Deputy executive Engineer
400KV GCR KORADI
1
220kV and 400kV Isolator
1. Different types
2. Main parts of isolator
3. Functions of different parts
4. Maintenance
5. Diagnostic Testing
2
Types of isolator
4
Operating
Mechanism Box
5
6
Y R
B
8
9
Vertical
Insulator
Main contact
10
11
12
13
14
Main Parts of isolator -
A.Support structure.
B. Insulator columns.
C.Operating Mechanism Box.
D.Main arms & contacts
E. Earth Blade(switch)
15
Support Structure -
16
Insulator column
Pg 31 17
Operating mechanism box
19
Limit Switch -
20
Limit Switch
21
Auxiliary Switch
22
Close/ Open operation
23
Main Contacts -
Pg 31 24
Maintenance -
A. Quarterly
B. Annual
Pg 34 25
Quarterly -
A. Tightening of nut/bolts of
clamps/connectors.
- To avoid hot spots.
B. Cleaning of surface of porcelain
insulators
C. Check main contact surface
D. Tightening of electrical connections.
Pg 34 26
Annual Maintenance -
Pg 34 27
Annual Diagnostic Testing
A. Static Contact Resistance – 75
micro Ohms
B. Check Hot spot – Thermo vision
camera – to record temperature
C. Hot spot – Measurement done
when isolator is in service.
28
Annual Diagnostic Testing
D. Insulation Resistance –
a) HV to Earth(Mega Ohms)
29
Thank You!
Pg 35 30