Sunteți pe pagina 1din 4

28

Analiza evoluiei comunicaiei prin liniile


electrice de exterior
C. Male, V. Popa, Universitatea tefan cel Mare Suceava
AbstractIn this paper are analysed PLC (Power Line
Communications) protocols and their evolution until the present
day. The article presents aspects of IEEE 1901.2 standard,
which regulates communications in narrowband (3-500 kHz),
and the theoretical and practical results used in the protocols
developed by PRIME Alliance and ERDF. The paper highlights
the huge potential of power line communications on LV and
MV, and the issues raised by the existence of the electrical
transformers between them. Thus, a comparative study
involving the performances of PLC protocols was made. In
conclusions are presented elements that can influence the
implementation of an electrical meter reading system based on
PLC. Some issues that were not analysed until now regarding
the implementation of an electrical meter reading system on a
large scale are also presented.
Index TermsCSMA/CA, DBPSK, ERDF, OFDM, PLC,
PRIME, P1901.2

I. INTRODUCERE

omunicaiile prin reeaua electric pot fi descrise ca


un transfer de date care utilizeaz ca mediu fizic liniile
de alimentare cu energie electric. Acest tip de comunicaii
este cunoscut n literatura de specialitate sub abrevierea PLC
(Power Line Communications) [1]. Comunicaia PLC ar
putea utiliza ntreaga structur a unei reele electrice,
respectiv liniile de nalt tensiune (100 kV-400 kV) sau de
foarte nalt tensiune (>400 kV), liniile de medie tensiune (1
kV-100 kV) i liniile de joas tensiune (230V, 400V), care
alimenteaz consumatorii casnici i industriali prin
intermediul transformatoarelor din structura acesteia. Pn n
prezent s-au utilizat, ca mediu de comunicaie, doar liniile de
joas tensiune, existnd ns i soluii pentru liniile de medie
tensiune. Comunicaia prin reeaua electric este utilizat la
monitorizarea i administrarea contoarelor electrice, de ap i
de gaz, avnd drept competitori soluiile oferite de reelele
fr fir i cablate. Transferul de date este realizat aadar
folosind purttoare din banda de frecvene 3 kHz 500 kHz,
aceasta fiind adaptat conform prevederilor rilor sau
referinelor geografice unde comunicaia PLC este utilizat.
n prezenta lucrare sunt analizate aspecte care in de
comunicaia PLC, protocoalele de comunicaie i propunerile
pentru crearea noului standard IEEE 1901.2 ce va reglementa
comunicaia PLC n band ngust.
II. COMUNICAIA PLC
Comunicaia prin reeaua de alimentare cu energie

electric necesit respectarea unor reglementri emise de


instituii recunoscute pe plan mondial, precum CENELEC
(European Committee for Electrotechnical Standardization),
FCC (Federal Communications Commission), ARIB
(Association of Radio Industries & Businesses) sau EPRI
(Electric Power Research Institute)
i trebuie s
ndeplineasc anumite performane, pentru a asigura un
transfer de date eficient i pe distane ct mai mari. Cele mai
importante benzi n care are loc comunicaia sunt
reglementate astfel: n Europa - CENELEC banda A (3 kHz
95 kHz), n SUA FCC banda 10 kHz 490 kHz, n
Japonia ARIB banda 10 kHz 450 kHz i n China EPRI
n banda 3 kHz 90/500 kHz.
Cele mai importante standarde care reglementeaz
comunicaia PLC sunt:
EN 50065 - Transmisia semnalelor prin reelele electrice
de joas tensiune n banda de frecvene de la 3 kHz pn la
148,5 kHz. Partea 1: Cerine generale, benzi de frecvene i
perturbaii electromagnetice;
IEC/TS 61334-5-4 - Automatizarea distribuiei electrice
folosind liniile purttoare de tensiune;
IEEE P1901 - Comunicaia n band larg n reelele
electrice: controlul accesului la mediu i specificaii ale
nivelului fizic;
IEEE P1901.2 (n lucru) - standard pentru comunicaia n
band ngust pentru aplicaiile de reea electric
inteligent.
Pentru efectuarea comunicaiei i creterea performanelor
pot fi identificate dou generaii de tehnici de comunicaie n
evoluia utilizrii modulaiilor. Prima generaie a utilizat
modulaiile ASK (Amplitude Shift Keying), SFSK (Spread
Frequency Shift Keying) i BPSK (Binary Phase Shift
Keying), n paralel cu modulaia DCSK (Differential Code
Shift Keying) care se afl sub licena companiei Yitran.
Aceste tehnici de comunicaie utilizau tehnica de mprtiere
a spectrului DSSS (Direct-Sequence Spread Spectrum).
Utilizarea DSSS nu permitea obinerea unei viteze de
comunicaie mai mari de 9,6 kbps, de asemenea distana de
comunicaie era limitat la 400 metri [2]. De asemenea aceste
tehnici de comunicaie nu ofereau posibilitatea transferului
comunicaiei de pe linia de JT (joas tensiune) pe linia de MT
(medie tensiune) fr utilizarea echipamentelor de traversare
a transformatorului. A doua generaie utilizeaz modulaiile
bazate pe DBPSK (Differential Binary Phase Shift Keying) i

29
tehnica de mprtiere a spectrului OFDM (Orthogonal
Frequency Division Multiplexing), datorit crora se pot
obine viteze de pn la 140 kbps pe distane de ordinul
kilometrilor. Spre deosebire de prima generaie, aceasta
permite efectuarea comunicaiei ntre liniile de JT i MT prin
intermediul transformatorului electric.
La fel ca i la alte protocoale de comunicaie, avantajele i
dezavantajele PLC sunt direct corelate cu mediul utilizat
pentru fluxul de date, respectiv linia electric. Liniile
electrice nu au fost proiectate pentru a asigura un transfer de
date, astfel c nu asigur un nivel minim de protecie la
perturbaii electromagnetice i nici un factor constant de
propagare. Neadecvarea mediului electric la transferul de date
se concretizeaz prin atenuarea semnalului PLC n special pe
linia de JT (joas tensiune) i la traversarea
transformatorului. Perturbaiile electromagnetice se datoreaz
regimului de funcionare al echipamentelor electronice ce
induc n reeaua electric fluctuaii n regim aleator [1].
Formele sub care perturbaiile electromagnetice pot aprea n
reeaua electric sunt: zgomot impulsiv, zgomot alb Gaussian,
zgomot colorat, zgomot de sincronizare i zgomot de cvasisincronizare [3]. Unul dintre cele mai importante avantaje ale
reelei electrice este nivelul mare de acoperire, oriunde se face
alimentare cu energie electric de la o reea naional, ceea ce
ofer posibilitatea utilizrii liniilor electrice pentru transfer de
date fr instalarea unor medii noi de comunicaie, cu sau
fr fir. Alternativele utilizrii PLC sunt: GPRS, WiFi,
WiMAX, reeaua de telefonie fix, reeaua de internet cablat
.a.
Un alt factor care influeneaz comunicaia PLC este
cuplajul la linia electric, un element foarte important n
structura reelei PLC, ntruct influeneaz nivelul de
atenuare a semnalului transmis/recepionat. Cuplajul se
realizeaz n dou moduri: inductiv i capacitiv, cel de-al
doilea fiind cel mai utilizat [1].
O alt problem a comunicaiei PLC a fost inexistena unui
standard pn la nceputul anului 2011, cnd a fost publicat
standardul IEEE P1901 ce reglementeaz acest tip de
comunicaie [4], pentru comunicaia n band larg cu
utilizarea frecvenelor mai mici de 100 MHz. Un standard
care s trateze comunicaia n band ngust (3 500 kHz)
prin reeaua electric nu este nc publicat, IEEE P1901.2
aflndu-se n lucru [5].
III. PROTOCOALE DE COMUNICAIE
Comunicaia PLC a fost utilizat la transmiterea
semnalelor de control n cadrul reelelor electrice nc de la
nceputuri. n anii '50, comunicaia PLC era folosit
unidirecional pentru controlul iluminatului public. Mai
trziu, n anii '70, odat cu apariia protocolului X-10 i mai
apoi, n anii '90, cnd platforma LonWorks a permis
comunicaia bidirecional, comunicaia PLC a cunoscut o
dezvoltare treptat dar important ce a dus la apariia
tehnicilor de azi. Pentru a putea comunica prin reeaua

electric productorii au dezvoltat protocoale proprii,


neexistnd un standard internaional care s reglementeze
acest tip de transfer. Printre cele mai importante protocoale
PLC se regsesc: X-10, CEBus, Lontalk, KNX PL,
IEC61334, G3-PLC, PRIME. Principalele specificaii ale
acestor protocoale sunt:
1) X-10: modulaie ASK, frecven 120 kHz, vitez de
transfer 50 bps [6];
2) Intellon CEBus (EIA-600): modulaie ASK, tehnica acces
la mediu CSMA/CDCR (Carrier Sense Multiple
Access/Collision Detection and Collision Resolution),
vitez de transfer 10 kbps, tehnic de mprtiere a
spectrului: salt n frecven 200 kHz ->400 kHz ->100
kHz -> 200 kHz [1];
3) Lontalk (EIA-709/LonWorks): tehnica de acces la mediu
CSMA/CA, band de frecvene 125 kHz 140 kHz,
modulaie BPSK, vitez de transfer 5,5 kbps, dezvoltat de
Echelon Corp. [7];
4) KNX PL 110: band de frecvene 90 125 kHz, modulaie
SFSK, vitez de transfer 1,2 kbps[8];
5) IEC 61334: medii fizice utilizate: MT, JT; band de
frecvene: CENELEC A, modulaie SFSK, tehnic de
acces la mediu SS-FFH (Spread Spectrum-Fast
Frequency Hopping) [9].
Au urmat un alt tip de protocoale, aparinnd celei de a
doua generaii, utilizate n comunicaia PLC n band
ngust, reprezentate de propunerile G3-PLC i PRIME n
vederea realizrii standardului IEEE P1901.2. Acestea
utilizeaz banda CENELEC A (3 kHz 95 kHz) pentru
Europa, iar pentru SUA banda 3 500 kHz reglementat de
FCC, precum i alte aspecte reglementate de standardul
EN50065-1.
6) PLC-G3 este propunerea ERDF (Electricite Reseau
Distribution France) pentru noul standard IEEE P1901.2.
Modelul propus utilizeaz tehnica de mprtiere a
spectrului OFDM i tehnica de acces la mediu
CSMA\CA (Carrier Sense Multiple Access/Collision
Avoidance). n specificaii se propune utilizarea doar a
unei pri din banda CENELEC A, i anume intervalul
35,9 kHz 90,6 kHz. Astfel, PLC-G3 i propune s
asigure comunicaia prin mediile electrice de JT i MT.
Modulaiile utilizate sunt DBPSK (Differential Binary
Phase Shift Keying), DQPSK (Differential Quadrature
Phase Shift Keying) i Robust (codul este repetat de 4 ori
de un bloc specializat al transmitorului numit
Interleaver). Viteza de transfer poate ajunge pn la
34,7 kbps la utilizarea DQPSK; la 20,3 kbps n cazul
DBPSK i la 5,7 kbps pentru modul Robust. Prin
utilizarea acestor specificaii se dorete realizarea
comunicaiei dintre linia de MT i cea de JT fr
echipamente de traversare a transformatorului [10].
7) Compania Iberdrola [11] este coordonatorul proiectului
PoweRline Intelligent Metering Evolution (PRIME),
proiect dezvoltat mpreun cu organizaia PRIME

30
Alliance pentru formarea noului standard PLC. Modelul
propus are la baz specificaiile stivei din protocolul
IEEE Std. 802.16 i utilizeaz tehnica de mprtiere a
spectrului OFDM i tehnica de acces la mediu
CSMA\CA. n specificaii se propune utilizarea doar a
unei pri din banda CENELEC A, i anume intervalul
41,992 kHz 88,867 kHz, deoarece frecvenele sub 40
kHz prezint probleme severe n reelele electrice
europene cauzate de zgomot. Numrul de frecvene
purttoare utilizat este 97 i semnalul este modulat
DBPSK (Differential Binary Phase Shift Keying),
DQPSK (Differential Quaternary Phase Shift Keying) sau
D8PSK (Differential Eight-Phase Shift Keying).
Conform specificaiilor PRIME, comunicaia ar trebui s
se realizeze cu viteze de 47 kbps, 94 kbps i 141 kbps.
Scopul final al specificaiilor PRIME este cel de a asigura
interoperabilitatea comunicaiei PLC cu arhitectura unei
reele tipice de date, integrnd capabilitile unei
conexiuni la internet [12].
IV. STUDIU COMPARATIV AL PROPUNERILOR PENTRU
STANDARDUL IEEE P1901.2
IEEE P1901.2 este standardul care urmeaz a fi publicat
pentru aplicaiile cu comunicaii n band ngust, n
domeniul de frecvene 3 500 kHz, avnd drept suport
reeaua electric. Standardul IEEE P1901.2 va reglementa
comunicaia prin reeaua electric cu tensiuni de pn la 72
kV i prin transformatoarele de MT/JT. Standardul anun
viteze de comunicaie de pn la 500 kbps. Acest standard va
fi compatibil cu tehnologiile existente PRIME i G3-PLC,
care se bazeaz pe tehnica de multiplexare OFDM [13] .
A. Evaluarea performanelor

STANDARD

TABEL 1
STUDIU COMPARATIV AL PROTOCOALELOR PLC
TEHNOLOGI
TEHNOLOGI
E
BAND DE
E
MODULAIE

MPRTIER
E SPECTRU

FRECVENE

VITEZ
TRANSFER
(KBPS)

PLC-G3
PRIME
IEEE
P1901.2
ANSI/EIA
709.1,2
KNX
IEC61334

DBPSK
DBPSK

OFDM
OFDM

30-90,6 KHZ
42-89 KHZ

5,6-34,7
21,4-128,6

OFDM

9-500 KHZ

N LUCRU

BPSK

DSSS

86, 131 KHZ

3,6-5,4

SFSK
SFSK

DSSS
DSSS

125-140 KHZ
CENELEC A

1,2
2,4

X-10

ASK

DSSS

120 KHZ

0,5

Se poate observa n tabelul 1 evoluia de la modulaia n


amplitudine spre cea n frecven, pentru ca n final s fie
aleas o modulaie n faz (PSK), capabil s asigure o
rezisten sporit la interferene. De asemenea se poate
observa o cretere a vitezei de comunicaie, odat cu trecerea
de la OFDM la DSSS.
B. Rezultate teoretice i practice ale PRIME i PLC G3
Pn la aceast dat, n cadrul manifestrilor tiinifice
internaionale s-au prezentat rezultate referitoare la transferul

de date i simulri ale modelului PRIME. Astfel au fost


obinute n urma simulrii viteze de transfer de 21,4 kbps,
42,9 kbps i 64,3 kbps, utiliznd ca modalitate de corecie a
erorilor FEC (Forward Error Correction) de tip activ. La
dezactivarea FEC aceste viteze au fost duble. Modulaiile
utilizate sunt DBPSK, DQPSK, D8PSK. S-a mai observat i o
scdere a BER (Bit Error Rate) la utilizarea FEC cu pn la
25% [14]. ntr-un articol prezentat la ISPLC ediia 2010 [15],
reprezentanii companiei Maxim au prezentat rezultatele
obinute n urma simulrii modelului PLC G3, obinnd rate
de transfer de 5,5 kbps, 20 kbps i 34,1 kbps folosind
modulaiile ROBUST, DBPSK i DQPSK.

MEDIU
FIZIC

JT
MT
MT-JT
JT-MT

TABEL 2
REZULTATE TESTE PRACTICE CENELEC
VITEZ MAXIM
MODULAIE
DISTAN
OBINUT (KBPS)
DQPSK
200 M
17,2
DQPSK
6,4 KM
17,2
DBPSK
0,9+1,1 KM
8,64
ROBUST
1,1+0,9 KM
2,68

La testele de teren realizate ntr-o reea electric din


Europa n banda de frecvene 35,9 kHz 90,6 kHz, s-au
obinut rezultate promitoare, dup cum sunt prezentate n
tabelul 2. Astfel se poate observa c s-au obinut viteze de
comunicaie de 17,2 kbps la transferul pe linia de JT pe o
distan de 200 m cu utilizarea modulaiei DQPSK i de 17,2
kbps la transferul pe linia de MT pe o distan de 6,4 km cu
utilizarea modulaiei DQPSK. La transferul de pe linia de MT
pe linia de JT fr echipamente de traversare a
transformatorului s-a obinut viteza de transfer de 8,64 kbps,
cu utilizarea modulaiei DBPSK, iar la transferul de pe linia
de JT pe linia de MT fr echipamente de traversare a
transformatorului s-a obinut viteza de 2,68 kbps cu utilizarea
modului Robust. La transferul de pe linia de JT pe linia de
MT i invers au fost sesizate probleme de comunicaie, cea
mai mare performan fiind posibil doar pentru cazurile
prezentate n tabelul 2 [15].
Aceeai echip a companiei Maxim a prezentat la ediia
din 2011 a ISPLC teste practice [16], realizate ntr-o reea
electric din SUA, unde comunicaia este permis n banda
FCC cu frecvene cuprinse ntre 10 kHz i 490 kHz. Folosind
specificaiile din suplementul G3-FCC, au fost realizate teste
practice pentru cele trei cazuri de comunicaie, respectiv pe i
ntre liniile electrice de JT i MT. Conform acestor noi
specificaii, se pot atinge viteze teoretice de transfer de pn
la 208 kbps, utiliznd modulaia D8PSK.
TABEL 3
REZULTATE TESTE PRACTICE FCC

IE

DISTAN
(KM)

VITEZ
TRANSFER
(KBPS)

NR.
TRANSFORMAT
OARE
TRAVERSATE

DBPSK
D8PSK
D8PSK

8
8
1,5

35
>100
>50

1-2

MEDIU

MODULA

FIZIC

MT
MT
MT-JT

La testele de teren realizate ntr-o reea electric din SUA


n banda de frecvene 10 kHz 490 kHz, s-au obinut

31
rezultatele prezentate n tabelul 3. Conform tabelului 3 i
explicaiilor date de autori se poate observa c la transferul pe
linia de MT s-a obinut o rat de transfer de 35 kbps pe o
distan de 8 km la utilizarea DBPSK, iar la utilizarea
D8PSK rata de transfer a crescut la peste 100 kbps pe aceeai
distan. La transferul de pe linia de MT pe cea de JT pe o
distan de 1,5 km prin transformator, nu a fost observat
scderea acestor rate de transfer raportat la aceast distan.
S-a mai observat c n locurile unde sunt puine ramificaii
ale reelei i nivelul zgomotului este sczut, comunicaia PLC
poate fi realizat i prin dou transformatoare, fr ca viteza
de transfer s fie afectat major, aceasta avnd valori de peste
50 kbps [16].
V. CONCLUZII
n aceast lucrare s-au prezentat tehnicile de comunicaie
utilizate la transferul de date prin reeaua de alimentare cu
energie electric n band ngust. S-au prezentat rezultatele
obinute, n urma testrilor n teren i la simularea
comunicaiei PLC, conform specificaiilor PRIME i PLC-G3
n [14]-[16]. Testele fcute pentru a verifica performanele
viitoare ale standardului IEEE P1901.2 arat posibilitatea
comunicaiei pe liniile electrice de MT i JT la viteze
semnificative,
precum
i
posibilitatea
traversrii
transformatorului dar la o vitez de transfer redus. Testele
practice realizate pn n prezent arat posibilitatea
traversrii transformatorului folosind modul ROBUST,
prezentat n specificaiile PLC-G3, la o distan de 1 km de o
parte i de alta a transformatorului n ambele sensuri n banda
CENELEC. Pe de alt parte, arhitectura propus de
specificaiile PRIME este mai puin complex dect cea
propus de specificaiile PLC-G3. Cele dou specificaii
demonstreaz potenialul comunicaiei PLC prin liniile
electrice de exterior de MT i JT, precum i prin corpul
transformatorului, fapt care va duce desigur la mbuntirea
modului de administrare i control al contoarelor electrice sau
de alt gen.
Deoarece reeaua electric tinde s devin o reea de
comunicaie bidirecional de mare ntindere i complexitate,
vor aprea, fr ndoial, i unele dificulti n ceea ce
privete rutarea pachetelor prin nodurile acesteia, noduri
amplasate pe linia de MT ce asigur comunicaia cu diferite
segmente ale liniei de MT i cu liniile de JT. Pn n prezent,
acest aspect nu este analizat nc, dar va constitui un element
important n eficientizarea traficului i a consumului de
energie a echipamentelor ce se vor ocupa strict de asigurarea
comunicaiei.
Elementul definitor pentru reuita realizrii structurii de
comunicaie doar prin reeaua electric l constituie
transformatorul. Acesta produce o atenuare semnificativ a
semnalului de pn la 50 dB, iar gsirea unei soluii fiabile,
care s asigure comunicaia prin acesta pe distane ct mai
mari de o parte i de alta a lui, va reprezenta cheia reuitei
implementrii acestui sistem. Este important a se sublinia c,

pn la G3 i PRIME, traversarea transformatorului se fcea


cu echipamente speciale pentru comunicaia pe linia de MT
i cu soluii fr fir, care asigurau legtura dintre un centru de
control i un concentrator amplasat pe partea de JT a
transformatorului. Aceste standarde introduc o nou
posibilitate de transfer a datelor pe distane mari, asigurnd
trecerea semnalului PLC prin transformator.
Deoarece specificaiile PRIME i PLC-G3 ofer viteze de
transfer asemntoare, iar testele practice tind s certifice
aceste viteze, veridicitatea acestora va fi testat n momentul
implementrii ntr-un sistem real cu un numr reprezentativ
de contoare electrice la nivel metropolitan, unde necesitatea
comunicaiei cu contoarele, evitarea coliziunilor i utilizarea
multiplexrii vor fi cei mai importani factori n determinarea
fiabilitii soluiei oferite de comunicaia PLC.
MULUMIRI
Aceast lucrare a fost finanat prin FONDUL SOCIAL
EUROPEAN, proiect cofinanat din Fondul Social European,
prin Programul Operaional Sectorial Dezvoltarea Resurselor
Umane 2007-2013, Axa prioritar 1: Educaia i formarea
profesional n sprijinul creterii economice i dezvoltrii
societii bazate pe cunoatere, cu domeniul major de
intervenie 1.5: Programe doctorale i post-doctorale n
sprijinul cercetrii, proiectul Q-DOC- Creterea calitii
studiilor doctorale n tiine inginereti pentru sprijinirea
dezvoltrii societii bazate pe cunoatere, contract
POSDRU/107/1.5/S/78534, acord de parteneriat nr.
24266/30.09.2010, avnd ca beneficiar Universitatea Tehnic
din Cluj-Napoca i ca partener Universitatea tefan cel
Mare din Suceava.
REFERINE
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]

H. C. Ferreira, L. Lampe, Power Line communications Theory and


Applications for Narrowband and Broadband Communications over Power
Lines, Ed. Wiley, 2010.
Souha Souissi, Arwa Ben Dhia, OFDM modem design and implementation
for narrowband powerline communication, DTIM, 2010
Asier Llano, Alberto Sendin, Quasi-synchronous Noise Interference
Cancellation Techniques Applied in Low Voltage PLC, ISPLC, 2011
http://grouper.ieee.org/groups/1901/
http://standards.ieee.org/news/2011/p19012.html
http://www.eurox10.com/Content/x10information.htm
LonTalk Protocol Specification, v3, Echelon Corporation, 1994
http://www.weinzierl.de/download/references/KNX_Impl_E_2006_11_02.
pdf
Open Meter, WP2/T2.1.3, D2.1 parte 4, STATE-OF-THE-ART
TECHNOLOGIES & PROTOCOLS, 2009
Electricite Reseau Distribution France, PLC G3 Physical Layer
Specification, Project PLC G3 OFDM, 2009.
http://www.iberdrola.es/webibd/corporativa/iberdrola?IDPAG=ENWEBP
ROVEEBASDOCCONT
PRIME Alliance, Draft Standard for PoweRline Intelligent Metering
Evolution, Version 1.3E, 2010.
http://grouper.ieee.org/groups/1901/2/
J. M. Domingo, S. Alexandres, PRIME performance in power line
communication channel, ISPLC, 2011
K. Razazin, M. Umari, G3-PLC Specification for Powerline
Communications: Overview, System Simulation and Field Trial Results,
Internation Symposium on Power Line Communications, 2010.
Kaveh Razazian, Amir Kamalizad, G3-PLC Field Trials in U.S.
Distribution Grid: Initial Results and Requirements, ISPLC, 2011.

S-ar putea să vă placă și