Product Description-BBU3900-Baseband Processing Module
BBU3900
Equipment Name
Power -48 V
Input
distribution
Installation 19-inch standard rack; mounted on the wall
Installation mode
scenario
2
Product Description-RRU-RRU of Distributed BTS
Power
Integrated Equipment Parameters Installation Scenario
distribution
Equipment Dimensions Reference Picture
Name (width x Weight
Power consumption (W) Input Installation mode
height x (kg)
depth)
Typical power consumption: 190
W (20 W/3 carriers)
RRU3804
Maximum power consumption:
275 W (20 W/3 carriers)
Take 900 MHz and TOC = 30 W
for example Pole, wall-mounted,
Typical power consumption: 150 angle steel, channel
RRU3004 380 mm x
17 kg- W (TRx = 2) steel or close to an
485 mm x
23 kg Maximum power consumption: antenna (the DC RRU
170 mm
220 W (TRx = 2) also supports
centralized installation)
Take 900 MHz and class2 for
-48 V DC
example
Typical power consumption: 265
RRU3008
W (TRx = 8)
Maximum power consumption:
315 W (TRx = 8)
Pole, wall-mounted,
Typical power consumption: 190 angle steel, channel
380 mm x W (20 W/2 carriers) steel or close to an
RRU3801C 485 mm x 20 kg
Maximum power consumption: antenna (the DC RRU
170 mm
240 W (20 W/2 carriers) also supports
centralized installation)
3
Product Description-RTN910
4
Product Description-RTN950
Installation space
2U (IDU)
required
Specification of
adaptive air circuit 20 A for one (no backup mode) and 20 A for two (power backup mode)
breaker
Number of directions
1-6
supported
5
Product Description-DCDU-03B
Parameter Index
- 48 V DC input and nine-48 V DC outputs, which power the BBU and DC RRU. To be used with the
Function DBS3900. Core diameter of the DC power cable from the DCDU to customers: 16 mm^2 (-48 V blue,
GND black)
Power distribution 6x20 A + 3x12 A; 6 20-A air circuit breakers are used to power the RRU; one 12 A air circuit breaker
specification® powers the BBU and the other two are reserved.
Outline dimensions (height x
43.6 mm (height, 1U) x 442 mm (width, 19 inches) x 200 mm (depth)
width x depth)
6
Product Description-TMC11H-Transmission Cabinet
7
Part Description-APM30 (AC, Auxiliary DBS)
Parameter Index
Provide 220VAC/-48VDC conversion and provide DC power distribution for the BBU, DC
RRU, and transmission equipment.
Use
Provide standard 19-inch installation space for the BBU, transmission equipment, and
DDF.
Weight <= 91 kg (excluding user equipment)
Outline
dimensions of 900 mm (height) x 600 mm (width) x 480 mm (depth), (with a base)
cabinet (width
x height x 700 mm (height) x 600 mm (width) x 480 mm (depth), (without any base)
depth)
Surge
Differential mode (8/20 us): 10 kA; common mode (8/20us): 15 kA; the corresponding load
protection
of the DC output coming out of the cabinet is secondary load.
class
Primary power-off:
Auxiliary distributed BTS: RRU: 6 x 20 A air circuit breakers
Secondary power-off:
Power
distribution TMC: 1 x 25 A fuse, 4 x 15 A fuse (one for the BBU and fan respectively), 4 x 5 A fuse,
specification (six 15 A fuses and two 5 A fuses are configured inside the cabinet. They can be replaced
on site.)
Battery:
1 x 100 A air circuit breaker
Specification
of input air
Three-phase: 20 A 2.5mm^2–black jacket (core wire: yellow, green, red, and blue); single-
circuit
phase: 32 A 6mm^2 black jacket (core wire: blue, brown, and yellow/green);
breaker/power
cable
Embedded
7U 19-inch standard installation space (the northern-type heater occupies 1 U)
user space
Installation
Installed directly on the floor; pole installation; mounted on the wall
mode
8
Product Description-ETP48200
9
Product Description-TPS48300/A
10
Monitor system---EPAC
Function An EPAC-2UB collects and uploads environment alarms for An EPAC-2UB can either upload
sites and also drives two 1phase air conditioners below 3 digital signals through Huawei
hps and two heat exchangers or fan sets below 16 A main equipment or output alarm
signals through dry contact.
Weight 4.2 kg
Environment parameter The host is delivered with various sensors, such as indoor AC power outage alarm, navigate
temperature and humidity sensor, outdoor temperature light alarm (optional)
sensor, water sensor, door sensor, and infrared sensor.
Alarm input port 6 channels of analog signals are input to the passage, 20 Two channels of analog signals
channels of digital signals are input. are connected to the temperature
and humidity sensor.
Upload interface RS232/RS422
Function An EMUA collects and uploads environment alarms for the site. An EMUA can upgrade alarm signals
only through Huawei main equipment.
Weight 3.5 kg
Environment parameter Smoke sensor, door sensor, water sensor, temperature and Sensor selection
humidity sensor
Alarm input port 32 output branches
Fan of APM30
OVP(E1/FE)
EPS(AC/DC)
BBU
IDU910-link 1
IDU910-link 2
IDU910-link 3
SPACE
SPACE
Battery Power Cable layout
16
FAN/TEC Power Cable layout
IBBS 1 IBBS 2 RECTIFIER
FAN/TEC RTN1 FAN/TEC RTN1 F2
6mm2 cable
17
Power distribute for Cell site(G22) RTN950<=2
18
Power distribute for Cell site(G222+U333)
19
Set some parameter in rectifier for cell site
20
Signal Cable layout
IBBS 1 IBBS 2 PMU CMUA BBU
Com_in Com_in Com_in Com_in Mon_1
Com_485
21
Metro Site
System layout
Equipment layout
Password: 0#
27
Signal Cable layout
Alarm distribute for Hub site
Dowen line
Hub Site
System layout
Minishelter
insider
Equipment layout
Equipment layout
Equipment layout
Power Cable layout
DC Power distribute for Hub site(G222+D222+U333)
LOAD8 20A MCB Head Lamp
Load Low Voltage
LOAD7 100A MCB
Disconnection
LOAD6 100A MCB DCDU-1
LOAD5 32A MCB DCDU-2
ETP48200 LOAD4 32A MCB BBU
Battery Low
LOAD3 32A MCB HEX
Voltage
LOAD2 16A MCB RTN950
Disconnection
LOAD1 16A MCB TEC
LOAD0 16A MCB EMUA
LOAD8 12A MCB RRU1
LOAD7 12A MCB RRU2
LOAD6 12A MCB RRU3
LOAD5 20A MCB RRU4
DCDU03B(1) LOAD4 20A MCB RRU5
LOAD3 20A MCB RRU6
LOAD2 20A MCB RRU7
LOAD1 20A MCB RRU8
LOAD0 20A MCB RRU9
LOAD8 12A MCB RTN910(1)
LOAD7 12A MCB RTN910(2)
LOAD6 12A MCB RTN910(3)
LOAD5 20A MCB RTN910(4)
DCDU03B(2) LOAD4 20A MCB RTN910(5)
LOAD3 20A MCB RTN910(6)
LOAD2 20A MCB RTN910(7)
LOAD1 20A MCB
LOAD0 20A MCB AWL
39
Set some parameter in rectifier for HUB site
Password: 00200#
40
Signal Cable layout
Alarm distribute for Hub site
42
Alarm check/test on site
ALM1 AC Power-off alarm Shut down AC input MCB Short the ALM dray
and power the system contact with a
with battery. nipper.
ALM2 DC input overvoltage and / Short the ALM dray
undervoltage contact with a
nipper.
ALM3 Power supply system fault Block the rectifier fan Short the ALM dray
alarm to simulate a fan contact with a
alarm. nipper.
ALM4 Surger protector failure Pull out a SPD module to Short the ALM dray
alarm simulate a SPD alarm. contact with a
nipper.
ALM5 Fuse disconnection alarm Shut down DC output MCB Short the ALM dray
with load. contact with a
nipper.
ALM6 Battery protection Shut down battery MCB Short the ALM dray
with battery contact with a
nipper.
43
Setting the switches in EMUA
off
on
on
on
SW_ADDR出厂默认拨码设置