INTRODUCTION
 Brief History
 Findings on the “OLD STRUCTURAL PLAN”
<15 Km from Fault System Seismic Source Type A
SEISMIC PARAMETER
Seismic Zone (Z) 0.4
Importance Factor (I) 1.5
Soil Profile (Sc) C
Seismic Force Resisting Factor (R) 8.5
Near Source Factor 1.0
 STRUCTURAL ANALYSIS
 FRAMING PLAN
 DESIGN SUMMARY
FOUNDATION PLAN
MEZZANINE FRAMING PLAN
ROOFDECK FRAMING PLAN
 STAAD
REINFORCEMENT BAR
Philippine National Standard (PNS 49:2002)

ASTM Standard (ASTM A615/A706) American Society


for Testing and Materials (now known as ASTM
International).
BEAM TOP BARS OTHERS
Ø Lap Length Ø Lap Length
10mm = 400mm 10mm = 400mm
12mm = 400mm 12mm = 400mm
16mm = 600mm 16mm = 600mm
20mm = 900mm 20mm = 800mm
25mm = 1400mm 25mm = 1200mm
 10-meters frontage
 8-meter frontage
 City fire station class
Issues and Concern
 Steel Deck used for Slab
 Mezzanine Provision, Beam and Slab
 Retrofitting of station that implemented the “Old
Structural Plan”