CGS (City Gate Station)

It is entry gate for natural gas to enter in city.

City gas station is a location of custody transfer of gas from a


transmission company to a distribution company.

it’s a position where a company takes the tap-off from the


main pipeline of gas in order to distribute it among the
domestic, industrial and commercial consumers and
refuelling CNG vehicles.
CGS (City Gate Station)
 Functions of a city gas station
Filtration
Pressure Reduction
Custody Transfer metering
Odorization
Preheating of NG if required
 Components of a city gas station
 Inlet and outlet isolation valves
 Knock out drum ( KOD ), if required
 Filters
 Metering unit ( turbine, orifice, ultrasonic)
 Preheater, if required
 Pressure reduction skid comprising
 Active & monitor regulators
 Stream distribution arrangement
 Slam shut valve for over & under pressure protection
 Creep relief valve
 Odorization unit
 Isolation valve
• An isolation valve is a valve in a fluid handling system that stops the flow
of process media to a given location, usually for maintenance or safety
purposes. They can also be used to provide flow logic (selecting one flow
path versus another), and to connect external equipment to a system.
 Types of isolation valves used in industries
Ball valve
Butterfly valve
Globe valve
Gate valve
 Diaphragm valve
 Ball valve
Ball valves offer very good shut-off capabilities.
 A simple quarter-turn (90°) completely opens or closes the valve.
 This characteristic minimizes valve operation time and decreases the
likelihood of leakage due to wear from the gland seal.
 Pressure relief valve (PRV)
• A Pressure Relief Valve is a safety device designed to protect
a pressurized vessel or system during an overpressure event.
An overpressure event refers to any condition which would
cause pressure in a vessel or system to increase beyond the
specified design pressure or maximum allowable working
pressure (MAWP).
• The primary purpose of a pressure Relief Valve is protection
of life and property by venting fluid from an over pressurized
vessel.
 Slam shut-off valve (SSV)
• Slam shut-off valve is installed immediately after the filter
and prior to the Regulator.
• It normally remains open, in case the outlet pressure of the
regulator exceeds the permissible limits, the slam shut-off
valve senses it through the impulse line and immediately
shut-off the flow to downstream.
• When the regulator is repaired the slam shut-off valve is to
be opened manually by pulling the knob. Once the flow
starts through the slam shut-off valve it remains open till the
outlet pressure of the regulator is within limits.
 Creep relief valve (CRV)

• The creep valves are safety valves installed in gas lines downstream
of the PCV (pressure control valve). When the PCV is unable to
maintain the downstream pressure and it exceeds a set limit, the
creep safety valve relieves the excess pressure and maintains the line
pressure.
CGS
Pressure Regulating System with Check Metering Skid

Block diagram :

Odorization RTU
Unit (Remote Terminal Unit)

Pressure
Filtration To CNG &
Gas Inlet regulating Turbine meter
Unit Compressor
valve

To Steel pipe
into city
PI
GAS Inlet:- 01 PG
PI 01
01 TG
01
PT 3 Way

½” * 300 #
01 Manifold

BV BV
½” * 800 # ½”*800#
From Tap-off Ball Valve To Filtration
Point 4” * 300# unit Inlet
Filtration Unit : -
 To Remove foreign particles from natural gas Like dust, water, metal etc.

 Active stream is online at a time & Standby stream is for the redundancy purpose ,both are identical.

Active Stream

To
From Inlet
Odorization
Unit

Stand-by Stream
Filtration unit
Flame PVS DPG
arrestor 01 01
1”

Angle 5 way
1” * 500 # valve manifold
¼” *600 #

Knock out To
BV BV
From inlet Drum Odorization
4” * 300# 3” * 300 #
Cartridge filter unit
Flame
Pressure Regulating system Arrestor Natural gas line

1”
Feedback line

BV Pressure BV
3” * 300 # regulating valve 3” * 300 #
CRV
01

Drain Drain Angle


valve
To Metering
From skid
Odorization BV & GV
Unit 1” *800 #
PG 3 way
01 manifold
Standby stream
Flame 1”
Metering skid Arrestor
PT
BV & GV 03
1” * 800 #

Standby stream
3 way
manifold
RTU
FY TG ½” 800 #
02 03
TG ½” 300 # BV
PT
03 3” * 300 #
03 FT
02 TE OUTLET
02 BV & GV
3 way 1” * 800 #
manifold
Electrical line

BV Turbine Meter BV
3” * 300 # 4” * 300 # 5D 3” * 300 #
10D
Turbine flow meter
 Meter uses the mechanical energy of the fluid to rotate a “pinwheel” (rotor).
 Blades on the rotor are angled to transform energy from the flow into rotational energy.

 The rotor shaft spins on bearings. When the fluid moves faster, the rotor spins
proportionally faster.

 Blade movement is often detected magnetically, with each blade or embedded piece of
metal generating a pulse.

 When the fluid moves faster, more pulses are generated.

 Turbine flowmeter sensors are typically located external to the flowing stream to avoid
material of construction constraints that would result if wetted sensors were used.

 The transmitter processes the pulse signal to determine the flow of the fluid. Transmitters
and sensing systems are available to sense flow in both the forward and reverse flow
directions.
Plusses and Minuses
The cost is moderate.
 Very good at clean, low viscosity fluids of moderate velocity and a
steady rate.
Turndown is very good as it can read very low compared to the
maximum flow. They are reliable if put in a clean fluid especially if it
has some lubricity.
They do cause some pressure drop where that may be a factor such
as gravity flows. Not reliable for steam. Bearings wear out.
Turbine Flowmeters
High accuracy turbine flowmeters are available for custody transfer of hydrocarbons and
natural gas.
 the functionality of a flow computer to correct for pressure, temperature and fluid
properties in order to achieve the desired accuracy.
Be careful using turbine flowmeters on fluids that are non-lubricating because the
flowmeter can become inaccurate and fail if its bearings prematurely wear. Some turbine
flowmeters have grease fittings for use with non-lubricating fluids.
Turbine flowmeters that are designed for a specific purpose, such as for natural gas
service, can often operate over a limited range of temperature (such as up to 60ºC)
whereby operation at higher temperatures can damage the flowmeter.
Smaller turbine flowmeters can be installed directly in the piping, but the size and
weight of larger turbine flowmeters may require the installation of substantial concrete
foundations and supports
Applications for turbine flowmeters are found in the water, petroleum, and chemical
industries.
 Petroleum applications include the custody transfer of hydrocarbons. Miscellaneous
applications are found in the food and beverage, and chemical industries.
 Odorization unit
• The natural gas being odourless, it is recommended by PNGRB and as
per safe practices, the natural gas supplied to customers through, the
City Gas Distribution System should be odorized for facilitating the
early detection of gas, when it leaks, before it causes hazards like fire
/ explosion and asphyxiation.
• Adequate odour / smell is imparted to piped natural gas by
continuously dozing controlled quantity of odorant chemical, in the
flowing gas supply.
• Normally Ethyl Mercaptan chemical is used as odorant. The dozing
rate may vary from 150 ml to 250 ml per 10000 m3 of gas supply to
achieve the required smelling sulphur content to 10 to 12 ppm.
Odorants used are:  Properties of Ethyl
Mercaptan
Tetrahydrothiophene or  Flammable
THT  Heavier than Air
Tert-Butylthiol  Colourless
Ethanethiol (Ethyl  Very unpleasant odour
mercaptan)  Explosive Range : 2.8%
Spot leak to 18%
 Components of Odorization System
1. Bulk Odorant Tank
• It is used to store odorant chemical (ethyl mercaptan is used as
odorant).
2. Bulk Odorant Filter
• It is used to filter out any dust particles and impurities from odorant
chemical before injecting in pipeline.
3. Fill valve
• The purpose of fill valve is to control the odorant flow into the
verometer.
4. Verometer
• Verometer act as an injected odorant volume verification device. It
combines with expansion tank to prevent odorant from escaping in
the atmosphere.
5. Pump
• It is a pneumatically actuated, positive displacement, reciprocating
plunger pump. It increases the pressure of odorant slightly above the
line pressure and thus discharges the odorant into the pipeline.
6. Odorant discharge manifold
• It directs the flow of odorant during regular working, maintenance,
bypass etc.
7. Gas supply filter
• It is 25 micron coalescent filter. It conditions the actuation gas and
provides clean gas to solenoid valves.
8. Expansion tank
• It acts as a pressure source and buffer for verometer. As the verometer
filled or emptied, blanket gas flows into or out of the expansion tank.
Filtration unit
;PI PG
TG

FILTER
PG
02
PG
TG

TG
Odorisation PRS
skid metering
skid

Compressor

Compressor

Compressor

Compressor
r CONTROL
ROOM

CASCADE
STATIONARY
CASCADE
STATIONARY

CASCADE
STATIONARY

CASCADE
STATIONARY
r r r r

L L L L
Gail Terminal, Cr rC Cr Cr
TALEGAON V V V V
To
DBS
Flame ARRESTOR
PRS with Check Metering Skid
Flow-
Computer
Emreson
Flow Boss Junction Box
-107 SSV [Slam
Shut off Datasheet
valve] Flange rating: 300 #
Ball Valve
Cartridge/element : Wire Cloth
3” * 300 #
Design Pressure : 49 Bar
Design Temp. : -29 To 65 C
Operating Temp : 0 to 65 C
Filtration Efficiency : 98 %
To CNG & Drain for SSV Filter Cp & Cv : 1.27 | Type : vertical
Compressor Inlet Size : 4” | Outlet size : 3”
@ ~ 35 Bar INLET From
Item Tag : CF -01 & 02GAIL Tap off
Flow Rate: 18000 SCMH @ 39 Bar
Filter Pressure drop :Pressure
250 mbar
Filter Model : Fisher-D-100-C1.5
OUTLET FOR Steel Pipe line MakeBall
: Fisher
Valve
Ball Valve Ball Valve
2” * 300 # @ ~ 33 Bar 3” * 300 # 4” * 300 #
Slam Shut-off Valve

Datasheet
Item Tag : SSV - 01 & 02
INLET OUTLET Size : 3”
Flange rating : 300 #
Body material : Carbon Steel
Trim / Plug Material : Steel
Inlet Pressure (Min. / Max. ) : 44 / 46 Bar
outlet Pressure (Min. / Max. ) : 43.5 / 45.5 Bar
Flow Rate (Min. / Max):1500 / 18000 SCMH
Failure Position : Fail Close type
Pressure drop : 0.5 barg
Operating Temp(Max./ Design) :0 Deg to 65 Deg C
Limit Switches : Required , Each for opening and closing
Position indicator : Required
Valve model : JEQ 3”
Spring : OPSO spring range : 40 to 55 bar