FIRE TRIANGLE
FUEL VAPOUR
OXYGEN
HEAT
TO COMBAT A FIRE, WE CAN REMOVE ANY ONE COMPONENT IN THE FIRE TRIANGLE OR THE CHAIN REACTION IN THE FIRE TETRAHEDRON HEAT COMPONENT - COMBAT BY COOLING OXYGEN COMPONENT - COMBAT BY SMOTHERING FUEL - COMBAT BY STARVATION
CLASSIFICATION OF FIRE
CLASS A FIRES
WOOD BASE MATERIALS TEXTILES & FIBRES PLASTIC & RUBBER
CLASS B FIRES
FLAMMABLE LIQUIDS COMBUSTIBLE LIQUIDS PAINTS & VARNISHES FLAMMABLE GASES
CLASS C FIRES
GENERATORS MOTORS WIRING SWITCHES, FUSES
CLASS D FIRES
SODIUM POTASSIUM MAGNESIUM TITANIUM, ALUMINIUM
CABIN FIRE
WHEN THE FIRE ALARM IS SOUNDED, RUSH TO THE MUSTER STATION HEAD COUNT IS CARRIED OUT AND ANY MISSING PERSON MUST BE DETERMINED REPORT TO THE BRIDGE AND AWAIT FOR THE ORDERS FROM THE MASTER FIRE FIGHTING PARTY TO DON THE FIRE FIGHTERS OUTFIT AND THE BA SET THE BACK-UP PARTY STANDBY WITH THE FIRE FIGHTERS OUTFIT AND THE BA SET
FIRST AID PARTY GETS READY AND STAND BY IDENTIFY THE ZONE OF FIRE (FROM THE FIRE DETECTION PANEL) IDENTIFY THE TYPE OF FIRE OR THE POSSIBILITY- CLASS C OR CLASS A SHUT ALL THE VENTILATORS, AIR-CON, DAMPERS, FIRE DOORS AND ANY OTHER OPENINGS PROCEED TO THE ZONE OF FIRE. ENTER WITH A WATER HOSE UNDER PRESSURE. USE WATER SPRAY AS A SHIELD IF NECESSARY WHEN ENTERING IF A POSSIBILITY OF FIRE IS SUSPECTED INSIDE A CABIN, FEEL THE DOOR WITH THE BACK OF THE PALM. IF HOT FIRE IS NOT DEAD. ONCE FIRE IS EXTINGUISHED IT MUST BE REPORTED TO THE BRIDGE FIRE WATCH IS MAINTAINED AND THE CAUSE IS INVESTIGATED
IF DANGEROUS CARGO IS PRESENT THEN THE TEAM SHOULD WEAR THE CHEMICAL SUIT ALL VENTILATORS, BOOBY HATCH COVERS AND CARGO HOLD FANS ARE SHUT FIRE FIGHTING TEAM THEN PROCEEDS TO THE CARGO HOLD, WHILE THE BACK-UP TEAM CARRIES OUT BOUNDARY COOLING IF CO2 TO BE USED,AGAIN THIS SHOULD BE THE LAST RESORT IF ANY PERSON IS SUSPECTED TO BE INSIDE ONCE THE FIRE IS SUSPECTED TO BE EXTINGUISHED, ENTER THE HOLD AND CONFIRM VISUALLY WHEN ENTERING THE HOLD DURING OR AFTER EXTINGUISHING A LIFE-LINE MUST BE ATTACHED TO THE PERSONS ENTERING FINALLY THE CAUSE OF FIRE TO BE INVESTIGATED
AT LEAST 2
DIAMETER OF THE FIRE MAINS SHALL BE SUFFICIENT FOR THE EFFECTIVE DISTRIBUTION OF THE MAXIMUM REQUIRED DISCHARGE FROM THE TWO FIRE PUMPS OPERATING SIMULTANEOUSLY, EXCEPT IN THE CASE OF CARGO SHIPS WHERE THE DIAMETER NEED ONLY BE SUFFICIENT FOR THE DISCHARGE OF 140m/h. THE NUMBER AND POSITION OF HYDRANTS SHALL BE SUCH THAT AT LEAST TWO JETS OF WATER NOT EMANATING FROM THE SAME HYDRANT, ONE OF WHICH SHALL BE FROM A SINGLE LENGTH OF HOSE, MAY REACH ANY PART OF THE SHIP NORMALLY ACCESSIBLE TO THE PASSENGERS OR CREW. IN PASSENGER SHIPS THERE SHALL BE AT LEAST ONE FIRE HOSE FOR EACH OF THE HYDRANTS. THESE SHALL BE USED ONLY FOR THE PURPOSE OF EXTINGUISHING FIRES OR TESTING DURING FIRE DRILLS AND SURVEYS.
IN CARGO SHIPS OF 1000GRT AND UPWARDS THE NUMBER OF FIRE HOSES TO BE PROVIDED SHALL BE ONE FOR EACH 30M LENGTH OF THE SHIP AND ONE SPARE BUT IN NO CASE LESS THAN FIVE IN ALL. THIS NUMBER DOES NOT INCLUDE ANY HOSES REQUIRED IN ANY ENGINE OR BOILER ROOM. IN CARGO SHIPS OF LESS THAN 1000GRT THE NUMBER OF FIRE HOSES SHALL BE TO THE SATISFACTION OF THE ADMINISTRATION. IN ADDITION SHIPS CARRYING DANGEROUS CARGO SHALL BE PROVIDED 3 HOSES AND NOZZLES. EACH FIRE HOSE SHALL BE PROVIDED WITH A NOZZLE AND THE NECESSARY COUPLINGS
PASSENGER SHIPS OF >36 PAX SHALL BE EQUIPPED WITH AUTOMATIC SPRINKLER SYSTEM IN ALL CONTROL STATIONS, CORRIDORS AND STAIRWAYS PASSENGER SHIPS OF < 36 PAX AUTOMATIC SPRINKLER SYSTEM SHALL BE PLACED IN THE CORRIDORS, STAIRWAYS, ETC WITHIN ACCOMODATION SPACES ACCCORDING TO THE REQUIREMENTS OF THE ADMINISTRATION CARGO SHIPS SHALL BE PROVIDED WITH FIXED FIRE FIGHTING SYSTEMS IN CARGO SPACES, PUMP-ROOM, GALLEY AND MACHINERY SPACE
SMOKE DETECTORS SHALL BE INSTALLED IN ACCOMODATION SPACES, ESCAPE ROUTES, ETC PASSENGER SHIPS >36 PAX - FIXED FIRE DETECION & ALARM SYSTEMS SHALL BE INSTALLED IN ACCOMODATION SPACES, SERVICE SPACES, CONTROL STATIONS, ETC EXCEPT IN BATHROOMS, PUBLIC TOILETS, CO ROOMS PASSENGER SHIPS <36 PAX - FIXED IN EACH SEPARATE ZONE, ACCOMODATION SPACES, SERVICE SPACES CARGO SHIPS - SMOKE DETECTORS IN ALL CORRIDORS, STAIRWAYS, ESCAPE ROUTES WITHIN ACCOMODATION SPACES. AUTOMATIC SPRINKLER & FIRE ALARM SYSTEM WITHIN GALLEY, ENGINE ROOM, ETC. SMOKE DETECTION SHALL BE FIXED IN CARGO SPACES
DONT SLEEP!
PORTABLE EXTINGUISHERS SHALL BE PROVIDED WITH DEVICE WHICH INDICATES WHETHER THEY HAVE BEEN USED OR NOT THERE SHALL BE ONE PORTABLE FOAM APPLICATOR UNIT AT THE ENTRANCE OUTSIDE OR IN THE BOILER ROOM. THERE SHALL BE AT LEAST TWO SIMILAR EXTINGUISHERS OR EQUIVALENT IN EACH FIRING SPACE IN THE BOILER ROOM. THESE EXTINGUISHERS SHALL BE PROVIDED WITH HOSES ON REELS THERE SHALL BE SUFFICIENT FOAM TYPE EXTINGUISHERS OF AT LEAST 45 LITRES OR EQUIVALENT TO BE DIRECTED ONTO ANY PART OF LUBE OIL PRESSURE SYSTEMS, GEARING OR OTHER FIRE HAZARDS IN ADDITION THERE SHALL BE SUFFICIENT NUMBER OF PORTABLE FOAM OR EQUIVALENT EXTINGUISHERS WITHIN MACHINERY SPACE SO PLACED THAT NO POINT IN THE SPACE IS MORE THAN 10m WALKING DISTANCE FROM AN EXTINGUISHER PORTABLE EXTINGUISHERS OF 12kg OF DRY POWDER SHALL BE PROVIDED IN THE CARGO HOLD SPACES. PORTABLE EXTINGUISHERS SHALL BE PROVIDED AT EACH DECK LEVEL IN EACH HOLD, SPACE NOT MORE THAN 20m APART ON BOTH SIDES OF THE SPACE
FIXED FIRE DETECTION AND FIRE ALARM SYSTEMS FIXED FIRE EXTINGUISHING SYSTEMS & FFA AUTOMATIC SPRINKLERS, FIRE DETECTION AND FIRE ALARMS VENTILATION SYSTEMS, INCLUDING FIRE AND SMOKE DAMPERS, FANS & THEIR CONTROLS EMERGENCY SHUTDOWN OF FUEL FIRE DOORS, INCLUDING THEIR CONTROLS EEBD PORTABLE FIRE EXTINGUISHERS, INCLUDING BA SETS AND SPARE BOTTLES FIRE FIGHTERS OUTFIT CHEMICAL SUITS
THE VALVES ARE GREASED PROPERLY AND EASY TO MOVE PRESSURE TESTING HOSES TESTING SPRAY NOZZLES THROUGH THEIR OPERATING RANGE REPLACE DAMAGED PARTS, LIKE BOLTS, COUPLINGS, ETC IF FOUND NON-FUNCTIONAL ORDER NEW SPARES
ENSURE SAFETY PIN PUT IN CAP AFTER RECHARGING WRITE THE DATE OF TEST ON THE LABEL ATTACHED REPLACE CYLINDER IN PREVIOUS POSITION
RISE
-END-