Sunteți pe pagina 1din 40

DENUMIRE CIRCUIT

C1
C2
C3
C4
C5
C6
CP1
CP2
CP3
CP4
CP5
CP6
CIRCUIT REZERVA
CIRCUIT REZERVA
CIRCUIT REZERVA

NUMAR CIL
17
10
17
10
8
8
6
7
2
7
4
4

L1
1000

L2

L3

1200
1025
950
775
850
2000
2000
2000
2000
2000
2000

OBSERVATII
D0+D8
D1+D7
D6
D2+D5
D3
D4
D0+D8
D1+D7
D6
D2+D5
D3
D4

2000
2000
2000

7950

7975

7875

L1

L2

L3
820

SUBSOL
DENUMIRE CIRCUIT
C1
C2
C3
C4
C5
C6
C7
CIRCUIT REZERVA

NUMAR CIL
10
10
14
12
13
8
8

820
820
738
533
328
656
1500

2214

2033

6215

1968

OBSERVATII
S01+S02
S03
S04+S05
S06+S07
S08
S09
S10+S11

41.08
41.18
40.75

27.16
27.197
27.058

49.24664456
49.35047324
48.91521097

Parter

5800
18000

264
246
Siguranta
DENUMIRE CIRCUIT
CS1
CS2
CS3
CS4
CS5
CS6
CIRCUIT REZERVA

NUMAR CIL
12
12
6
6
6
6

L1

L2

L3
264

264
246
246
246
246
350

350

350

860

842

860

OBSERVATII

Calculul circuitelor de lumina


C1

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
1000
4.577

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 3FY1,5

Conductor din Cu:

Numar conductoare n=3


Ima =
17
[A]
[mm2]
SF=
1.5
SF=SN=

1.5

[mm2]

SPE=

1.5

[mm2]

<25 mm2

Sectiunea nulului de protectie

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

3FY1,5/IPEY 16

10

[A]

izolant
protejant
etans
masa plastica

C3

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
1025
4.691

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 3FY1,5

Conductor din Cu:

Numar conductoare n=3


Ima =
17
[A]
[mm2]
SF=
1.5
[mm2]
SF=SN=
1.5

<25 mm2

Sectiunea nulului de protectie


SPE=

1.5

[mm2]

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

3FY1,5/IPEY 16

10

[A]

izolant
protejant
etans
masa plastica

C5

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
850
3.890

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 3FY1,5

Conductor din Cu:

Numar conductoare n=3


Ima =
17
[A]
[mm2]
SF=
1.5
[mm2]
SF=SN=
1.5

<25 mm2

Sectiunea nulului de protectie


SPE=

1.5

[mm2]

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

3FY1,5/IPEY 16

10

[A]

izolant
protejant
etans
masa plastica

CALCULUL PIERDERILOR DE TENSIUNE


1. Circuitul cel mai indepartat
Circuitul de lumina C1 are o lungime totala de 20.5 m
Tronsonul 1
P1=
L1=
P1=p1*l1=

200 [W]
6 [m]
1200 [W/m]

Tronsonul 2
P2=
L2=
P2=p2*l2=

75 [W]
9 [m]
675 [W/m]

100 [W]
5.6 [m]
560 [W/m]

Tronsonul 4
P4=
L4=
P4=p4*l4=

150 [W]
7.7 [m]
1155 [W/m]

200 [W]
6 [m]
1200 [W/m]

Tronsonul 6
P6=
L6=
P6=p6*l6=

75 [W]
9 [m]
675 [W/m]

Tronsonul 7
P7=
L7=
P7=p7*l7=

100 [W]
5.6 [m]
560 [W/m]

Tronsonul 8
P8=
L8=
P8=p8*l8=

75 [W]
1.5 [m]
112.5 [W/m]

Tronsonul 9
P9=
L9=
P9=p9*l9=

1000 [W]
20.5 [m]
20500 [W/m]

Tronsonul 3
P3=
L3=
P3=p3*l3=

Tronsonul 5
P5=
L5=
P5=p5*l5=

Zona circuitelor:
=
54 (m/mm2)
s=
(P*l/s)=(P1+P2+P3+P4+P5+P6+P7+P8+P9)/2,5=
17758.33
U1=((2*100/*Uf)*P*l/s)%=
1.243 (%)
Zona coloanei secundare:
P=5*Pi= 5*5800=
l=
(P*l/s)=
U2=((100/*U)*P*l/s)%=
Zona coloanei principale:
P=29000+6215=
l=
(P*l/s)=

29000 [W]
12 [m]
21750
0.252 (%)

35215 [W]
20 [m]
5869.17

1.5 (mm2)

s=

16 (mm2)

s=

120 (mm2)

U3=((100/*U)*P*l/s)%=
Verificare:
U=U1+U2+U3Uad
uad=8% pentru PT
U=
1.56 (%)

0.07 (%)

C2

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
1200
5.492

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 3FY1,5

Conductor din Cu:

Numar conductoare n=3


Ima =
17
[A]
[mm2]
SF=
1.5
SF=SN=

1.5

[mm2]

Sectiunea nulului de protectie


SPE=

1.5

[mm2]

<25 mm2

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

10

3FY1,5/IPEY 16

[A]

izolant
protejant
etans
masa plastica

C4

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
950
4.348

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 3FY1,5

Conductor din Cu:

Numar conductoare n=3


Ima =
17
[A]
[mm2]
SF=
1.5
[mm2]
SF=SN=
1.5
Sectiunea nulului de protectie
SPE=

1.5

<25 mm2

[mm2]

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

10

3FY1,5/IPEY 16

[A]

izolant
protejant
etans
masa plastica

C6

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
775
3.547

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 3FY1,5

Conductor din Cu:

Numar conductoare n=3


Ima =
17
[A]
[mm2]
SF=
1.5
[mm2]
SF=SN=
1.5
Sectiunea nulului de protectie
SPE=

1.5

<25 mm2

[mm2]

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

10

3FY1,5/IPEY 16

[A]

izolant
protejant
etans
masa plastica

Calculul circuitelor de priza


COS =
U=
=
Pi=
In=

Factor de putere
Tensiunea de alimentare
Randament
Circuit dezavantajat
Calculul curentului nominal

0.8
230
1
2000
10.9

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=2.5mm2

Conductor din Cu:

Numar conductoare n=3


Ima =
24
[A]
n=
3
[mm2]
sF=
2.5
[mm2]
SF=SN=SPE=
2.5
2 Alegerea tubului de protectie
[mm2]

SF=

2.5
n=
3
tub de protectie:
IPEY 20
3

Alegerea sigurantei automate(disjunctor)

Id>=In
Id=

16

3FY2,5/IPEY 20

[A]

<25 mm2

Calcul dimensionare coloane lumina si priza parter


L1l=
1950
L2l=
1975
L3l=
1875
U= 230

L1p=
L2p=
L3p=
np= 0.8

6000
6000
6000

TLP
Inj=sqrt(Inaj^2+Inrj^2)
Ina =Pilj/Uf + Pip/(Uf*np)
Ina1=
Ina2=
Ina3=

41.09 [A]
41.20 [A]
40.76 [A]

Inr=PiLj/Uf*tgf + Pipj/(Uf*np)*tgf
tg c=(Pl+Pp)\(Ql+Qp)
cosl=0.95 l=18.194tgl=
cosp=0.8 tgp=

0.32

0.75

Inr1=
Inr2=
Inr3=

27.17 [A]
27.20 [A]
27.07 [A]

In1=
In2=
In3=

49.26 [A]
49.37 [A]
48.93 [A]

Alegem

valoarea cea mai mare

1. Calea de curent:

Ima>=Inc=28.9 A
nca=4

49.37 [A] Ima=53 [A]

sn=spe=sF=16 mm2
2.Tub protectie

n=5
s=4

IPEY40

3.Siguranta fuzibila

If>=In
If amonte >= If max aval +2tr
If<= 3Ima
If max aval= 16A
4.Intrerupator parghie tripolar

alegem IPIII 63/50

.=>>If =50A
Is=63A
.=>> LF =50/63

Calcul dimensionare coloane lumina subsol


L1=
2214 [W]
L2=
2033 [W]
L3=
1968 [W]
U= 230
cos f =0.95

TLS
Alegem pentru calcul faza cea mai dezavantajata (L1):
Ina= Pil/U
Inr= Pil/U *tgf
InL = sqrt(Ina^2 + Inr^2)
InaL1 =
InrL1=

9.63 [A]
3.08 [A]

In L1 =

10.11 [A]

Curentul nominal al tabloului TLS:


Ic<=Imin
Imin =2.5mm
nca=4
Imax =18A .=>>
2.Tub protectie

5FY2.5
n=5
s=4

3. Siguranta fuzibila:
If >= In
If amonte > (Ifmax)aval + 2tr
.=>> If = 20A; Is =25A =>> LF 25/20
If <= 3 Ima
4.Intrerupator parghie tripolar

alegem IPIII 25/20

IPEY25

Calculul circuitelor de siguranta


CS1

COS =
U=
Pi=
In=

Corpuri de iluminat fluorescente


Tensiunea de alimentare
Puterea circuitului
Curent nominal

0.95
230
264
1.208

[V]
[W]
[A]

1 Determinarea sectiunii fazei


Sectiune minima SFmin=1.5mm2 2FY1,5

Conductor din Cu:

Numar conductoare n=2


Ima =
17
[A]
[mm2]
SF=
1.5
[mm2]
SF=SN=
1.5
Sectiunea nulului de protectie
SPE=

1.5

<25 mm2

[mm2]

2 Alegerea tubului de protectie


Tub de protectie:

IPEY 16

I
P
E
Y

izolant
protejant
etans
masa plastica

Alegerea sigurantei automate(disjunctor)

Ind>=In
Id=

[A]

2FY1,5/IPEY 12

If >= In
If amonte > (Ifmax)aval +
.=>> If = 20A; Is =25A =>>
If <= 3 Ima

4.Intrerupator parghie tr

alegem IPIII 25/20

Calcul dimensionare coloana tablou siguranta


L1=
L2=
L3=
U= 230

860 [W]
842 [W]
860 [W]
cos f =0.95

TSG
Alegem pentru calcul faza cea mai dezavantajata (L1):
Ina= Pil/U
Inr= Pil/U *tgf
InL = sqrt(Ina^2 + Inr^2)
InaL1 =
InrL1=

3.74 [A]
1.20 [A]

In L1 =

3.93 [A]

tg = 0.32

Curentul nominal al tabloului TLS:


Ic<=Imin
Imin =2.5mm
nca=4
Imax =18A .=>>
2.Tub protectie

5FY2.5
n=5
s=4

IPEY25

3. Siguranta fuzibila:
If >= In
If amonte > (Ifmax)aval + 2tr
.=>> If = 20A; Is =25A =>> LF 25/20
If <= 3 Ima
4.Intrerupator parghie tripolar

alegem IPIII 25/20

Circuite motor cu pornire directa ( Pi < 5,5kW)


Motor 1-pornire directa

Pi =
Ul =

0.75
400

[kW]
[V]

n=
h=

750
0.66

In = Pi / ( 1.733*Ul*cosj*h)

Curentul nominal

s = f(na, Ima)
na =
3
Ima =
14

Sectiune conductor

Tub protectie

cos j =
Ip/In(kp) =

[rot/m]

In =

2.61
[mm2]

s=

1.5

[A]

10

[A]

2.18
3.25

[A]
[A]

[A]
FY1.5

[A]

PEL 16

s=
nf =

1.5
4

[mm2]

Contactor

tip TCA 6 A

Inc =

Releu termic

tip TSA 10 A

InRT =
I s '=
Is =

If>=Ip/k
IF>=In=
IF<=IFRT=
IF<=IFC=
IF<=3*Ima=

Siguranta fuzibila

4.18
2.61
20
0
42

[A]
[A]
[A]
[A]
[A]

LF 25/10 A

Jp = Ip / sF

Verificarea sectiunii la densitatea de curent

Jp =
Jadm =

6.96
35

[A/mm2]
[A/mm2] - FY

Solutia
LF 25/10 A

TCA 6 A

TSA 10 A
4FY 1.5 / IPEY16

0.63
4

Circuite motor cu pornire directa ( Pi < 5,5kW)


Motor 2-pornire directa

Pi =
Ul =

1.5
400

[kW]
[V]

n=
h=

750
0.72

In = Pi / ( 1.733*Ul*cosj*h)

Curentul nominal

s = f(na, Ima)
na =
3
Ima =
14

Sectiune conductor

Tub protectie

cos j =
Ip/In(kp) =

[rot/m]

In =

4.49

s=

1.5

[mm2]

6
20

[A]
[A]

10

[A]

3.37
5.61
20

[A]
[A]
[A]

[A]
FY1.5

[A]

PEL 16

s=
nf =

1.5
4

[mm2]

Contactor

tip TCA 6 A

Inc =
IFTCA =

Releu termic

tip TSA 10 A

InRT =
I s '=
Is =

IFRT =
If>=Ip/k
IF>=In=
IF<=IFRT=
IF<=IFC=
IF<=3*Ima=

Siguranta fuzibila

8.082
4.49
20
20
42

[A]
[A]
[A]
[A]

LF 25/10 A

Jp = Ip / sF

Verificarea sectiunii la densitatea de curent

Jp =
Jadm =

13.47
35

[A/mm2]
[A/mm2] - FY

Solutia
LF 25/10 A

TCA 6 A

TSA 10 A
4FY 1.5 / IPEY16

0.67
4.5

Circuite motor cu pornire directa ( Pi < 5,5kW)


Motor 3-pornire directa

Pi =
Ul =

2.2
400

[kW]
[V]

n=
h=

750
0.75

In = Pi / ( 1.733*Ul*cosj*h)

Curentul nominal

s = f(na, Ima)
na =
3
Ima =
14

Sectiune conductor

Tub protectie

cos j =
Ip/In(kp) =

[rot/m]

In =

6.14

s=

1.5

[mm2]

10
20

[A]
[A]

10

[A]

4.61
7.675
20

[A]
[A]
[A]

[A]
FY1.5

[A]

PEL 16

s=
nf =

1.5
4

[mm2]

Contactor

tip TCA 10 A

Inc =
IFTCA =

Releu termic

tip TSA 10 A

InRT =
I s '=
Is =

IFRT =
If>=Ip/k
IF>=In=
IF<=IFRT=
IF<=IFC=
IF<=3*Ima=

Siguranta fuzibila

11.05
6.14
20
20
42

[A]
[A]
[A]
[A]
[A]

LF 25/16 A

Jp = Ip / sF

Verificarea sectiunii la densitatea de curent

Jp =
Jadm =

18.42
35

[A/mm2]
[A/mm2] - FY

Solutia
LF 25/16 A

TCA 10 A

TSA 10 A
4FY 1.5 / IPEY16

0.69
4.5

Circuite motor cu pornire directa ( Pi < 5,5kW)


Motor 4-pornire directa

Pi =
Ul =

4
400

[kW]
[V]

n=
h=

750
0.8

In = Pi / ( 1.733*Ul*cosj*h)

Curentul nominal

s = f(na, Ima)
na =
3
Ima =
20

Sectiune conductor

Tub protectie

In =

cos j =
Ip/In(kp) =

[rot/m]

10.04

s=

2.5

[mm2]

16
35

[A]
[A]

16

[A]

7.53
12.55
35

[A]
[A]
[A]

[A]
FY1.5

[A]

PEL 16

s=
nf =

2.5
4

[mm2]

Contactor

tip TCA 16 A

Inc =
IFTCA =

Releu termic

tip TSA 16 A

InRT =
I s '=
Is =

IFRT =
If>=Ip/k
IF>=In=
IF<=IFRT=
IF<=IFC=
IF<=3*Ima=

Siguranta fuzibila

20.08
10.04
20
35
60

[A]
[A]
[A]
[A]
[A]

LF 25/25 A

Jp = Ip / sF

Verificarea sectiunii la densitatea de curent

Jp =
Jadm =

20.08
35

[A/mm2]
[A/mm2] - FY

Solutia
LF 25/25 A

TCA 16 A

TSA 16 A
4FY 2.5 / IPEY16

0.72
5

~
Circuite motor cu pornire Y - D ( Pi > 5,5kW)
Motor 5

Curentul nominal

Pi =
Ul =

5.5
400

[kW]
[V]

n=
h=

In = Pi / ( 3*Ul*cosj*h)

In =
Ipdir =
IpY =
Infaza =

IpY = Ipdir /3
Infaza = In /1.73
Sectiune conductor

s = f(na, Ima)
na =
3
Ima =
20

750
0.815

s=

2.5

cos j =
Ip/In =

[rot/m]

13.27
72.99
24.33
7.67
[mm2]

0.735
5.5

[A]
[A]
[A]
[A]
FY

[A]
9.625

Tub protectie

d = f(s, nf)
s=
2.5
nf =
3

[mm2]

PEL 20

0.697273
Contactor

tip TCA 25 A

Inc =
IFC =

Releu termic

tip TSA 16 A

InRT =
I s '=
Is =

IFRT =

25
63

[A]
[A]

16

[A]

5.75
9.58
63

[A]
[A]
[A]
`

Siguranta fuzibila

LF 25 / 25 A
IF>=In=
13.27
IF<=IFRT=
63
IF<=IFC=
63
IF<=3*Ima=
60

[A]
[A]
[A]
[A]

IF>=IpY/2=

12.165 [A]

Jp = IpY / sF

Verificarea sectiunii la densitatea de curent

Jp =
Jadm =

9.73
35

[A/mm2]
[A/mm2] - FY

Solutia
TCA 25 A
TSA 16 A

3FY 2.5 / IPEY20

LF 25 / 25 A
3FY 2.5 /I PEY20

/ IPEY16

/ IPEY16

Pi L=
5800 (w)
Pi P=
18000 (w)
cos m=Pi L*cos L+PiP*cos P)/(Pi L+Pi P)=
sin m=
0.74
IN=
49.37 [A]
Ina=In*cos m=
41.30 [A]
Inr=In*sin m=
36.65 [A]
TLP:

TLS:

Pi=
cos =
sin =
IN=
10.11 (A)
Ina=In*cos m=
Inr=In*sin m=

cos L=
cos P=
0.84

0.95
0.8

6215 [W]
0.95
0.81
9.60 [A]
8.22 [A]

I na = cs* Ina k

I nr = cs* Inr k

I na =

I nr =

129.66

cs=0.6

114.88

In=(Ina+Inr)
IN =
173.24 [A]
2.Alegerea sectiunii conductorului
Conditia de stabilitate termica IN Ima
IN=
173.24 [A]
Ima=
315 [A]
k1=
0.92
k2=
0.68
k3=
1
Ima=
197.06 [A]
1. sF=

cf Tab 4.1.Indrumator (pag 13)


cf Tab 5.1.Indrumator (pag 15)
cf Tab 5.2.Indrumator (pag 16)
cf Tab 5.3.Indrumator (pag 17)

Pozare in pamant (manta PVC)


R term. specif.=120C cm/w
Nr.cabluri=4
tsol=20C

120 [mm2]

Aleg ACY AbY 4x120

(mm2)

3.Alegere Intreruptor automat


Conditia : IniIn
IN=
173.24 (A)
Ini=
250 (A)
Aleg USOL
4.Alegere Intreruptor parghie
In=
173.24 (A)
Ini=
630.00 (A)
Ir=
300 (A)

IP III 630 (A)


5.Siguranta fuzibila
Conditii:

cos =

0.7
cf Tab II.6.15 Manualul instalatorului editia 2010 (pag 230)

IFIn

IF=
200 (A)
IF3Ima

591.19 (A)

IF= (IF )max aval + 2 trepte

Se alege : IF=315(A)
6.Reductoare de curent
Inp1,1*In=
Ins=
Inp=

IF=
IF=

MPR 315/315 A

191 A
5A
250 A

7.Ampermetre
Alegem 3A (0..250 A)
8.Contor trifazat de energei activa
Alegem CAT 43
(4 conductoare active dezechilibrate)
9.Aparat de masura a tensiunii
Aleg CV 67
(6 pozitii active +1 pozitie repaus)
10.Voltmetrul
Aleg 1 V (0.500 V)

600 (A)
315 (A)

Pozare in pamant (manta PVC)


R term. specif.=120C cm/w
Nr.cabluri=4

editia 2010 (pag 230)

NR. Col

Pi [w]

1
2
3
4
5
6
7
8
9
10

6215
23800
23800
23800
23800
23800
29250
39400
34800
2562

P totala =

Repartitia pe faze
Alimentare
L1
L2
L3
2214
2033
1968
TLS
7950
7975
7875
TLP
7950
7975
7875
TL1
7950
7975
7875
TL2
7950
7975
7875
TL3
7950
7975
7875
TL4
9750
9750
9750
TF1
13133.33 13133.33 13133.33
TF2
11600
11600
11600
TF3
860
842
860
Tsig

231.23 [kW]

TABLOURI FORTA
I na = cs* Ina k

I nr = cs* Inr k

I na =

I nr =

140.09

cs=0.7

123.01

In=(Ina+Inr)
IN =
186.44 [A]

2.Alegerea sectiunii conductorului


Conditia de stabilitate termica IN Ima
IN=
186.44 [A]
Ima=
315 [A]
k1=
0.92
k2=
0.68
k3=
1
Ima=
197.06 [A]
1. sF=

cf Tab 4.1.Indrumator (pag 13)


cf Tab 5.1.Indrumator (pag 15)
cf Tab 5.2.Indrumator (pag 16)
cf Tab 5.3.Indrumator (pag 17)

Pozare in pamant (manta PVC)


R term. specif.=120C cm/w
Nr.cabluri=4
tsol=20C

120 [mm2]

Aleg ACY AbY 4x120

(mm2)

3.Alegere Intreruptor automat


Conditia : IniIn
IN=
186.44 (A)
Ini=
250 (A)
Aleg USOL
4.Alegere Intreruptor parghie
In=
186.44 (A)
Ini=
630.00 (A)
Ir=
300 (A)

IP III 630 (A)

cos =

0.7
cf Tab II.6.15 Manualul instalatorului editia 2010 (pag 230)

5.Siguranta fuzibila
Conditii:
IFIn

IF=
200 (A)
IF3Ima

591.19 (A)

IF= (IF )max aval + 2 trepte

Se alege : IF=315(A)
6.Reductoare de curent
Inp1,1*In=
Ins=
Inp=

IF=
IF=

MPR 315/315 A

205 A
5A
250 A

7.Ampermetre
Alegem 3A (0..250 A)
8.Contor trifazat de energei activa
Alegem CAT 43
(4 conductoare active dezechilibrate)
9.Aparat de masura a tensiunii
Aleg CV 67
(6 pozitii active +1 pozitie repaus)
10.Voltmetrul
Aleg 1 V (0.500 V)

600 (A)
315 (A)

Pozare in pamant (manta PVC)


R term. specif.=120C cm/w
Nr.cabluri=4

ATELIER MECANIC
TF 1
Motoare
Putere[Kw]
M1=
0.75
M2=
1.5
M3=
4
M4=
4
M5=
5.5
M6=
5.5
CP400=
6
Cp230=
2

In [A]
2.61
4.49
10.04
10.04
13.27
13.27
10.83
10.9

cos fi
0.63
0.67
0.72
0.72
0.735
0.735
0.8
0.8

sin fi
0.76
0.73
0.68
0.68
0.66
0.66
0.6
0.6

P totala=

29.25
kw

1. In = sqrt (Ina^2 + Inr^2)


Ina = Ini * cos fi
Ina =

56.00 [A]

Inr = Inr * sin fi


Inr=

49.47 [A]

In=

74.72 [A]

In<= Ima
4ca
.=>>Ima=76A
sF = 25mm
I max abs = sqrt( Imax abs a^2 + Imax abs r^2)
Imax abs a= Ina I + Ip cosf
Imax abs a=
109.65 [A]
I max abs =

Imax abs r= Inr I + Ip sinf


Imax abs r=
97.64 [A]

146.82 [A]

Jp = 5.87
2. Tub protectie
5ca
sF = 25mm .=>> IPEY 50
3. Intrerupator tripolar
IP III 200/100
Ir>=In
Ir = 100A
pagina230
.=>>> In = 200A

A/mm
4. Siguranta fuzibila
If >= In
If >= Imax abs/2=73.4
If <= 3*Ima
If >= If max aval + 2tr

.=>> LF100/80 A

ATELIER TAMPLARIE
TF 2
Motoare Putere[Kw]
M1=
2.2
M2=
2.2
M3=
5.5
M4=
5.5
M5=
4
M6=
4
2XCP400=
12
2XCp230=
4

In [A]
6.14
6.14
13.27
13.27
10.04
10.04
21.66
21.8

cos fi
0.69
0.69
0.735
0.735
0.72
0.72
0.8
0.8

sin fi
0.71
0.71
0.66
0.66
0.68
0.68
0.6
0.6

P totala=

1. In = sqrt (Ina^2 + Inr^2)


Ina = Ini * cos fi
Ina =

77.21 [A]

Inr = Ini * sin fi


Inr=

65.97 [A]

In=

101.55 [A]

In<= Ima
4ca
.=>>Ima=123A
sF = 50mm
I max abs = sqrt( Imax abs a^2 + Imax abs r^2)
Imax abs a= Ina I + Ip cosf
Imax abs a=
130.85 [A]
I max abs =

Imax abs r= Inr I + Ip sinf


Imax abs r=
114.14 [A]

173.63 [A]

Jp = 3.47

A/mm

2. Tub protectie
5ca
sF = 50mm .=>> IPEY 63
3. Intrerupator tripolar
IP III 350/175
Ir>=In
Ir = 175A
pagina230
.=>>> In = 350A

4. Siguranta fuzibila
If >= In
If >= Imax abs/2=86.5
If <= 3*Ima
.=>> LF100/100 A
If >= If max aval + 2tr

39.4
kw

STATIE POMPARE
TF 3
Motoare Putere[Kw]
CP 24 =
0.4
M1=
1.5
M2=
1.5
M3=
2.2
M4=
2.2
M5=
4
M6=
4
M7=
5.5
M8=
5.5
CP400=
6
Cp230=
2
1. In = sqrt (Ina^2 + Inr^2)
Ina = Ini * cos fi
Ina =

In [A]
2.17
4.49
4.49
6.14
6.14
10.04
10.04
13.27
13.27
10.83
10.09

cos fi
0.8
0.67
0.67
0.69
0.69
0.72
0.72
0.735
0.735
0.8
0.8

sin fi
0.6
0.73
0.73
0.71
0.71
0.68
0.68
0.66
0.66
0.6
0.6

P totala=

66.93 [A]

Inr = Ini * sin fi


Inr=

60.30 [A]

In=

90.08 [A]

In<= Ima
4ca
.=>>Ima=98A
sF = 35mm

Conductoare cupru pag. 8

I max abs = sqrt( Imax abs a^2 + Imax abs r^2)


Imax abs a= Ina I + Ip cosf
Imax abs a=
120.57 [A]
I max abs =

Imax abs r= Inr I + Ip sinf


Imax abs r=
108.47 [A]

162.18 [A]

Jp = 4.63

A/mm

2. Tub protectie
5ca
sF = 35mm .=>> IPEY 50
3. Intrerupator tripolar
IP III 200/100
Ir>=In
Ir = 100A
pagina230
.=>>> In = 200A

4. Siguranta fuzibila
If >= In
If >= Imax abs/2=81
If <= 3*Ima
If >= If max aval + 2tr

.=>> LF100/100 A

34.8
kw

Circuite priza joasa tensiune


Determinarea curentului nominal
In = Pi/(Uf * cosf)
230V

Pi =
Uf =
cosf =

400
230

In =

0.8

Pi =
Uf =
cosf =

400
24
0.8

In =

[W]
[V]

1.Determinarea sectiunii conductorului


Ima >=In

s=
na =
Ima =

2.5
2
24

[mm2]

2.5
3

[mm2]

[A]

2.Determinarea tubului de protectie

s=
nf =
PEL 12
3.Alegerea sigurantei fuzibile

[A]

Aleg sig. fuz LF 25/4

In = Pi/(Uf * cosf)

24V

2.17

[W]
[V]

LF25/25 A

FY

20.83

[A]

Calculul circuitelor de priza trifazat


Calculul curentului nominal

In=Pi/1,73*400*cos
cos =

0.8

Pi=

6000 [W]

In=

10.83815 [A]

1.Determinarea sectiunii fazei


Sectiune minima SFmin=2.5mm2
Ima =
n=
sF=
SF=SN=SPE=

20
3
2.5
2.5

2.Alegerea tubului de protectie

n=
sF =

5
2
2.5 mm

3.Alegerea sigurantei fuzibile

3 LF25/16

[A]
[mm2]
[mm2]
PEL16

IPEY 25

Calculul pierderii de tensiune pentru instalatia de forta

DU3%

DU2%

L3

L2

PT

DU1%

TGF

TF3

1.In regim nominal


Relatie de calcul: U 1,2,3=(100/*U)*(P*l/s)
Pi motor
In
cos
U
P abs
s
Kp
=

750
1500
2.61
4.49
0.63
0.67
400
400
1137.86 2081.74
1.5
1.5
4
4.5
54 (m/mm2)

2200
6.14
0.69
400
2931.73
1.5
4.5

4000
10.04
0.72
400
5002.33
2.5
5

5500
13.27
0.735
400
6749.39
2.5
5.5

a).circuit
TF 3:
U1=max( U1.1 ; U1.2 ; U1.3;U1.4)
U1.1=(100/*U)*(P*l/s)=
P1=3*U*In*cos=3*400*3,1*0,71=
L1=
4.9 (m)
s=
1.5 (mm2)

0.08 (%)

2081.74 (w)

U1.2=(100/*U)*(P*l/s)=
P2=3*U*In*cos=3*400*5,6*0,74=
L2=
7.8 (m)
s=
1.5 (mm2)

0.18 (%)

2931.73 (w)

U1.3=(100/*U)*(P*l/s)=
0.132 (%)

P3=3*U*In*cos=3*400*9,39*0,76=
5002.33 (w)
L3=
5.7 (m)
s=
2.5 (mm2)
U1.4=(100/*U)*(P*l/s)=
0.100 (%)

P4=3*U*In*cos=3*400*16,54*0,78=
6749.39 (w)
L4=
3.2 (m)
s=
2.5 (mm2)
U1=U1.3=

0.132 (%)

Pi motor=

1500 (w)

Pi motor=

2200 (w)

Pi motor=

4000 (w)

Pi motor=

5500 (w)

b).coloana secundara
Relatie de calcul:
PTF3=
26400
L=
26
s=
35
U 2=
0.227

U 2=(100/*U)*(P*l/s)
(w)
(m)
(mm2)
(%)

b).coloana generala
Relatie de calcul:
P=
231000
L=
100
s=
120
U 3=
2.228

U 2=(100/*U)*(P*l/s)
(w)
(m)
(mm2)
(%)

Relatie de calcul:
U%=UiUad%

U=
Uad% =

2.59
10

(%)
(%)

2.La pornire
Relatie de calcul:
TF 3:
U1=max( U1.1 ; U1.2 ; U1.3;U1.4)
U1.1=(100/*U)*(P*l/s)=
0.354 (%)
P1=3*U*Ipa=
9367.85 (w)
lpa=Ip*cos=
13.54 (A)
Ip=Kp*In=
20.205 (A)
l1=
s=

Pi motor=

4.9 (m)
1.5 (mm2)

U1.2=(100/*U)*(P*l/s)=
0.771 (%)
P2=3*U*Ipa=
12810.37 (w)
lpa=Ip*cos=
18.51 (A)
Ip=Kp*In=
27.63 (A)
l2=
7.8 (m)
s=
1.5 (mm2)

Pi motor=

U1.3=(100/*U)*(P*l/s)=
P3=3*U*Ipa=
25011.65 (w)
lpa=Ip*cos=
36.14 (A)
Ip=Kp*In=
50.2 (A)
l3=
5.7 (m)
s=
2.5 (mm2)

0.66 (%)

Pi motor=

U1.4=(100/*U)*(P*l/s)=
P4=3*U*Ipa=
37121.63 (w)
lpa=Ip*cos=
53.64 (A)
Ip=Kp*In=
72.985 (A)
l4=
3.2 (m)
s=
2.5 (mm2)

0.55 (%)

U1p=U1.2=

0.77 (%)

Pi motor=

1500 (w)

2200 (w)

4000 (w)

5500 (w)

Antemasuratoare pentru camera tehnica statie de hidrofor


S-a efectuat o lista care cuprinde materialele necesare pentru incaperea cu
destinatia statie de hidrofor pentru care s-a facut detaliul tabloului de forta aferent.
Nr. Crt
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Materiale
Conductor FY 1.5 mm2
Conductor FY 2.5 mm2
Tub protectie PEL 16mm2
Tub protectie PEL 20mm2
Tub protectie PEL 12mm2
Doze de aparat
Corp iluminat FIPRA 04-136
Motor 1.5kw
Motor 2.2kw
Motor 4kw
Motor 5.5kw
Platbanda OL Zn 25x4
Prize joasa tensiune
Prize monofazate
Prize trifazate
Cutie tablou electric

U.M
m
m
m
m
m
buc
buc
buc
buc
buc
buc
m
buc
buc
buc
buc

Cantitate
70.8
158.2
61.4
5.6
14
2
8
2
2
2
2
23.4
3
3
3
1

S-ar putea să vă placă și