PRESENTED BY :
SOUMYADEEP MUKHERJEE
ROLL NO. :11701616024
ELECTRICAL ENGINEERING DEPT.
RCC INSTITUTE OF INFORMATION TECHNOLOGY
SPAN OF TRAINING:-21ST JUNE 2019 TO 18TH JULY 2019
CONTENT
• INTRODUCTION
• TPS
• ELECTRICAL MAINTENANCE
• GT UNIT
INTRODUCTION
SUPERIOR KEROSENE
ATF
RTF
FURNACE OIL
FIRE AND SAFETY DEPARTMENT
● On site industrial fire department comprised of full time career personnel.
● Volunteer emergency response team members from within the various work groups.
● Fire station has the following apparatus: 2 specialized foam engines, recue/hazmat
truck, 2 foam tenders, 3 squads and a utility truck.
TPS (THERMAL POWER STATION)
BASIC OVERVIEW OF THERMAL POWER PLANT
● This is a CPP(captive power plant) i.e. the plant uses its generated power and doesn’t
sell the power.
● There are 4 boilers, 4 TGs and 4 transformers in the TPS.
● Among the 4 transformers, 3 of them are 6.6/0.415kV and 1 one of them is 11/6.6kV.
● In TPS there are 4 auxiliary generation bus i.e. AG1-AG4, which are fed from the
4TGs.
● From the auxiliary generation bus the distribution bus bars i.e. A01-A04 are fed.A05
and A06 is fed from the grid of state electricity board which is used in case of any
fault in the refinery so as to maintain the continuity of supply.
SLD OF POWER GEN. AND DISTRIBUTION
ELECTRICAL EQUIPMENTS OF A THERMAL
POWER SYSTEM
● Transformer
● Alternator
● Exciter
● Voltage Regulator
● Circuit Breaker
● Current Transformer
TRANSFORMERS
● In TPS there are 4 transformers, among them 3 of them are
6.6/0.415 KV which are used to run LT machines and 1 of them is
11/6.6KV for HT machines and distribution.
● All the 6.6/0.415 KV transformers are having ONAN type of cooling.
The 11/6.6 KV transformer is having ONAN & ONAF type of cooling.
● Ascar oil is used in the transformers for cooling purpose.
● Bucholz relay is used for protection against internal faults.
ALTERNATOR
● In CPP-1 there are 4 alternators, among them 3 are 10.5MW and 1 of them is 16.5MW.
● The alternator which is having the rating of 16.5 MW also have a brushless exciter and a
stroboscopic panel.
● All the alternators have speed of 3000 rpm.
● All the alternators are coupled with the turbine and only the 4th alternator is having a
gearbox as the speed of turbine of TG4 is 6000 rpm.
● All the TG’s are gradually started using a baring motor which provides the initial torque
to the system and it is also used for gradually stopping the motor so as to avoid breaking
of the shaft due to excessive heating.
● The static part of the alternator i.e stator has 3 phase double star winding from which 3
phase AC output power is available at a rated voltage of 6.6 kV.
● The rotating part of alternator i.e. rotor has field winding by controlled DC power
supplied from DAVR(Digital Automatic Voltage Regulator)
EXCITER
● The type of excitation system used is
current.
subsequent to a fault.
● The types of circuit breaker used in the plant are air circuit breaker(ACB), vaccum
circuit breaker(VCB), SF6 oil circuit breaker.
● These circuit breakers can be operated manually or by remote control under normal
conditions and automatically under fault conditions.
CURRENT TRANSFORMER
● Current transformers (CT) is primarily used for measuring high currents.
● CT’s are step up transformers which are connected to an ammeter for measuring the
current flowing through the circuit.
● CT’s are also used for providing protection to the alternators and transformers by
following differential protection or MERZ-PRICE protection scheme.
ELECTRICAL MAINTENANCE
MOTOR MAINTENANCE
There are 3 types of maintenance :
● Preventive maintenance
○ A schedule(6 months)
○ B schedule(1 year)
○ C
● Predictive maintenance
○ Temperature, Vibration, IR value
● Breakdown maintenance
● Troubleshooting
ELECTRICAL MAINTENANCE(CONT.)
TRANSFORMER MAINTENANCE