Documente Academic
Documente Profesional
Documente Cultură
ELECTRICAL SYSTEM
NON-
Electrical system includes the following: ELECTRIC CONVENTIONAL
ELECTRIC
FILLINGS AND
ENERGY
• Nature and magnitude of load
SUPPLY INSTALLATIONS
• Air conditioning
• Isolation transformers for operation room complex
• Switchgears and control panels inside, in a shaded/dust
• free environment.
DUAL SUPPLY
IN ESSENTIAL
CONTROL
PANEL AND
• All important areas like emergency, OT, ICU to have dual supply.
MAIN
SOURCE AREAS POWER
CIRCUITS
• Standby DG sets (noise free) with SEB, SPCB approval.
• One electrical circuit for 10 lights/ fan points.
• One power circuit for two 15 Amp sockets/1800 Watts.
ELECTRICITY
• Use of appropriate MCB.
• Steel conduits tubes more preferable than PVC tubes.
CABLES AND
ALTERNATE
SOURCE • No socket/switches in anesthetic store room.
GENERATOR
•
TRANSFORMERS
SWITCHES
NON-
CONVENTIONAL
High illumination in Admin offices, nursing station, dietary store,
• examination rooms.
• Illumination standards for different areas.
FIRE FIGHTING SYSTEM
• A Multi-Storey Hospital requires the following fire safety measures as per National Building Code, Part IV.
• 1. Fire extinguishers as per BIS-2190.
• 2. Hose reel on all floors.
• 3. Wet riser system with landing values on all floors.
• 4. Yard Hydrant system.
• 5. Automatic sprinkler system.
• 6. Manually operated electric fire alarm systems.
• 7. Automatic Detection and alarm system.
• 8. Underground static water storage tank of 50,000/1, 00,000 1ts. Capacity.
• 9. Terrace water tank of 10,000/20,000 1ts. Capacity.
• 10. One electric and one diesel pump of 2280 LPM/min and one Jockey (electrical) pump of 180 lts/min.
• 11. Emergency lighting and exist sign boards.
FIRE FIGHTING SYSTEM
•A TOTAL NUMBER OF 16 STAIRCASES AND 16 LIFTS HAVE BEEN PROVIDED
• ALL FLOORS ARE CONNECTED VERTICALLY THROUGH CENTRALLY LOCATED RAMP.
•THE OPERATION THEATRE CONSISTS OF SEPARATE INTERNAL STAIRCASE FOR DOCTORS AND NURSES.
RAMP CONNECTED
TO ALLFLOORS
ENTRANCE
STAIRCASE
RAMP
LIFTS
PATIENTS 30 LITRES/DAY
Hot water - Hot water supply to wards and
departments of the general hospital shall OTs 5 LITRES
be provided by means of electric storage
type water heaters or centralized hot PHYSIOTHERAPY 500 LITRES/DAY
water LABS 1000 LITRES/DAY
Filtered and soft water - Filtered and soft water supply is required LAUNDRY 50 LITRES/BED/DAY
in pathology laboratories and shell be supplied as requirements. ATTENDANTS 15 LITRES/BED/DAY
Cold water - Cold water supply is needed for processing tanks in film KITCHEN 10 LITRES/BED/DAY
developing room and shall be supplied as required.
WATER SUPPLY
PUMP ROOM
MUNICIPAL MAIN
• Medical Gas Distribution System is a central supply system to supply a medical gas (O2, N2O, N2), medical air, and
medical vacuum to each ward of hospital safely and conveniently through a central supply piping from medical
gas supply sources.
Design
• The outside walls of rooms for cylinder supply systems shall be
built of materials having a fire rating of at least 1 hour.
• Doors to the room shall open outwards and personnel shall be able to
open the doors from the inside without a key.
• Electrical wall fixtures in rooms for supply systems shall be positioned at
least 1.5 m (5 ft) above the floor to avoid physical damage.
• The ambient temperature in rooms for supply systems shall not exceed 40°C
for any gas and shall not be less than 15°C for nitrous oxide and carbon
dioxide.
• Ventilation: Provided that the room has venting with a
total free area of at least 465 cm2.
• The outlets of pressure relief vent pipes shall be at least 3 m from any door,
operable window, or ventilation intake
and located so that discharges will not endanger passersby.
• The ducts run throughout the buildings, branching along every kind of wards and
units.
MEDICAL GAS DISTRIBUTION SYSTEM
Color Codes:
Provided pipelines
- Nitrous Oxide N2O - Blue colored pipes
- Medical Vacuum - Yellow colored pipes
- Carbon Dioxide CO2 - Grey colored pipes
3. All pipelines for medical gases shall be routed in such a way that they are not
exposed to a temperature less than 50 C
above the dew point of the gas at pipeline pressure.
Maximum intervals between supports for gas pipes
MEDICAL GAS DISTRIBUTION SYSTEM
Components Provided:
• Medical Gas Pipelines
• Shutoff valves
• Warning and Alarm System
• Bedhead Units
• Vacuum Pipe
Bedhead Unit
Warning & Alarm System Medical Gas Pipeline Medical Gas duct
MEDICAL GAS DISTRIBUTION SYSTEM
GAS SUPPLY
D.G.SET
Ductwork AHU
HVAC SYSTEM
AREAS CONSIDER FOR HVAC DESIGN:
Critical Care Spaces:
• single duct terminal reheat or double duct systems is used.
• Simultaneous temperature, humidity, and pressurization control requirements for
these spaces preclude the use of other types of systems.
Administrative Areas:
• single duct reheat, multi-zone, VAV, or dual-duct systems, with perimeter radiation
when required.
Outpatient Clinics:
General ward in patient
• single duct reheat, dual duct, VAV, or multi-zone systems can be used.
• Outpatient clinics may be served by single duct reheat, dual duct, VAV, or multi-zone
systems.
Patient Bedrooms:
• dual duct, multi-zone, VAV, or single duct reheat systems can be used.
• Perimeter radiation systems (radiant panels) may be considered in conjunction with
these air systems.
Patient Isolation Bedrooms:
• airflow systems can be used.
• Pressurization control equipment serving Protective Isolation and Disease Isolation
Bedrooms shall be connected to the emergency electrical power system. Patient isolation bedroom
SINGLE DUCT SYSTEM
• The simplest and most common of the “All-
Air” central systems
• either hot air or cold air flows, but not both
simultaneously
• control is based on temperature and humidity
ratio measured at a single point
VAV SYSTEM
• system delivers a constant air volume to the
conditioned space irrespective of load.
• The air conditioner cycles “on and off”, or
chilled water is modulated for a chilled water
cooling coil, as the load varies.
• system changes the quantity of air supplied to
a space in response to changes in loads.
HVAC SYSTEM
COOLERS ARE ALSO PROVION
• For air conditioning a chill water system was installed. THE TERRACE TO COOL
• A.C. Plant room was located in the basement . SUMMERS.(STACK EFFECT)
• Four air chilled centrifugal chillers were there to provide chilled water supply to A.H.U.
• Three hot water generator of 400 kw capacity were provided for
Heating .
• There are 4 no’s condenser water pumps and 3 no’s hot water pumps located in the
plant room.
• A.C. Ducts were covered by metallic false ceiling .
• All A.C. Ducts were properly insulated by glass wool .
DG ROOM
LIFT LOBBY
STAIRCASE
FIRE DUCTS
WATER SUPPLY
STP
DG YARD OXYGEN
MANIFOLD
AHU UNIT
AHU room are provided near spaces which have centralized
air conditioning Spaces such as-
• MRI room
• CT scan room
• cardio
• Labs
• emergency room
• lobby
• OPD
AHU ROOMS
MEDICAL WASTE MANAGEMENT
VACCUM ROOM
WASTE COLLECTION AREA
D.Y.PATIL HOSPITAL,NERUL
FIRE FIGHTING SYSTEM
SITE HYDRANT LOCATION
DISTANCE BETWEEN
BUILDING HYDRANT IS 15 M
FIRE FIGHTING
PUMP ROOM
GAS STATION
MEDICAL WASTE MANAGEMENT
VENTILATION SYSTEM