Documente Academic
Documente Profesional
Documente Cultură
By
K.V.PRASAD,
SR.FACULTY
NTPC – PMI
For
On-off Control
Proportional Control
Proportional-Integral ( P-I ) Control
Proportional – Derivative ( P-D ) Control
Proportional-Integral-Derivative ( PID ) Control
Ratio Control
Spilt Range Control
Cascade Control
Feed-forward Control
Adaptive Control
Intelligent Controls
Feedback Controllers
m
yt me
as
ur
edv
a
lu
eo
ft
hec
on
tr
ol
le
dva
r
ia
bl
e
(
ore
qu
iv
al
ents
ig
na
lf
ro
mt
hes
en
so
r
/t
ran
s
mit
te
r)
Transfer Function
P'()
s
G
c s
() Kc
Es()
BITS Pilani, Deemed to be University under Section 3 of UGC Act, 1956
Proportional -Integral (PI)
Control
The actuating signal is related to the error by
t
1
p
(
t
)
pK
c
e
(
t
)
e
I0
(t
)d
t
Where, I is the integral time constant or the reset time.
Transfer Function
P
'
(s) 1
G
c(
s)
E
(
s )
c
K1
s
I
Transfer Function
G
(
cs
)
P
'
(
E
(
s
)
s)
K
c
1
1
1s
s
D
Decrease the gain to provide a smoother, slower, and more stable response.
Whereas insufficient gain slows down the initial approach, inadequate reset
action slows down the final approach to set point.
If the reset action is too large (reset time too small), there is excessive
overshoot.
Some simple rules of Tuning the Auto Control Loops
If there is excessive overshoot and oscillation, decrease the reset action
(increase reset time).
For level loops with low controller gains (< 5.0), reset action must be
greatly restricted (reset time increased to 50 or more minutes) to help
mitigate nearly sustained oscillations.
If the noise is greater than the measurement resolution limit, the loop sees it.
If it causes an output change greater than the final element or control valve
resolution limit, loop variability will be worse in auto than in manual,
particularly if there is any rate action.
Tuning the Auto Control Loops
Test new tuning settings by changing the set point in both directions.
Don’t leave these new settings over night until you are sure they are
right.
Before entering new settings, ask the operator for permission to tune
the loop.
Secondary Loop gets a set point from a primary (master or outer) loop.
The secondary loop response is normally faster than (about five times)
the primary loop response.
The secondary loop can correct for upsets it can measure before they
affect the primary loop.
18
25 November 2012 19
25 November 2012 20
Obsolescence
540°C, 255 Ksc
568°C, 47
Ksc 492°C, 260 Ksc
FUR ROOF
457°C, 49 Ksc
I/L HDR ECO HGR O/L
HDR
HRH LINE
MS LINE
411°C, 411°C,
277Ksc 275 Ksc
SEPARATOR
S
T FINAL SH
FINAL
O RH LTRH
R
A DIV PANELS SH PLATEN
SH
G
E
T
A VERTICAL WW
N
305°C, 49 Ksc
G K ECO
JUNCTION
HDR
LPT LPT IPT
C
O HPT
N ECONOMISER
D
E
N
S
E
R
ECO I/L
FEED WATER
By BWRP
290°C, 302 KSC
S.K.MATHU SUDHANA
Executive Trainee 05 FUR LOWER HDR
FRS
COMMISSIONING NTPC SIPAT
BOILER OPERATING PARAMETER
FD FAN 2 No’S ( AXIAL ) 11 kv / 1950 KW 228 mmwc
1732 T / Hr
947 T / Hr
MILL OPERATION 7 / 10
660MW & 500 MW PARAMETERS :
5000 MW AT BMCR
DESCRIPTION UNIT 660 MW AT BMCR
VERTICAL WW
SEPARATORS
F
W
R
STORAGE TANK
S
ECONOMISER
ECO I/L
HPH
FL
AS
H
W ZR
R T
AN
K
CONDE
NSER CEP LPH DA
FEED WATER PATH - LOAD < 30% Back
VERTICAL WW
SEPARATORS
S
T
O
R HPH
A
G
E
T
A ECONOMISER
N
K
ECO I/L
MIXING PIECE
CCP UG
FEED WATER PATH – LOAD > 30% Back
S S
E E
P P VERTICAL WW
A A
R R
A A HPH
T T
O O
R R
ECONOMISER
ECO I/L
TO BACKPASS
CONNECTING PIPES
SEPARATOR ACTUAL LEVEL
LEVEL SET POINT
FROM ULD
SEPARATOR LEVEL SETPOINT
SUB
10
LEVEL SETPOINT
8
6
PID Series1
4
2
0
0 100 200 300 400
ULD
TO BFPS
ULD 0 300
MIN. FW FLOW FW FLOW TO
SET POINT ECONOMISER
SUB
DP SET POINT
DP ACROSS CC ACROSS CC
PUMP PUMP
PID
SUB
PID
<
SUB
FG FG
PID >
FWPCV
MEASURED SEPERATOR LEVEL STORAGE TANK
OUTLET LINK SET POINT
LEVEL
SUB
F(X) F(X)
PID
WR ZR WARM UP VALVE
Wet Mode and Dry Mode of Operation
Wet Mode Operation
• Separator level control by BFPs and FW flow control by UG.Min FW
flow set point from boiler desk. Initial level set point is 9 Mtr. WR and
ZR will act as emergency control for separator level
• If water disappears in separator during wet mode then boiler will trip
on separator outlet level low low – 1.1 Mtr (3 Sec delay)
• Boiler will trip if separator outlet level goes high high in wet mode –
17.7 Mtr
• WR opens at 14.2 Mtr in auto
• ZR opens at 16.2 Mtr in auto
Feed Water Control In Dry Mode
• First controller acts on load dependant average DT
across PDSH. Its output represents the required
adjustment to maintain the steam conditions, flue gas
temperatures entering Platen SH so as to ensure
adequate spray platen range
• Second controller acts on load dependant separator
temperature set point corrected by first controller. The
output adjusts feed water in response to firing system
disturbances
• Minimum set point of 30% for safety is additionally
provided
SEPERATOR SEPERATOR
PLATEN SH DT OUT STM TEMP OUT STM PR
BMD BOILER MASTER
DEMAND DSH SEP SEP
PI
FF SIGNAL
∑
ANY SCANNER FLAME (AND)
0% BCP OFF
A
a 30 %
b
TOTAL FW FLOW
> T2 A
FB SIGNAL
FWF F(x)
PI
TO BFPs
DT SETPOINT IN FW LOOP BM(%) DT
30
25
0 0
DT SETPOINT
20
15 Series1
10
5
28.8 11
0
0 50 100
BOILER MASTER
43.3 28
52.1 22
Final Control Elements In FW
20
15 Series1
10 43.3 21
5
0
52.1 18
0 50 100
BOILER MASTER
70.7 7
100 7
DIV SH PLATEN SH FINAL SH
15% 3%
•RH O/L AVG temp and temp SP (568 DEG) with RHDSH DT
correction (Max 5 DEG) correction fed to PID, PID output with
airflow FF goes to 2 sets of tilt - one for wind box and other for
SOFA
RH Temperature Control By Spray
LTRH FINAL RH
DSH
296 451 451 560
0%
FUEL FLOW CONTROL
PA HDR PRESS CONTROL
PA HDR PRESS CONTROL
MILL-A AIR FLOW CONTROL
MILL –A AIR TEMP CONTROL
Control time scheduling of hp bypass
valve
Control time scheduling of lp bypass
valve
Calculation Of Spray Flow
Runbacks /Rundowns
• Two TDBFPs – 120%
• One TDBFP + One MDBFP – 95% (625 MW)
• One TDBFP – 65% (429 MW)
• One MDBFP – 30% (198 MW)
• Rundown if FW master is maximum and FW flow is < FW demand
• BFPS will go for pressure control when FW deviation is very high
• ID / FD / PA runback demand is 396 MW and turbine trip is 330 MW
Protections
• Feed water flow low low for 10 sec ( 300 T/Hr)
• Vertical wall tube metal temparature hi hi (4/48) (479 DEG)
• MS / RH STEAM temparature hi hi 560/580 DEG 20 sec
• All BFP off for 20 Sec
SLIDING PRESSURE OPERATION
PURGE CONDITIONS
No Boiler Trip Condition Exists
Heat the incoming feed water to the saturation point to reduce the
solubility of entrained gases.
The gases are basically O2, CO2 and NH3 - very corrosive at
elevated temperatures.
Set of trays that separates the water into thin sheets from which the
gases can easily escape.
The gases are vented out of the deaerator to the atmosphere.
To ensure mixing & elimination of corrosive gases, the FW level &
steam pressure controls are important.
DEAERATOR PRESS CONTROL
DEAERATOR LEVEL CONTROL
DEAERATOR LEVEL CONTROL
Dosing in Condensate & Feed Water
Low Flue gas temp. (below dew point) at AH cold end may
result in condensation of water vapour.