220kV and 400kV Isolator

1. Different types
2. Main parts of isolator
3. Functions of different parts
4. Maintenance
5. Diagnostic Testing
2
Types of isolator

1. Centre Break type ( one break


point)
2. Two breaks at two ends
# These two – horizontal rotating
3. Pantograph type isolator(400kV)
# This moves vertically up and down
3
Main Contacts

Vertical Support Insulato

Vertical Support Structu

4
Operating
Mechanism Box
5
6
Y R
B

Operating Mechanism Box


7
High Level Main Bus

8
9
Vertical
Insulator

Main contact

10
11
12
13
14
Main Parts of isolator -

A.Support structure.
B. Insulator columns.
C.Operating Mechanism Box.
D.Main arms & contacts
E. Earth Blade(switch)

15
Support Structure -

A. Galvanized Iron or Cement concrete.


B. Insulator column & isolator operating
mechanism box- erected on it.

16
Insulator column

A. Provides ground clearance


B. Rotating.

Pg 31 17
Operating mechanism box

A. To operate ( Close/Open) isolator


B. AC 3 phase 440V, motor to drive
the mechanism
C. One common box ( 220kV)
D. Three boxes ( 1 for each phase)
E. One master two followers
18
Operating mechanism box

F. Limit switches to limit


operation
G. Auxiliary switches ( Set of
NO & NC contacts)
H. Control supply 220V DC

19
Limit Switch -

20
Limit Switch

21
Auxiliary Switch

22
Close/ Open operation

A. Remote from Control room


B. Local Electrically –
Gang/Individually
C. Local Manually – using
handle / individually

23
Main Contacts -

A. Made up of Copper alloy coated


with silver coating.
B. Carry full load current
C. Most important part of isolator.

Pg 31 24
Maintenance -

A. Quarterly
B. Annual

Pg 34 25
Quarterly -

A. Tightening of nut/bolts of
clamps/connectors.
- To avoid hot spots.
B. Cleaning of surface of porcelain
insulators
C. Check main contact surface
D. Tightening of electrical connections.
Pg 34 26
Annual Maintenance -

A. Check main contacts


B. Tightening of nuts/bolts of all clamps
C. Vermin proofing of mechanism box
D. Check smooth operation of isolator
E. Check auxiliary switches

Pg 34 27
Annual Diagnostic Testing
A. Static Contact Resistance – 75
micro Ohms
B. Check Hot spot – Thermo vision
camera – to record temperature
C. Hot spot – Measurement done
when isolator is in service.

28
Annual Diagnostic Testing

D. Insulation Resistance –
a) HV to Earth(Mega Ohms)

29
Thank You!