Run Back
Permit
Turbine Run Back
Run Back Permits
Load Reject /
MFT
T.Master Auto
TBN BYPS CV
FDF Run Back
A FDF
SET IF LOAD IS
B FDF
> 186 MW
FDF RUN BACK FDF RUN BACK
OPRATED
RESET IF LOAD IS
< 186 MW
RUN BACK
PERMIT
MW DEMAND
181 MW
REJECTION RATE
1086 MW/MIN
BFP Run Back
A BFP
B BFP
SET IF LOAD IS
C BFP > 150 MW
BFP RUN BACK BFP RUN BACK
OPRATED
RESET IF LOAD IS
< 150 MW
RUN BACK
PERMIT
MW DEMAND
145 MW
REJECTION RATE
1086 MW/MIN
AH Run Back
A AH
SET IF LOAD IS
B AH
> 186 MW
AH RUN BACK AH RUN BACK
OPRATED
RESET IF LOAD IS
< 186 MW
RUN BACK
PERMIT
MW DEMAND
181 MW
REJECTION RATE
1086 MW/MIN
GRF Run Back
A GRF
SET IF LOAD IS
B GRF
> 223 MW
GRF RUN BACK GRF RUN BACK
OPRATED
RESET IF LOAD IS
< 223 MW
RUN BACK
PERMIT
MW DEMAND
217.2 MW
REJECTION RATE
108.6 MW/MIN
BCP Run Back
A BCP
SET IF LOAD IS
B BCP
> 222.2 MW
BCP RUN BACK BCP RUN BACK
OPRATED
RESET IF LOAD IS
< 222.2 MW
RUN BACK
PERMIT
MW DEMAND
217.2 MW
REJECTION RATE
362 MW/MIN
CP Run Back
A CP
B CP
SET IF LOAD IS
C CP > 196.1 MW
CP RUN BACK CP RUN BACK
OPRATED
RESET IF LOAD IS
< 196.1 MW
RUN BACK
PERMIT
MW DEMAND
199.1
REJECTION RATE
362 MW/MIN
CWP Run Back
A CWP
B CWP
SET IF LOAD IS
C CWP > 205.1 MW
CWP RUN BACK CWP RUN BACK
OPRATED
RESET IF LOAD IS
< 205.1 MW
RUN BACK
PERMIT
MW DEMAND
199.1
REJECTION RATE
362 MW/MIN
Initial Pressure Regulator OPE
GEN OUTPUT ABN
MAIN STEAM
IPR IN
PRESSURE ABN
IPR IN/OUT
PMS CONTROL
MODE
s
GENERATOR LOAD
R
PMS CONTROL
TURBINE TRIP GEN CB 52 C ON GEN LOAD GEN LOAD
MODE
Vacuum OPE
COND. VAC. ABN
VACUUM UNL. IN
VACUUM
UNL.OPE.
VACUUM
PRESSURE
s
R
s
LLR OPE
GEN LOAD
R
GEN LOAD
TURBINE TRIP
GEN. CB.52C ON