Harmonics - Basics

What Are Harmonics ?


●Sinusoidal Waveform.
●Frequency higher than power frequency.
●Generally harmonic Frequency will be Multiple of
Power Frequency.

Schneider Electric - Division - Name – Date 2


What Are Harmonics ?

Schneider Electric - Division - Name – Date 3


15
10
5
Fundamental 50Hz
0
-5
-10
-15

4 1 2 3 4 5
2
5th harmonic 250Hz
0

-2

-4

3
1 2 3 4 5 6 7
2
1 7th harmonic 350Hz
0
-1
-2
-3

Schneider Electric - Division - Name – Date 4


How wave-shape is distorted?
15
10
5
0
-5
-10
-15

3
2
1
0
-1
-2
-3

15

10

-5

-10

-15

Schneider Electric - Division - Name – Date 5


How wave-shape is distorted?
15
10
5
0
-5
-10
-15
4
15
2
10
0
5
-2
0
-4
-5
3
2 -10
1
-15
0
-1
-2
-3
1

0.5

-0.5

-1 - Name – Date
Schneider Electric - Division 6
Harmonic Source?
Sources of Harmonic?
●Loads.
●Voltage / Current Converters - Transformers.
●Alternators.

Schneider Electric - Division - Name – Date 8


Harmonic from Loads..
●Two types of Loads.
● Linear Loads.
● Non-Linear loads.

Schneider Electric - Division - Name – Date 9


What is Linear & Non-Linear?

Schneider Electric - Division - Name – Date 10


Linear Load!

Schneider Electric - Division - Name – Date 11


Non Linear Loads!

Schneider Electric - Division - Name – Date 12


Number of Pulses?
1 Pulse?

N
Single pulse

Schneider Electric - Division - Name – Date 14


1 Pulse?

N
Single pulse

Schneider Electric - Division - Name – Date 15


1 Pulse?

N
Two pulse

Schneider Electric - Division - Name – Date 16


Pulse?

Schneider Electric - Division - Name – Date 17


6 Pulse?

Schneider Electric - Division - Name – Date 18


12 Pulse?

30D

Schneider Electric - Division - Name – Date 19


Examples of Non-Linear loads..

3,5,7,9
2 Pulse

6 Pulse

6, 12 or
24 Pulse

5,7,11,13 etc
Schneider Electric - Division - Name – Date 20
Attributes of harmonic.
Harmonic Attributes..
●Magnitude – Amps or Volts.
●Frequency.
●Sequence.

Schneider Electric - Division - Name – Date 22


Sequence harmonic.
Sequence?

Schneider Electric - Division - Name – Date 25


Sequence?
R R

B Y B Y

Positive Sequence? Negative Sequence?

Schneider Electric - Division - Name – Date 27


Zero Sequence?

R
Y
B

Schneider Electric - Division - Name – Date 28


How to Determine the Phase
Sequence of Harmonics ?
Harmonic order 1 2 3 4 5 6 7 8 9

Phase Sequence + - 0 + - 0 + - 0

Positive Sequence Negative Sequence Zero Sequence


Fundamental 2nd Harmonic 3rd Harmonic
4th Harmonic 5th Harmonic 6th Harmonic
7th Harmonic 8th Harmonic 9th Harmonic
10th Harmonic 11th Harmonic 12th Harmonic
3n+1 3n+2 3n+3
Schneider Electric - Division - Name – Date 29
Adverse Effects of Harmonics
Behaviour of Zero sequence Harmonics
Zero sequence harmonic – Behaviour..
rd
Accumulation of 3 harmoni
Three phase system

Wa
fun
Time.

R - phase.

R-P
har
Time.

Y - phase.

Y-P
har
Time.

B - phase .

B-P
har
Time.

Addition of third harmonics in


Neutral conductor

Thi
pha
and
Time. can

Schneider Electric - Division - Name – Date 32


Skin Effect
● The high frequency current tends to concentrate on the periphery of
the conductor.
● Increases Resistance of the conductor.
● Increase losses in the conductors.
● Increase heating and eventually thermal failure.

Schneider Electric - Division - Name – Date 33


Skin Effect Contd..
Current in a Conductor with DC
Source

Current distributes equally through out the Cross section of


the conductor.

Schneider Electric - Division - Name – Date 34


Skin Effect Contd..
Current in a Conductor with AC 50Hz Source

AC

Current Tends to flow towards the conductor surface,


leaving the centre of the conductor.

Schneider Electric - Division - Name – Date 35


Skin Effect Contd..
Current in a Conductor with Harmonic 250Hz

AC

Current concentrates on conductor surface, leaving the


centre of the conductor. Hence increases resistance of the
conductor.

Schneider Electric - Division - Name – Date 36


Schneider Electric - Division - Name – Date 37
Schneider Electric - Division - Name – Date 38
Schneider Electric - Division - Name – Date 39
Effect on Rotating machines
● Negative sequence harmonics such as 5th harmonic will induce the
negative sequence torque or breaking torque on the motor or
Alternator.
● To over come the breaking effect the motor or Alternator demand
more power.

Schneider Electric - Division - Name – Date 40


Effect on Rotating machines Contd..
R

B Y
R

B Y

Schneider Electric - Division - Name – Date 41


Effect on Transformer/Reactors
Effects on Transformers

Schneider Electric - Division - Name – Date 43


Effects on Transformers Sound Loss

Heat loss due to


Skin effect

Heat loss due to


Iron Loss

Schneider Electric - Division - Name – Date 44


Noise
Un wanted sound within bandwidth of Human Ear (20 to 20kHz).

If the sound waves are more than 20kHz


– Ultra sonic

If the sound waves are less than 20Hz


– Infra sonic.

Schneider Electric - Division - Name – Date 45


Why Noise in Iron core reactor?

The Iron has the following properties:


- Allows magnetic fields to pass through it easily.
- When the magnetic field is applied, the Length of the
material will increase, Volume remains unaltered.
- When the magnetic field is removed, it will come to original
size.
- This is known as MAGNETO-STRICTION.
- The change in length will be about 1PPM or 0.0001%.

Schneider Electric - Division - Name – Date 46


Why Noise in Iron core reactor?

Expands twice in one cycle – i.e, Frequency is 2 x F.


For 50HZ system, the expansion frequency will be 100Hz. Hence the sound frequency.
If applied frequency is >10kHz, sound waves will have >20kHz frequency – this is
Ultrasonic waves.
Amount of Increase in length depends on Magnetic field strength.

Schneider Electric - Division - Name – Date 47


Why Noise in Iron core reactor?

The Lamination close to Magnet will have highest Flux – hence larger will be
the expansion.
The Lamination far away from magnet will have lowest Flux – hence smaller
will be the expansion.
Noise caused due to expansion & Friction

Schneider Electric - Division - Name – Date 48


Effects of Magnetostriction

Schneider Electric - Division - Name – Date 49


Effects..
- Loosens the core.
- Increases Heat within the core due to Friction.
- Excessive Magnetostriction will cause over heating of core, the
enamel will be liquefied.
- Harmonic distortion will have distorted Flux that causes high
frequency noise close to 1kHz.

Schneider Electric - Division - Name – Date 50


Effects on Transformers Contd..

Schneider Electric - Division - Name – Date 51


Electro magnetic forces contd..

Schneider Electric - Division - Name – Date 52


Resonance
What is Resonance ?

Burning material Capacitor

Fire Analogy Electrical Resonance

Schneider Electric - Division - Name – Date 54


Resonance
Inductance characteristics:
XL = 2 x ¶ x F x L.
Where,
- “2 x ¶” represents one cycle of AC.
- “F” represents number of such cycle per sec.
- “L” represents the inductance value in Henries.

XL
F

Schneider Electric - Division - Name – Date 55


Resonance Contd
Capacitor characteristics:
Xc = 1 / (2 x ¶ x F x L.)
Where,
- “2 x ¶” represents one cycle of AC.
- “F” represents number of such cycle per sec.
- “C” represents the Capacitance in Farad.

XL
F

Schneider Electric - Division - Name – Date 56


Resonance Contd

Xc XL

Resonance
Frequency

Schneider Electric - Division - Name – Date 57


Resonance Types

Series Resonance

Parallel Resonance

Schneider Electric - Division - Name – Date 58


Series Resonance

XL
X = -jXc+jXL
Xc

Xc XL

Schneider Electric - Division - Name – Date 59


Series Resonance Effects..

XL

X X = -jXc+jXL
Xc

Schneider Electric - Division - Name – Date 60


Parallel Resonance

X X ={-jXc x jXL}
[-jXc+jXL)

Schneider Electric - Division - Name – Date 61


Effect of Parallel Resonance…

ZT

VFD

Ih

Schneider Electric - Division - Name – Date 62


Effect of Series Resonance…

ZT ZT

M F

Ih

Schneider Electric - Division - Name – Date 63


Network Without Capacitors
Harmonic currents flow towards Grid.
GRID
Min. Import of Harmonics from Grid.
No Resonance at harmonic
frequencies.
BUS
Hence least Harmonic Problem.
Power Factor Very Low.
M

Schneider Electric - Division - Name – Date 64


Network With Capacitors
ZN
GRID

ZT
BUS

M
Non Linear

Equivalent Load
Impedance “ZL”
Load

Schneider Electric - Division - Name – Date 65


Harmonic import example..
Distorted voltage waveform from
GED supply, with 6 pulses in each
half cycle. Indicating the presence
of 12 pulse converters on the Grid.

Schneider Electric - Division - Name – Date 66


Harmonic import example..

33 kV Grid supply, with harmonics.

Grid supply, with


harmonics.

1600 kVA, 33 / 0.433 kV


Transformer at Zydus.
Xt – {Transformer
reactance}. Harmonic Current
amplified.

50 kVAr x 18 Capacitor.
Xc – Capacitive Reactance.

Schneider Electric - Division - Name – Date 67


Effect of Harmonics on - “Protective Relays”

Mal-operation Nuisance tripping

Trip level set lower than the fundamental Trip level set higher than the fundamental
value. The relay should trip as the value. The relay should not trip as the
fundamental value is higher than the trip fundamental value is lower than the trip
level. But the presence of harmonics has level. But the presence of harmonics has
reduced the peak value. Hence the increased the peak value. Hence the
Schneider Electric - Division - Name – Date
protective relay will not trip. protective relay will trip. 68
Harmonic Filters
Filter concepts

Schneider Electric - Division - Name – Date 70


Classification of Harmonic Filters
Harmonic
Filters

Passive Harmonic Active Harmonic Hybrid Harmonic


Filters Filters Filters

Broad band Detuned Tuned 3Ф


Filters Filters Filters 3wire


7% 4wire

14 % Single
Phase
Schneider Electric - Division - Name – Date 71
What is Passive Harmonic Filter

L L

Schneider Electric - Division - Name – Date 72


Types of Passive Harmonic Filters
Passive Filters

Shunt with Load Series With load

L
Load

Load

Shunt Filters
Line or Broadband Filters
Schneider Electric - Division - Name – Date 73
Shunt Filters

Tuned De-Tuned

L L
Load Load

Schneider Electric - Division - Name – Date 74


Tuned Filters

Schneider Electric - Division - Name – Date 75


Tuned Filters

Schneider Electric - Division - Name – Date 76


Tuned Filters

L L

5 7

Schneider Electric - Division - Name – Date 77


De-Tuned Filters

5 7

Schneider Electric - Division - Name – Date 78


Definitions of Tuned & De-tuned filters

If the Tuning frequency of a Filter is less than 90% of the


harmonic order: De-tuned filters.
For Ex:
a) 5th harmonic frequency is 250Hz.
De-tuned filter tuning frequency will be < 90% of 250Hz. i.e.
<225Hz.

b) 3rd harmonic frequency is 150Hz.


De-tuned filter tuning frequency will be < 90% of 150Hz. i.e.
<135Hz.

Schneider Electric - Division - Name – Date 79


Definitions of Tuned & De-tuned filters Contd..

If the Tuning frequency of a Filter is > 90% of the harmonic order:


Tuned filters.
For Ex:
a) 5th harmonic frequency is 250Hz.
Tuned filter tuning frequency will be > 90% of 250Hz. i.e.
>225Hz.

b) 3rd harmonic frequency is 150Hz.


Tuned filter tuning frequency will be >90% of 150Hz. i.e.
>135Hz.

Schneider Electric - Division - Name – Date 80


Series Filters

Line Choke De-Tuned

Load Load

Schneider Electric - Division - Name – Date 81


Active filter
Sinusoidal
Load Current with Supply
Harmonics Supply
Current
System

Compensating
Current

Active
Filter

+ =

(Time Domain)

+ =

(Frequency Domain)

Schneider Electric - Division - Name – Date 82


Active Compensation - Offerings

Sine Wave Accusine

Schneider Electric - Division - Name – Date 83


Active Compensation - Benefits
• Filtering upto the 50th HARMONIC including Inter-
Harmonics.
• Unsymmetrical Compensation of Reactive Power
• Real time response < 2 msec
• Independent of network characteristics, voltage &
frequency behavior
• INFINITE CONTROL
• Compatibility with conventional compensation
installations

Schneider Electric - Division - Name – Date 86


Sample Waveforms of current with & without out Active filter

Waveform of current
without Active filter

Waveform of current
with Active filter

Schneider Electric - Division - Name – Date 87


Harmonic Spectrum with & without active filter

Current Spectrum 5th Harmonic Current about 20 Amps.

without Active filter

5th Harmonic Current about 2 Amps.


Current Spectrum
with Active filter

Schneider Electric - Division - Name – Date 88


Cost-Technology Pyramid of Harmonic Filters

Top end solution for


wide spectrum of current
Suitable for Active harmonics & suitable for
installations having filters installations having
high harmonic sensitive equipment
distortion (cement,
sugar & steel plants, Hybrid Filters
etc.)

Tuned Filters

14% Detuned Filters


Suitable for installations having 3rd harmonics
and above (IT parks, corporate banks &
establishments)

7% Detuned Filters
Most common, Base end product suitable for
majority of industries having 5th and above
harmonics
Schneider Electric - Division - Name – Date 89
Application Guide
Eliminating Harmonic Problems

The De-tuned Harmonic Filter

PFC controller

VFD
M ~
~
loads generating
harmonics
~
automatic capacitor bank

Schneider Electric - Division - Name – Date 91


Eliminating Harmonic Problems

The De-tuned Harmonic Filter

PFC controller

VFD
M ~
~
loads generating
harmonics
~
automatic capacitor bank

Schneider Electric - Division - Name – Date 92


Eliminating Harmonic Problems

The De-tuned Harmonic Filter

PFC controller

VFD
M ~
~
loads generating
harmonics
~
automatic capacitor bank
Schneider Electric - Division - Name – Date 93
Eliminating Harmonic Import
The De-tuned Harmonic Filter

PFC controller

M ~
~
~
automatic capacitor bank

Schneider Electric - Division - Name – Date 94


Eliminating Harmonic Problems

The De-tuned Harmonic Filter

PFC controller

M ~
~
~
automatic capacitor bank

Schneider Electric - Division - Name – Date 95


Eliminating Harmonic Problems

Tuned Harmonic Filter (Passive)

MV/LV transformer

5th 7th 11th/13th

M ~
~ 242Hz 336Hz 530Hz
~
loads
generating harmonics tuned filter bank
(e.g. 6-pulse converter)

Schneider Electric - Division - Name – Date 96


IEEE 519 – Key points
Limits are specified for:
- Total Harmonic Voltage Distortion.
- Total Current Distortion.
- Individual Current distortion.

Limits specified at Point of Common Coupling.

The current harmonic limit is directly linked to the


system capacity (MVAsc)

Schneider Electric - Division - Name – Date 97


IEEE 519 – Key points
Point of common Coupling:

PCC: where Linear loads meets


Non linear loads

VFD
M ~
~
loads generating
harmonics
~
automatic capacitor bank

Schneider Electric - Division - Name – Date 98


IEEE 519 – Current harmonic Limits
Maximum Harmonic Current Distortion in percent of IL
Individual harmonic order (Odd Harmonics)
Isc/IL h<11 11<h<17 17<h<23 23<h<35 35<h TDD
<20* 4.0 2.0 1.5 0.6 0.3 5.0
20<50 7.0 3.5 2.5 1.0 0.5 8.0
50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<100 12.0 5.5 5.0 2.0 1.0 15.0
0
>1000 15.0 7.0 6.0 2.5 1.4 20.0
Even harmonics are limited to 25% of the ODD harmonic limits above.

* All power generation equipment is limited to these values of current distortion, regardless of actual Isc/IL.

Where,
Isc = Maximum Short-circuit current at PCC.
IL = Maximum demand load current (Fundamental frequency component) at
PCC.

Schneider Electric - Division - Name – Date 99


IEEE 519 – Voltage harmonic Limits

Bus voltage at PCC Individual voltage Total Voltage


Distortion (%) Distortion (THJDV%)

69kV and below 3.0 5.0

69.001kV through 1.5 2.5


161kV
131.001 kV and 1.0 1.5
above

Schneider Electric - Division - Name – Date 100