool bar and press

for the next LSS overview, and for the previews LSS overview press

PT TECHNICAL SOUTH EAST ASIA


button

Load Shedding System (LSS) need to be activated at LSS


overview in button Enable LSS and button
Enable under frequency LSS

5
LOAD SHEDDING OPERATION

For the log in password touch one of the enactive numeric


value or button for show the pop up password window

PT TECHNICAL SOUTH EAST ASIA


touch one of table name or Password and the keyboard will
show, input the user name and password “admin”

6
LOAD SHEDDING OPERATION

for the log in press the button and press the

For back to the previews overview screen or press the for


back to home screen

PT TECHNICAL SOUTH EAST ASIA


7
LOAD SHEDDING OPERATION

For the overview LSS we can see the logging of LSS load
previews before one of source power trip (GEG or PLN), and
monitoring fix set point under frequency

PT TECHNICAL SOUTH EAST ASIA


All overview in LSS screen HMI only for the monitoring
there’s no adjustable point presenting.

for the disable and enable LSS need password and


username to access where the password is : admin, user name is :
admin

8
LOAD SHEDDING OPERATION

LSS Overview page 1

PT TECHNICAL SOUTH EAST ASIA


9
LOAD SHEDDING OPERATION

LSS Overview page 2

PT TECHNICAL SOUTH EAST ASIA


10
LOAD SHEDDING OPERATION

LSS Overview page 3

PT TECHNICAL SOUTH EAST ASIA


11
LOAD SHEDDING OPERATION

LSS Overview page 4

PT TECHNICAL SOUTH EAST ASIA


12
LOAD SHEDDING OPERATION

After Load Shedding give command to open feeder, alarm


will be activated and HMI will recorded in alarm online and event
online

PT TECHNICAL SOUTH EAST ASIA


For resetting the Load Shedding command press the reset
button at Door MCP Panel for 5 seconds and see the event online
after 5 seconds the massage event LSS Reset will be shows and
recorded at Event History

After resetting the Load Shedding, then the feeder cubicle


can do the closing CB.

13
LOAD SHEDDING OPERATION

Alarm Online

PT TECHNICAL SOUTH EAST ASIA


14
LOAD SHEDDING OPERATION

Event Online

PT TECHNICAL SOUTH EAST ASIA


15
LOAD SHEDDING OPERATION

PT TECHNICAL SOUTH EAST ASIA


THE END

16