Documente Academic
Documente Profesional
Documente Cultură
Requirements for
Power Distribution
NDPL Case
Studies
North Delhi Power Limited
Flow of Presentation
After
GSAS in
Grid
Substati
ons
Transformation ( Distribution )
PRE- GSAS POST -GSAS
ØSustainability :
Sustainability of the
settings has ensured proper
sealing of RMU relays.
EXPLORATION
Improvement in System
Reliability
With IEDs used as relays, reliability of the Power System
improved due to various available functions.
•Faster relay operating time as low as 20 ms
•
•Effectiveness and Relay Co-ordination possibility on micro level by
utilizing multiple elements in the Relay. Almost all feeders
provided with High-set and IDMT Protection.
•
•As At feed end (DTL) only IDMT Protection is available best co-
ordination has been achieved by using DT-High set protection at our
end.
•
•Protection, Metering, Monitoring, Diagnosis and Control functions
can be performed from the one unit-IED
•
Improvement in System
Reliability
•All Protection relays cum BCU’s are well protected with Password.
Separate Passwords for operation and Protection facilitate safe
Protection settings and eliminated tampering of the relay settings.
•
•Ultimate Goal of the Automation is to operate the system in
Unmanned mode. Mimic diagrams and friendly relay functions of the
Relay helps breakdown team to visualize and understand the fault
and operation.
•
•Additional Trip Supervision relay and wiring has been reduced by
using status inputs of the Numerical Relay.
•
•Following Logics has been Configured in the relay for having
effective control and Protection of the system without conventional
hard wiring.
•
1.CBFP cum LBB Scheme.
2.Reverse Blocking Scheme for Bus bar Protection.
3. No requirement of the Annunciation fascia due to
availability of sufficient Configurable LED’s on relay itself.
Schemes / Logics
Implementation
•Important Projects/Logics includes:
•
•Reverse Blocking
•Local Breaker Backup
•Transformer Monitoring Unit
•CAP ON TAP
•Remote Relay Parameterization
•Multiple Relay setting groups
•Safety concerns tackled with
relaying
•Life assessment of Lightning
Arrestors
Reverse Blocking
•Reverse Blocking scheme is very useful for having co-
ordination in tripping between 11 KV OG Feeder and 11 KV
Incomer Breaker of the Bus.
•
•All outgoing feeders send a blocking command for 50 ms to
prevent tripping of the Incomer breaker during heavy faults
and even in cases of delayed tripping of outgoing feeder
breaker.
•
•Control wiring has been reduced by around 30% owing to
facility of control logic development in the relay.
•
•No requirement of interposing CT’s and VT’s in the system
for relay operation.
•
•Ratio Correction facility will serve the purpose.
Reverse Blocking
Reverse Blocking command is given by Outgoing feeders to
incomers/Bus-couplers to Block tripping of Incomers in case of
fault in 11 KV Outgoing feeder.
I>>> start
ers of Section
I>> start - 1
BLOCK HIGH SET I/C#1
I> (IDMT)
I< low
OR
BLOCK HIGH SET OF B/C
Reverse Blocking
Io>>> start command
Io>> start
11 KV Incomer tripping al
Due to fault summation at
11 KV Incomer -1
Reverse Blocking ( Cont .)
•ADLI Approach lead to rectification of Problem
•
•APPROACH: Specific type of fault was studied
•
•DEPLOYMENT: New Scheme implemented in 61850 compliant grid
stations
•
•LEARNING: On the lines of the scheme implemented in soft form
in 61850 compliant grid stations. New scheme designed for Grid
stations working on older standards is designed.
•
•INTEGRATION: The learning is integrated across all NDPL grids
and that helped a lot in increasing reliability of the network.
•
rectional Protection for parallel feede
33 / 66 KV
unregulated
Input
Voltage
Automatic
Voltage
Regulator
Power
Transformer with
ON - LOAD Tap
Changer
Capacitor Bank
11 KV
regulated
output
voltage
CAP ON TAP
33 / 66 KV
unregulated
Input
Voltage
Automatic
Voltage
Regulator
Power
Transformer with
ON - LOAD Tap
Changer
Capacitor Bank
11 KV
regulated
output
voltage
Underlying logic used …..
Cap . Bank CB
status
K101 K102
U17 U18 11 12
Ratio
< 20 Harmonic
4.0 % odd Harmonic
0.3 % odd THD-i
5.0 %
Iscc / Iload numbers (<11) numbers (>35)
20 - 50 7.0 % 0.5 % 8.0 %
50 - 100 10.0 % 0.7 % 12.0 %
>1000 15.0 % 1.4 % 20.0 %
41
Standard of Harmonics
Limitation
•IEEE 519-1992 Standard: Recommended Practices and
Requirements for Harmonic Control in Electrical
Power Systems (Voltage Distortion Limits)
Table 2: Voltage Harmonic Limits
•
• Voltage Harmonic limit as THD-v (%)
Bus Voltage
• <= 69Kv 3.0 5.0
(%) of Fundamental
•
69 - 161Kv 1.5 2.5
•
• >= 161 Kv 1.0 1.5
•
•
42
H a rm o n ic M e a su re m e n ts
•PCC showing THD higher than the permissible limits is
investigated thoroughly to obtain the spectrum of voltage and
current waveform.
•
•THD is obtained from energy meters attached to the C&R
panels. Examples of such meters are PM500 (Schneider), Ref542+
(ABB), S80 etc.
•
•Power quality analyzer is used to obtain voltage and current
spectrum. Example of such instrument is Fluke power quality
analyzer.
•
•In second phase we would segregate different harmonics and
accordingly design mitigation techniques for specific
feeders.
Exploitation of Relay
facilities
• Detailed study of
∑kA²
•
NO
CASE STUDIES
Tripping Analysis report for 11 KV Mithila
Vihar feeder along - with 11 KV Incomer .
DETAILS OF EVENTS
•11 KV Mithila Vihar feeder tripped along-with 11 KV Incomer
•
OBSERVATIONS
•Total load of the station is around 800 Amps and System is keeping
total load on any of the transformer keeping the other
transformer on no load.
•Mithila Vihar feeder tripped on over current High set.
•11 KV Incomer-2 tripped on over current High set.
•Fault data record of the Incomer show’s that Fault seen by 11 KV
Incomer is 9.1 KA while fault seen by Mithila Vihar feeder is 6.2
KA.
•It is observed that Nithari feeder was also seen the fault but not
tripped due to isolation of the fault. Protection settings were
coordinated and CT Ratio adoption was found correct.
•
CONCLUSION
After going through the tripping events it was observed that both
feeders were getting tripped simultaneously.
CASE STUDY ( Contd ..)
•Both the outgoing feeders were routed on the same poles and on
same cross arm. Thereby, the occurrences of birdage in both
the feeders occur simultaneously.
•
•We have identified around twenty feeders that emerges from the
same bus and have same route, as a corrective action we
changed the emerging bus of those feeders.
Transformer Tripping on
differential protection
PTR - 2 Tripping on differential
protection at Badli Grid .
OBSERVATION
•Stray DC Current component was present in R Phase current at the time of
event.
•It was also confirmed from the event that DC Ingress has caused the
tripping.
•It was confirmed that no ingress was there through external cabling.
•Even after isolating external circuit, Relay has generated tripping.
•Waveform of this particular event was showing that tripping is purely due
to DC Component of the current in CT Circuit. It also shows that after
decay of the DC Current Output relay got reset.
•
CONCLUSION
•It is confirmed that Tripping is due to intermittent DC Ingress in R
Phase Secondary of HV CT Circuit especially.
•In modular type Duo-bias relay, two separate modules are there for power
supply as Well as CT Circuit. It seems DC is getting mixed up in CT
Circuit within the relay.
•
CORRECTIVE ACTION
•Suitable input was given to the OEM for correction in the barrier plate
between power supply module and CT card.
Malfunctioning of Directionality
sense
•On analysis of the cases, we found that the open delta voltage
from the installed IVT’s was causing the spurious trippings.
•
•The cause was mainly because of ageing effect of the IVT’s in the
circuits.
•
•Afterwards we started to make open delta with the spare core of
PT’s in the yard and extending that to the relays.
CT Saturation leading to
differential fault
•Earlier transformer tripping on differential leads to a series of
transformer tests that are carried out to ascertain the health of
transformer.
•
•In some cases a through fault lead to saturation of CT that causes
tripping on differential protection.
•Tests on CT indicated
that knee point voltage
of PS Class CT Core has
got reduced due to
Saturation.
•
•
CT Saturation leading to
differential fault
•A New feature of the Numerical relay can discriminate CT
Saturation.