Sunteți pe pagina 1din 114

Power Quality Partnership

Harmonics in Power Systems

Copper Development Association


Power Quality Partnership

Copper Development Association

Fluke (UK) Ltd

MGE UPS Systems Ltd

Rhopoint Systems Ltd

Copper Development Association


Copper Development
Association
• Established 1933
• website - www.cda.org.uk
• Technical helpline 01727 731200
• IEE Endorsed Provider

Copper Development Association


Harmonics in Power Systems

Background to Harmonics, Problems, Solutions and Standards


David Chapman, Copper Development Association

Harmonic Measurement and Power Quality Surveys


Ken West, Fluke (UK) Ltd

Total Harmonic Management


Shri Karve, MGE UPS Systems Ltd

Applying Predictive Techniques to Power Quality


David Bradley, Rhopoint Systems Ltd

Copper Development Association


Fundamental with third and fifth harmonics
1.100

Fundamental

Third harmonic

Fifth harmonic

0.000
0 90 180 270 360

-1.100

Copper Development Association


Composite waveform
1.600

0.000
0 90 180 270 360

-1.600

Copper Development Association


Loads that generate harmonics

 Switched mode power supplies (SMPS)

 Electronic fluorescent lighting ballasts

 Variable speed drives

 Un-interruptible power supplies (UPS)

These are all non-linear loads

Copper Development Association


How harmonics are generated – linear load

Copper Development Association


How harmonics are generated – non-linear load

Copper Development Association


A Common non-linear load

Copper Development Association


Current waveform for a typical Personal Computer

Copper Development Association


Harmonic profile of a typical Personal Computer

Copper Development Association


Harmonic profile for electronic fluorescent ballast

Copper Development Association


Harmonic profile for magnetic fluorescent ballast

Copper Development Association


Six-pulse bridge

Copper Development Association


Typical harmonic profile - six-pulse bridge

Six pulse bridge - harmonic current

25

20

15

10

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Harmonic number

Copper Development Association


Twelve-pulse bridge

Copper Development Association


Typical harmonic profile - twelve-pulse bridge
Twelve pulse bridge - harmonic current

25

20

15

10

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Harmonic number

Copper Development Association


Why have harmonics become so important?

Harmonic generating equipment has been in


use for decades

• Increase in the number of loads

• Change in the nature of loads

• Increase in those producing triple-Ns

Copper Development Association


Equivalent circuit of a harmonic generating load

Copper Development Association


Harmonic Diversity

80

70

60

50

% wrt RMS 40

30

20

10

0
41
Fund 20
3rd 10
5th 5 No of Units (pairs)
Harmonic 7th
9th 2
11th 1

Copper Development Association


Harmonic Diversity - THDI

THD

120

100

80
% wrt Fundamental

60

40

20

0
1 2 5 10 20 41
No of Units (pairs)

Copper Development Association


Problems caused by harmonics
 currents within the installation
 overloading of neutrals
 overheating of transformers
 nuisance tripping of circuit breakers
 over-stressing of power factor correction capacitors
 skin effect
 voltages within the installation
 voltage distortion & zero-crossing noise
 overheating of induction motors
 currents in the supply

Copper Development Association


Overheating of neutrals

In balanced three phase systems the


fundamental current cancels out

But triple-N harmonics add arithmetically!

Non triple-N harmonics cancel in the neutral

Copper Development Association


Harmonic neutral currents

8 .0

P hase 1 Phase 2 P hase 3

6 .0

P hase 1 3rd harmonic


4 .0

P hase 2 3rd harmonic


2 .0

P hase 3 3rd harmonic


0 .0

0 120 240 360 480 600 720


-2 .0

3rd harmonic neutral current

-4 .0

-6 .0

-8 .0

Copper Development Association


Neutral conductor sizing

Copper Development Association


Neutral conductor sizing

Copper Development Association


Neutral conductor sizing

Copper Development Association


Neutral conductor sizing

Neutral currents can easily approach twice the phase


currents - sometimes in a half-sized conductor.

IEEE 1100-1992 recommends that neutral busbars


feeding non-linear loads should have a cross-
sectional area not less than 173% that of the phase
bars.

Neutral cables should have a cross-sectional area that


is 200% that of the phases, e.g. by using twin single
core cables.

Copper Development Association


Sizing the neutral conductor

BS 7671:2001 - From January 2002

473 - 03 - 04

where neutral current is expected to exceed phase


current

473 - 03 - 05
where neutral cross-section is less than phase cross
section

- neutral overcurrent protection is required

Copper Development Association


Sizing the neutral conductor

For three phase circuits using single core cables:

• Use a neutral conductor sized for the actual


neutral current

• If the neutral current is not known, use a double


sized neutral cable

• Provide overcurrent protection

• But take account of the grouping factors!

• Take into account voltage drop

Copper Development Association


Sizing the neutral conductor
For multi-core cables :

• Multi-core cables are rated for only three loaded


cores - applies to both 4 and 5 core cables

• When harmonics are present the neutral is also a


current carrying conductor

• Cable rated for three units of current is carrying


more - three phases plus the neutral current

• It must be de-rated to avoid overheating

• Neutral must have overcurrent protection

• Grouping factor must be taken into account


Copper Development Association
Sizing the neutral conductor - thermal
2.5

2.0
Cable size multiplier

1.5

1.0

0.5
0 10 20 30 40 50 60 70
% third harmonic current in phase

Copper Development Association


Sizing the neutral conductor - IEC
2.5

2.0
Cable size multiplier

1.5

1.0

0.5
0 10 20 30 40 50 60 70
% third harmonic current in phase

Copper Development Association


Sizing the neutral conductor
2.5

Thermal
IEC

2.0
Cable size multiplier

1.5

1.0

0.5
0 10 20 30 40 50 60 70
% third harmonic current in phase

Copper Development Association


Neutral conductor protection

Neutral conductors should be appropriately


sized and provided with over-current protection.

The protective device must break all the phases,


but does not necessarily need to break the
neutral itself.

This implies a future need for 4 pole breakers


with double rated neutral poles.

Copper Development Association


Effect of harmonics on transformers

Transformers supplying harmonic loads must be


appropriately de-rated

 Harmonic currents, being of higher frequency,


cause increased magnetic losses in the core
and increased eddy current and skin effect
losses in the windings

 Triple-n harmonic currents circulate in delta


windings, increasing resistive losses, operating
temperature and reducing effective load
capacity

Copper Development Association


Increased Eddy current losses in transformers

Increase in eddy current loss can be calculated by:

h  h max
Peh  Pef  I 2h h 2
h 1

where:
Peh is the total eddy current loss
Pef is the eddy current loss at fundamental
frequency
h is the harmonic order
Ih is the RMS current at harmonic h as a
percentage of rated fundamental current
Copper Development Association
K-Rating of Transformers

Two rating or de-rating systems for transformers:-

• American system, established by UL and


manufacturers, specifies harmonic capability of
transformer - known as K factor.

• European system, developed by IEC, defines


de-rating factor for standard transformers -
known as factor K.

Copper Development Association


K-Rating of Transformers - US System

First, calculate the K factor of the load according to:

h  h max
K  I 2h h 2
h 1

where:
h is the harmonic order
Ih is the RMS current at h in per unit of rated load current

Copper Development Association


K-Rating of Transformers - US System

For this typical PC load, the K factor is 11.6


(See IEE 1100-1992 for a worked example)

Copper Development Association


K-Rating of Transformers - US System

Next, select a transformer with a higher K rating:


standard ratings are 4, 9, 13, 20, 30, 40 and 50.

NB - for non K-rated transformers:

The K factor describes the increase in eddy


current losses, not total losses.

Copper Development Association


K-Rating of Transformers - European System
In Europe, the transformer de-rating factor is calculated
according to the formulae in BS 7821 Part 4. The factor
K is given by:
0.5
 e  I1 
2 n N  I   2
 n q  n  

K  1

 
1 e  I 
   I1  
 n2
 

e is ratio of eddy current loss (50 Hz) to resistive loss


n is the harmonic order
q is dependent on winding type and frequency,
typically 1.5 to 1.7

Copper Development Association


K-Rating of Transformers - European System

For the same PC load, the de-rating factor is 78%

Copper Development Association


K Factor

The methods for rating transformers


are discussed in CDA Publication 144

In addition, calculation software is


available on our web site:

www.cda.org.uk

Copper Development Association


K-Rating - Calculation software

Copper Development Association


K-Rating - Calculation software

Copper Development Association


Harmonic Diversity - K Factor
K Factor

16

14

12

10
K Factor

0
1 2 5 10 20 41
No of Units (pairs)

Copper Development Association


K-Rating or De-rating?

‘K-rated’ transformers are designed to supply harmonic


loads by :
• using stranded conductors to reduce eddy current
losses
• bringing secondary winding star point connections
out separately to provide a 300% neutral rating

Copper Development Association


K-Rating or De-rating?

‘De-rating’ a standard transformer has some


disadvantages:-
 primary over-current protection may be too high
to protect the secondary and too low to survive
the in-rush current
 the neutral star point is likely to be rated at only
100% of the phase current
 it is less efficient
 future increases in loading must take the de-rating
fully into account

Copper Development Association


Effect of harmonics on transformers

Transformers supplying harmonic loads must be


appropriately de-rated

 Harmonic currents, being of higher frequency,


cause increased magnetic losses in the core
and increased eddy current and skin effect
losses in the windings

 Triple-n harmonic currents circulate in delta


windings, increasing resistive losses, operating
temperature and reducing effective load
capacity

Copper Development Association


Effect of triple-n harmonics in transformers
Triple-n harmonic currents circulate in delta windings -
they do not propagate back onto the supply network.

- but the transformer must be specified and rated to


cope with the additional losses.

Copper Development Association


Skin effect

Alternating current tends to flow on the outer surface


of a conductor - skin effect - and is more pronounced
at high frequencies.

 At the seventh harmonic and above, skin effect


will become significant, causing additional loss
and heating.

 Where harmonic currents are present, cables


should be de-rated accordingly. Multiple cable
cores or laminated busbars can be used.

Copper Development Association


Skin effect - penetration depth
where:
1   105 d is the depth of penetration, mm
d
2 f f is the frequency, Hz, and
 is the resistivity of the
conductor

At the fundamental, 50 Hz d = 9.32 mm


At the 11th harmonic, 550Hz d = 2.81 mm

Copper Development Association


Circuit breakers

Nuisance tripping can occur in the presence of


harmonics for two reasons:

 Residual current circuit breakers are


electromechanical devices. They may not sum
higher frequency components correctly and
therefore trip erroneously.

 The current flowing in the circuit will be higher


than expected due to the presence of harmonic
currents. Most portable measuring instruments
do not read true RMS values.

Copper Development Association


Problems caused by harmonics
 currents within the installation
 overloading of neutrals
 over-heating of transformers
 over-stressing of power factor correction capacitors
 skin effect
 nuisance tripping of circuit breakers
 voltages within the installation
 voltage distortion & zero-crossing noise
 over-heating of induction motors
 currents in the supply

Copper Development Association


Voltage distortion

Copper Development Association


Reducing Voltage Distortion by Circuit Separation

Copper Development Association


Effect of harmonics on induction motors
 Increased magnetic and copper losses

 Each harmonic generates a field which may rotate


forward (+), backward (-), or remain stationary (0)

1 2 3 4 5 6 7 8 9 10 11 12

+ - 0 + - 0 + - 0 + - 0

• Zero sequence harmonics produce a stationary field,


causing over-heating and reduced efficiency

Copper Development Association


Effect of harmonics on induction motors
• The negative and positive sequence harmonics
together cause torque pulsing, vibration and
reduced service life
• Harmonics are induced in the rotor leading to
overheating and torque pulsing

Stator harmonic 1 5 7 11 13 17 19
Rotor harmonic - 6 6 12 12 18 18
Harmonic rotation F B F B F B F

Copper Development Association


Motor de-rating curve for harmonic voltages

0.95

0.9
De-rating Factor

0.85

0.8

0.75

0.7
0 2 4 6 8 10 12
Harmonic Voltage Factor (HVF)

Copper Development Association


Harmonic voltage factor
The Harmonic Voltage Factor (HVF) is defined as:

n  V 2
n
HVF  
n 5 n
where:
Vn is the RMS voltage at the nth harmonic as a
percentage of the fundamental, and
n is the order of each odd harmonic, excluding
triple-Ns

Copper Development Association


Harmonic problems affecting the supply
 Harmonic currents cause harmonic voltage
distortion on the supply that can affect
other customers. This distortion can
propagate onto the 11 kV grid and spread
widely.

 There are limits for harmonic voltage


distortion - a supplier may refuse to
supply power to a site that exceeds them.

Copper Development Association


Harmonic Standards
Electricity Association Engineering
Recommendation G 5/4 (2001)

BS EN 61000

IEEE Std 519-1992 Recommended Practices and


Requirements for Harmonic Control in Electrical
Power Systems

ISBN 1 - 55937 - 239 - 7


Copper Development Association
Why revise G5/3?

 Levels at 132kV higher than Grid Code allows


 Introduction of concept of Electromagnetic
Compatibility
 G5/3 didn’t include notching and burst harmonics
 Introduction of the EU Compatibility Directive and
developments in IEC and European Standards

 Better information on network harmonic impedance


(see ETR 112)

Copper Development Association


The Electromagnetic Compatibility concept

 Satisfactory operation of supply systems and


users’ equipment only when electromagnetic
compatibility exists between them
 Emission limits help fulfil this objective
 G5/4 seeks to limit harmonic distortion levels on
the network at the time of connection to below the
immunity levels of equipment
 Enforced via the Electricity Supply Regs, Grid &
Distribution Codes, and connection agreements

Copper Development Association


Harmonic Compatibility
Planning levels
Compatibility Level
Total supply
network
disturbance Immunity Susceptibility of
(test) levels local equipment
Emission
limits for
Probability Density

individual
sources

Disturbance Level

Copper Development Association


Compatibility levels v Planning levels
 Compatibility levels in IEC 61000-2-2 & 61000-2-12,
for 400V and 6.6kV to 33kV systems are based on
the immunity of capacitors

 The margins between planning levels and the


compatibility levels depend on voltage level and
range from 3% at lv and 5% at mv to 0.5% at ehv

 The margins are necessary to make allowance for


system resonance and for loads connected where
there is no consent required from the DNO

Copper Development Association


Stage 1

 Applies only to lv connected loads

 Requires reference to other IEC standards e.g.


 IEC 61000-3-2 emissions from lv connected
equipment <16A
 IEC 61000-3-4 ditto >16A (To be 61000-3-12)

 Clarifies that levels may be modified by reference to


relevant fault levels rather than the notional ones
used to derive the table of emissions Table 7

Copper Development Association


Aggregate loads
 G5/4 requires that aggregate non-linear loads be
considered
• An individual non-linear equipment complying
with 61000-3-2 can be connected without
consideration
• Groups of non-linear equipment with
aggregate rated current <16A and complying
can be connected
• For >16A either 61000-3-4 or 61000-3-6 should
be used to assess emissions using diversity
rules from 61000-3-6 if necessary

Copper Development Association


Example of application - the problem
 Connection of communication centre equipment
– 15 off rectifier equipment type R2948-15
– each equipment is rated at 12.37A
– each equipment meets BS EN 61000-3-2
– the connection will be at lv and single phase
– future expansion expected to 30 units

 Can they be connected?

 The customer says that no data on emissions is


available

Copper Development Association


The solution

 Data must be available - cannot claim


BS EN 61000-3-2 compliance otherwise!

 Data was obtained simply by e-mailing


the manufacturer in New Zealand

 Simplified calculations were carried out


on a spreadsheet to check compliance

Copper Development Association


Product data sheet
Product Test
Harmonic Emissions
Test Parameters
Product: R2948-15 Input Voltage: 230v 50Hz
Serial #: 1040171 Output Voltage: 54v at no load
Product Compliance Group
Date tested: 07 October 1999 Output Current: 52A
Ambient temperature: +20°C
12.37A
0.5
EUT
EN61000-3-2

0.4

0.3
IP Currenty(A)

0.2

0.1

0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Harmonic (f1 = 50Hz)

Copper Development Association


The calculations

 As a first estimate the current emissions are


multiplied by the number of units, and the result
compared with the values in Table 7 of G5/4.
This shows that there is no problem

 The spreadsheet calculations would show that


the future increase to 30 units would give values
of emissions greater than the limits for triple-Ns
above 21st

Copper Development Association


Table 7: Stage 1 Max Harmonic RMS Current Emissions
for aggregate loads and equipment rated >16A per phase

Harmonic Emission Harmonic Emission Harmonic Emission Harmonic Emission


order ‘h’ current Ih order ‘h’ current Ih order ‘h’ current Ih order ‘h’ current Ih
2 28.9 15 1.4 28 1.0 41 1.8
3 48.1 16 1.8 29 3.1 42 0.3
4 9.0 17 13.6 30 0.5 43 1.6
5 28.9 18 0.8 31 2.8 44 0.7
6 3.0 19 9.1 32 0.9 45 0.3
7 41.2 20 1.4 33 0.4 46 0.6
8 7.2 21 0.7 34 0.8 47 1.4
9 9.6 22 1.3 35 2.3 48 0.3
10 5.8 23 7.5 36 0.4 49 1.3
11 39.4 24 0.6 37 2.1 50 0.6
12 1.2 25 4.0 38 0.8
13 27.8 26 1.1 39 0.4
14 2.1 27 0.5 40 0.7

Copper Development Association


Sample spreadsheet
Harmonic Emission Emissions Table 7 Emissions
number from EUT 15 units emissions 30 units
3 0.42 6.3 48.1 12.6
5 0.21 3.1 28.9 6.2
7 0.16 2.3 41.2 4.7
9 0.11 1.65 9.6 3.3
15 0.03 0.43 1.4 0.8
21 0.035 0.525 0.7 1.05

Emissions in Amps (RMS)

Copper Development Association


Example flow chart for lv connection
START

N N N
Less than Complies with Complies with
16A 61000-3-4 6.3.1
Y Y
Y
N N
<5 kVA
Y 3 phase
Complieswith
Complies with
61000-3-2
61000-3-2 Y
0 Y
N Complies N
with Table 6
N
Complies with Y Y Complies
6.2 with Table 7
Y
N
Mitigation required Connect to network Go to Stage 2

Copper Development Association


Stage 2
 This applies only to:

 a load or aggregate load that doesn’t meet IEC


61000-3-2 and 61000-3-6, or Table 7 current
emissions, i.e. Stage 1

 PCC less than 33kV i.e. at 6.6, 11 or 22kV

 Current emissions can be less than Table 12, or a


simplified voltage assessment can be used based
on the harmonic impedance just described

Copper Development Association


Harmonic Measurements

Copper Development Association


Assessment of the connection of new
non-linear equipment under Stage 2

a) measure voltage distortion present at PCC

b) assess the voltage distortion which will be


caused by the new equipment, and

c) predict the possible effect on harmonic


voltage levels by an addition of the results
of (a) and (b)

Copper Development Association


Assessment of the connection of new
non-linear equipment under Stage 2

If the results of (c) are less than


• the harmonic voltage planning levels for the
5th harmonic and
• the THD planning level

connection of the equipment is acceptable

Copper Development Association


Combination rules
 for harmonics up to and including the 5th and for
all triple-Ns, the measured and calculated values
of voltage distortion are assumed to peak at the
same time and to be in phase - linear addition

 for the other harmonics, an average phase


difference of 90 is assumed at the time of
maximum THD - rms addition

 the THD is then given by the rms addition of all


combined harmonics up to the 50th

Copper Development Association


The Challenge

to keep the harmonic voltage distortion at the point of


common coupling below levels permitted by G5/4

to keep harmonic currents below levels

that cause equipment overload and damage within the


installation

that are permitted by G5/4

Copper Development Association


Harmonic solutions

Steps to be taken to reduce voltage distortion on


the supply include, for example:

 Passive harmonic filters

 Isolation transformers

 Active harmonic conditioners

Copper Development Association


Passive harmonic filters

Filters are useful when

 the harmonic profile is well defined – such as


motor controllers

 the lowest harmonic is well above the


fundamental frequency

- but filter design can be difficult and, especially


for lower harmonics, the filters can be bulky and
expensive

Copper Development Association


Passive harmonic filter

Copper Development Association


Power Factor 

V I
Ip
Iq

Copper Development Association


0  2
Power Factor
POWER

Ip

Copper Development Association


0  2
Power Factor
POWER

Iq

0  2
Copper Development Association
Power Factor 

V IL
I1

I7
I5

Copper Development Association


0  2
Power Factor
G

active reactive power


power
M
Copper Development Association
Power Factor Correction
G

CAPACITOR
active reactive power
power
M
Copper Development Association
Power Factor Correction
G

CAPACITOR
active reactive power
power
M
Copper Development Association
Power Factor Correction
• Diversity
• Self Excitation
• Harmonics

M M M M

Copper Development Association


Power Factor Correction

Control

M M M M

Copper Development Association


Power Factor Correction

• Transformer overloading
• Step voltage
Control
• Bank Size
• Switch-fuse & Cable load
ratings
• Load make/break rating
of main isolator/switch-
M M M M fuse

Copper Development Association


Power Factor Correction Bank Sizing
Required improvement in % wattess
X kW Maximum Demand

equivalent to {tan(cos-1PFA) - tan(cos-1PFR)} X MD (kW)

or

kVArh (actual) - kVArh (required)


running hours X load factor

Copper Development Association


Power Factor Correction

• Capacitor Discharge time required for


standard Power Factor banks (1 minute)

• Rapidly switching loads require Zero


crossing Thyristor or IGBT switched
steps

e.g. Spot Welders


Lift motors
Cranes

Copper Development Association


Harmonic Resonance

TO POWER SYSTEM

LV

CONVERTOR

M HARMONICS
AMPLIFIED
HARMONICS
Copper Development Association
Detuned or Blocking Banks

SOURCE IMPEDANCE WITH FILTER IN CIRCUIT


Capacitive
0.3000

0.2500 Fo = 189 to 204 Hz


0.2000

Inductive
Y = Ln (Z+1)

0.1500

5th 7th 11th


0.1000

0.0500

0.0000
100

124
136
148
160

196
208
220
232

256

268
280
292

328
340

352
364

388

400
412
424

460
472
484

520
532

544
556

592
172
184

244

304
316

376

436
448

496
508

568
580
112

Frequency

Copper Development Association


Filter Banks - 5th Harmonic
SOURCE IMPEDANCE WITH FILTER IN CIRCUIT

Capacitive
0.3000

Fo = 235 to 245Hz
0.2500 7th
0.2000
Y=Ln (Z+1)

0.1500

Inductive
0.1000

0.0500

0.0000

Frequency

Copper Development Association


Filter Banks 5th & 7th Harmonic
SOURCE IMPEDANCE WITH FILTER IN CIRCUIT

0.5000

0.4500

0.4000

0.3500 5th 7th


0.3000
Y = Ln (Z+1)

0.2500

0.2000

0.1500

0.1000

0.0500

0.0000
124

160

280

400

556

568
100

136
148

172
184

196

208

220
232
244

256

268

292

304

316
328
340

352

364

376

388

412

424

436

448
460

472

484

496
508

520

532

544

580
592
112

Frequency

Copper Development Association


Third harmonic filters

10 Amps
R

30 Amps
N
Load
S 10 Amps
10 Amps
T
E

Copper Development Association


Third harmonic filters

10 Amps
R

I3 =300 Amps
Amps
N
Load
S 10 Amps
v 10 Amps
T
E

Copper Development Association


Delta Interconnected-Star Transformer
R S T R S T

Copper Development Association


N
Harmonic reduction transformers

Load
I3

Interconnected Star
Transformer sized for
harmonic currents only

Copper Development Association


Isolating transformers

Delta-star isolating transformers reduce propagation


of harmonic current into the supply.

 Transformers should be adequately rated to


cope with the harmonics

 Although the transformer effectively


establishes a new neutral, don’t use half-sized
neutrals

 Provide a well rated four wire feed so that the


transformer can be isolated for service

Copper Development Association


Isolating transformers

Copper Development Association


Isolating transformers

Copper Development Association


Isolating transformers

Copper Development Association


Isolating transformers

Copper Development Association


Active filters

 Where the harmonic profile is unpredictable or


contains a high level of lower harmonics,
active filters are useful

 Active harmonic conditioners operate by


injecting a compensating current to cancel the
harmonic current

Copper Development Association


Harmonic solutions
 Keep circuit impedances low

 Rate neutrals and multi-core cables generously -


1.73 to 2 times normal size

 Always use true RMS meters

 Provide a large number of separate circuits to


isolate problem and sensitive loads

 Take harmonics into account when rating


transformers

 Provide appropriate filtration where required

Copper Development Association


Harmonics in Power Systems

Copper Development Association

www.cda.org.uk

Copper Development Association

S-ar putea să vă placă și