Enabling the indicator to be ON after a 5 sec delay and OFF after a 3 sec delay by the
switch.
Topics Covered in this example is PLC Timer (ON Delay & OFF Delay).
http://plc-scada-dcs.blogspot.ro/2013/12/basic-plc-ladder-programming-training_7321.html#axzz5AhMuJKSo 1/3
3/24/2018 Basic PLC Ladder Programming Examples 8 | PLC, PLC LADDER, PLC EBOOK, PLC PROGRAMMING,
X1 – Start Switch.
Y1 – Output Indicator
T0 – 5 second Timer, 100 ms Time Base. (See K50 Preset Value for Timer)
T1 – 3 second Timer, 100 ms Time Base. (See K30 Preset Value for Timer)
· When X1 = OFF, T1 will start counting for 3 sec. When T1 reaches its set value,
the NC contact T1 will be activated while the NO contact T0 will remain OFF,
which makes the indicator Y1 to be OFF.
http://plc-scada-dcs.blogspot.ro/2013/12/basic-plc-ladder-programming-training_7321.html#axzz5AhMuJKSo 2/3
3/24/2018 Basic PLC Ladder Programming Examples 8 | PLC, PLC LADDER, PLC EBOOK, PLC PROGRAMMING,