Sunteți pe pagina 1din 38

1

Supervisor : Dr. Abdur Rashid

HOD
Dept. Of Electrical Engineering COMSATS
Institute of Information Technology,
Abbottabad, Pakistan.

By : Muhammad Tanveer ahmad


Fa12-R09-012

2
Presentation layout
Research Methodology
Work Flow Diagram
Problem Statement
Literature Review
Simulation Tool
MHO Relay model
Results
References
3
Research Methodology
Stage 1
• Literature survey on MHO relay modeling and distance relays.
Stage 2
• Analyzing Transmission line Model and MHO characteristics
Stage 3
• Learning Simulation Tool (PSCAD).
Stage 4
• Modeling Transmission line and Mho relay characteristic in PSCAD.
Stage 5
• Mho characteristic Analysis in PSCAD.
Stage 6
• Getting Results.

4
Work Flow Diagram
Analyzing MHO
Learning
Literature Survey relay
Simulation tool
characteristic

Modeling MHO Analyzing


Modeling simple
relay Faultless Line
Transmission line
characteristics results

Applying Fault on
Analyzing Faulty
Transient model Get Results
line in PSCAD
of T-line
5
Problem Statement
The thesis studies the modeling of MHO relay for power
system protection. The aim is to Model the MHO
characteristics and simulate the transmission systems using
PSCAD/EMTDC simulation software. MHO relay is modeled
to identify between fault zones location and study the
effect of resistance on the behavior of modeled MHO
characteristics. Test network used is shown in figure below.

6
Literature
Referenc Considered Model Analysis Done Transmission Simulation Solution
e of line line Length tool Technique
2009 [1] mathematical Distance relays Long EMTP mathematical
model modeling model

2010 [2] 3 Phase Time-domain Long MATLAB Differential


model environment Equations
2000 [3] 3 Phase Dynamic state Long N/A Modified
space model Fourier
Transform
Method
2006 [4] 3 Phase Steady State Long EMTP State space
Model model
2012 [15] 3 Phase Microprocessor Long MATLAB/EMTP Programming
based

2015 Three Phase Multi MHO relay Long PSCAD/EMTDC Frequency


conductor modeling Dependent
Bundling (Phase) Model
7
Software and Techniques used before

In analyzing the problems in long transmission


systems and Relay Modeling

EMTP (Electromagnetic transient program)


MATLAB
PWS (Power World Simulator)

8
Simulation Tool

The transmission line and MHO relay


characteristics model is studied and
implemented in PSCAD.
 PSCAD is user-friendly.
Provide graphical user interface.
Provides powerful means of visualizing the
transient behavior of the systems.
 PSCAD/EMTDC provides a fast and accurate
solution.
9
Transmission line Models

Transmission
line

Steady State Transient


model model

10
MHO relay working principal
The impedance of Transmission Lines is proportional to its
length. A relay capable of measuring the impedance up to a
given point can be used to protect a Transmission Line and is
described as Distance Relay. This is designed to operate only for
faults occurring between the relay location and selected point.
The Relay compares the current flowing and the Voltage at
Relay point. In case of fault on Transmission Line, the current
flowing to fault point increases and the voltage at relay point
decreases. The relay sees this as fall in impedance and if this is
below pre-fixed setting, the relay Operates.

Distance relay measures the apparent impedance from relay


point until fault point and send the trip signal when computed
impedance is less than set impedance [3]. 11
MHO relay impedance trajectory

12
Zones settings

13
Calculating the zones impedance settings
 Impedance of 300km line

Z of transmission line of 300km = 300 (0.12413 + j0.665 )


= 67.4375<76.33o Ohm

 Zone setting for Mho relay at relay CB1

Zone 1 reach setting = 80% of transmission line A


= 0.8 x (67.4375<76.33o)
= 53.95<76.33o

Set radius of the mho circle = 53.95/2


= 26.975 Ohm

14
 Zone 2 sets to back up Mho relay at relay CB1
Zone 2 reach setting = 100% of line A + 50% next line (line B)

=[1x(67.4375<76.33o)]+[0.5x(67.4375<76.33o) ]
= 101.16<76.33o
Set radius of the circle = 101.16/2 = 50.58 Ohm
 Zone 3 sets to back up mho relay at relay CB1

Zone 3 reach setting = 100% of line A + 120% next line (line B)


= [1 x (67.4375<76.33o) ] + [1.2 x (67.4375<76.33o) ]
= 151.75<76.33o
Set radius of the circle = 151.75/2 = 75.872 Ohm

15
MHO characteristics

16
Conductor data and Sag
10m

Fig. 1 transmission line conductor data


 Conductor Configurations
– 3 Conductors used
– Bundled Conductors
– Conductors Spacing is shown in the figure 1.
 Sag: Vertical Distance between the highest and lowest point of the curve.
 Sag Calculations:
 10m for conductors
 10m for Ground Wires
17
Conductor data Calculations

 For Three-Conductors bundle equation is


3
𝐷𝐵𝐸 = 𝑟𝑥 . (𝐷𝐵 )2

 For Four-conductors
4
𝐷𝐵𝐸 = 𝑟𝑥 . (𝐷𝐵 )2 . 𝐷𝐵 2
 Conductor Configurations with equal spacing:
𝐷𝐵𝐸
– 𝐿𝑎 = 2 × 10−7 (H/m)
𝐷𝑠
– Where 𝐷𝐵 is Geometric mean distance.
– 𝐷𝑠 is Geometric mean radius.
– 𝑟𝑥 is radius of conductor
18
Simulation Data
Transmission line Data
• Frequency Dependent (Phase) Model.
• Three Conductors with Two Ground.
• 300km Long Line.
• 500kV 50 Hz used.

Faults Applied.
• Single Line to ground fault
• 60km, 20km and 12 km from the location of bus-A, bus-B and bus-C.
• 60 Km from bus-A with fault resistance of 10 Ω and 20

19
Single Phase to Ground Fault
 Calculations for single line-to-ground
fault
 The Voltages and currents at the
point of fault are
 𝑉𝑎 = 𝑍𝑓 𝐼𝑎 ,
 𝐼𝑏 = 0
 𝐼𝑐 = 0
 Symmetrical components of current.
𝐼𝑎0 1 1 1 𝐼𝑎= 𝐼𝑓
1
 𝐼𝑎+ = 1 𝛼 𝛼 2 𝐼𝑏 = 0
3
𝐼𝑎− 1 𝛼 2 𝛼 𝐼𝑐 = 0
𝐼𝑓
 𝐼𝑎0 = 𝐼𝑎+ =𝐼𝑎− =
3
3𝐸𝑎
 𝐼𝑎 = 3𝐼𝑎0 =
𝑍0 +𝑍1 +𝑍2 +3𝑍𝑓

20
Single Phase to Ground Fault sequence network

Calculations for single


line-to-ground fault
𝐼𝑓
 𝐼𝑎0 = 𝐼𝑎+ =𝐼𝑎− =
3
𝐼𝑎 = 3𝐼𝑎0 =
3𝐸𝑎
=
𝑍0 +𝑍1 +𝑍2 +3𝑍𝑓

21
Simulation Results

22
To study the behavior of MHO relay

 To study the behavior of the developed mho relay


characteristics, fault at different locations on the
500kV, 300km transmission line and fault resistances
of different values were simulated using
PSCAD/EMTDC software. The behavior of the mho
relay is as explained here in after.

23
Case 1: L-G faults at different distances from the
relay location.

Single line to ground fault were set on the


500kV, 300 km transmission line model at a
distance of 60km, 20km and 12 km from the
location of bus-A, bus-B and bus-C

60km

24
Zone-1 fault location (at 60 km from bus A)

60km

25
Zone-2 fault location (at 20 km from bus B)

20km from bus B


26
Zone-3 fault location (at 12 km from bus C)

12km from bus C


27
Single line to ground fault with fault resistance

 Line to ground fault


with no fault
resistance

 i.e. Rf = 0

 Line to ground fault with


fault resistance

 i.e. Rf = fault resistance

28
Case 2: Single line to ground fault with fault resistance

 Single line to ground fault with different fault


resistance were applied on the transmission line at a
location of 60 Km from bus-A. Simulation results are
shown in following slides, when the fault resistance
is 10 Ω the relay detects the fault in zone 2 instead of
zone1

10 Ohm
60km

29
Zone-1 with fault resistance 10 Ω

10 Ohm
60km
30
Zone-2 with fault resistance 20 Ω
Now if fault resistance is increased from 10 Ω to 20 Ω then zone of fault again
changes from zone 2 to zone3

60km 20 Ohm 31
Conclusions

 In this thesis mho relay characteristics are developed using


PSCAD. The performance characteristics of mho relay was
evaluated at different locations with single line to ground
fault. Main conclusion of this work is as follows.
 The developed mho characteristics may be used for training
young and inexperienced engineers and technicians.
 Different case studies have been presented in order to
illustrate the response of the developed mho characteristics
at different locations, with and without fault resistances.
Resistive fault causes the relay to under-reach.

32
Future Work

 For future enhancement, the model can be extended for


other Protection Schemes.
 Presented Model can also be applied in other distance relays
characteristic and fault types. This model can be base for
complex system protection designing.
 The students are able to change simulation parameters such
Load and fault data.
 And observe their effects on the fault impedance locus.

33
Reference
 [1] Abdlmnam A. Abdlrahem, “Modeling of distance relays for Power
Systems Protection”,M.Sc. dissertation, EE&E Dept., Faculty of
Engineering, Al-Fatah University, Fall 2009.

 [2] Hamid Sherwali and Abdlrahem, Matlab - Modelling, Programming and


Simulations, InTech publishers, October 2010.

 [3] Z. Peng, M. S. Li, C. Y. Wu, T. C. Cheng, and T. S. Ning, “A dynamic State


Space Model of a Mho Distance Relay,” IEEE Transactions on Power
Apparatus and Systems, Vol. PAS-104, No. 12, December 2000.

 [4] R. E. Wilson, J. M. Nordstrom, “EMTP Transient Modeling of a Distance


Relay and a Comparison with EMTP Laboratory Testing,” IEEE Transactions
on Power Delivery, Vol. 8, No. 3, July 2006.

34
 [6] H. Dommel, “EMTP Reference Manual,” Bonneville Power
Administration 1986.

 [7] H. W. Dommel, “Digital Computer Solution of Electromagnetic


Transient in Single- and Multiphase Networks,” IEEE Transactions on Power
Apparatus and Systems, Vol. PAS- 88, No. 4, April 1998.

 [8] Introduction to PSCAD/EMTDC V3, Manitoba HVDC Research Centre


Inc., Canada, 2010.

 [9] Craig Muller, P. Eng. “Power system computer aided design user‟s
guide”, Manitoba HVDC Research Centre, September 2011.

 [17] A Phadke and J G Thorp, Computer Relaying for Power Systems, John
Wiley & Sons Inc, 1990, ISBN 0 471 92063 0.
35
 [13] Bin Wang, Xinzhou Dong, Zhiqian Bo. “A method of protective relaying
for single-phase to ground fault against the effect of distribution
capacitance current” China Patent, Application No.200610144275.8, Dec.
1, 2006.

 [14] Y.G.Paithankar “Transmission Network and Protection Theory and


Practice” (Text book), Publised by MARCEL DEKKAR INC, 1998.

 [15] Anamika Yadav, A.S. Thoke, “Transmission line fault distance and
direction estimation using artificial neural network , ”, International
Journal of Engineering, Science and Technology Vol. 3, No. 8, pp. 110-121 ,
2012.

 [16] Hadi Saadat, “Power system analysis”, 3rd Edition, PSA Publishing,
ISBN 0984543805, 9780984543809

36
 [17] A.A Abdlrahem and H.H Sherwali, “„Modeling Of Numerical
Distance Relays Using Matlab”, IEEE Symposium on Industrial
Electronics and Applications ISIEA, October 2009.

 [18] Abdlmnam A. Abdlrahem, Hamid H Sherwali, “Modelling of


Numerical Distance Relays Using Matlab”, IEEE Symposium on
Industrial Electronics and Applications, Kuala Lumpur, Malaysia,
October 4-6, 2009.

 [19] Harikrishna M, “ Performance of quadrilateral relay on EHV


transmission line Protection during various faults,”ACEEE
International journal on Control System and Instrumentation, Vol.1,
No.1, July 2010

 [20] P.M.Anderson. Power System Protection. IEEE Press power


engineering series, USA, 1998

37
Thanks
38