Substation Automation and Protection Training

REB500
HMI500 Settings

© ABB Group
31 August 2019 | Slide 1
HMI500 Settings
Scope

 CT Configuration
 I/O Configuration
 Busbar Protection Parameters
 Breaker Failure Parameters
 System Parameters
 Event Configuration
 Disturbance Recorder Configuration
HMI500 Settings
CT configuration
Current
transformer primary CT nominal
current R, S, T

Invert CT orintation

secondary CT nominal current


primary CT nominal R, S, T, N
current ratio N (only for information -
selection made by cabling)
HMI500 Settings
In- & Output configuration : Double BB
single line
diagram

overview

binary outputs
module
inputs
HMI500 Settings
BBP In- & Output configuration : Feeder
inputs

Double BB:
image Q1 & Q2 (open & close)
outputs

“21110_TRIP” = tripping command from intertripping


system to CR 11 - 16 (RST main 1 & main2)
HMI500 Settings
BBP In- & Output configuration : Coupler
inputs

Double BB:
image Q0 (open & close) and
outputs Q0 closing command !!!

“21110_TRIP” = tripping command from intertripping


system to CR 11 - 16 (RST main 1 & main2)
HMI500 Settings
Input configuration : CB & Isolator Image (Position)

images must have 2 aux. contacts

“closed”
“open” indication indication

event
recording

event send to the


event send
eventlist CU / BU
to IBB 1 / 2
HMI500 Settings
Busbar Protection

Minimum short current (IKmin)

Stability factor K

pick up value of
time delay for differential current
differential current supervision
alarm
HMI500 Settings
BFP Input configuration
inputs

“13605_Trip transferred” = “trip re-


direction” functionality (CB under pressure)

Start BFP Main 1 with single phase AR

Start BFP Main 2 with single phase AR

Start BFP Main 1 without single phase AR

Start BFP Main 2 without single phase AR


HMI500 Settings
BFP Output configuration
outputs

“23110_BFP REMOTE TRIP” = tripping command


from BFP to the remote CB (after t1) to CR 6 - 7
(RST main 1 & main2)

“21110_TRIP” = tripping command from intertripping


system to CR 11 - 16 (RST main 1 & main2)

“23105_BFP TRIP” = tripping command from BFP to the


local CB (after t1) to CR 11 - 16 (RST main 1 & main2)
HMI500 Settings
Breaker Failure Protection
activate / deactivate BFP

timer 1
timer 2
setting
setting

© ABB Group
August 31, 2019 | Slide 11
HMI500 Settings
End-Fault Protection : Input Configuration
inputs

“11530_Q0 Isolator/Breaker position”


= CB position

“11505_Closed Command CB”


= CB (manual) closed command

© ABB Group
August 31, 2019 | Slide 12
HMI500 Settings
EFP Output Configuration : Feeder CT LINE SIDE

outputs

“24105_EFP REMOTE TRIP” = tripping command


from EFP to the remote CB to CR 6 - 7 (RST main 1
& main2)

© ABB Group
August 31, 2019 | Slide 13
HMI500 Settings
EFP Output configuration : Feeder CT BUS SIDE

outputs

“21110_TRIP” = tripping command from intertripping


system to CR 11 - 16 (RST main 1 & main2)

© ABB Group
August 31, 2019 | Slide 14
HMI500 Settings
End Fault Protection Settings

pick up
time

I> setting

activate / deactivate EFP


© ABB Group
August 31, 2019 | Slide 15
HMI500 Settings
Output Configuration : Tripping
latched

blocking !!!

event recording

at leading edge

send to BU & CU
© ABB Group
August 31, 2019 | Slide 16
HMI500 Settings
System Response
condition for “differential current alarm”:
•no blocking
•blocking of BBP
•selective blocking BBP (zone blocking)

isolator running time

remote tripping pulse length

condition for “isolator image alarm”:


•no blocking
•blocking of BBP & intertripping
•selective blocking BBP & intertripping (zone blocking)
© ABB Group
August 31, 2019 | Slide 17
HMI500 Settings
Input configuration : System

typical system input


signals

© ABB Group
August 31, 2019 | Slide 18
HMI500 Settings
Output configuration : System

IMPORTANT:
all possible alarms have to be
configured !!!

© ABB Group
August 31, 2019 | Slide 19
HMI500 Settings
Input configuration : System Input Commands

1 aux. contacts

OC input

no prolongation

event
recording

event send event send to the


to IBB 1 / 2 eventlist CU
© ABB Group
August 31, 2019 | Slide 20
HMI500 Settings
Output configuration : System Alarm

reset delay 0 ms

non blocking !!!

event recording

at leading and
lagging edge

send to CU
HMI500 Settings
Disturbance Recorder configuration : Settings
enable DR station #

sampling frequency

# of records

Pre-fault and Post-


fault time

memory behaviour
HMI500 Settings
Disturbance Recorder configuration : Signals

signals to be
recorded - must be
configured as in- or
outputs in the
binary modules !!!

“text” in the
disturbance record

trigger condition
HMI500 Settings
Event Recorder Memory settings

memory behaviour