Calcul fundatii hala 9 ( MARTUR )

Stalp S-A1

Eforturi la partea superioara a paharului din combinatia Nslsld

N Edc=1235.00 KN
V Edc=170.00 KN
M Edc =2710.00 KNm

L=6.50 m lungime fundatie


B=6.50 m latime fundatie
H=1.30 m inaltime fundatie
l S =1.00 mlungime stal
b S=1.00 m latime stalp
h placa =0.40 m grosime pardoseala
hteren =h pahar=1.30 m grosime teren peste bloc fundatie , respectiv inaltime pahar
H fundare =h placa +h pahar + H=0.40+1.30+1.30=3.00 m
γ beton =25.00 KN
γ pamant =19.00 KN
daN
Pconv =2.50
cm2

KN
G PLACA =L× B × h placa × γ beton =6.50 m× 6.50 m× 0.40 m×25.00 =423.00 KN
m3
KN
G TEREN =L× B × hteren × γ teren =6.50 m× 6.50 m×1.30 m ×19.00 3 =1044.00 KN
m
KN
G FUNDATIE=L × B× H × γ beton =6.50 m×6.50 m ×1.30 m× 25.00 3 =1374.00 KN
m

G TOTAL=G PLACA +GTEREN + G FUNDATIE =423.00+1044.00+1374.00=2841.00 KN

Eforturi la partea inferioara a fundatiei

N Edf =N Edc +G TOTAL=1235.00+2841.00=4076.00 KN


V Edf =V Edc=170.00 KN
M Edf =M Edc +V Edc × H fundare =2710.00 KNm+170.00 KN × 2.60 m=3152.00 KNm

NOTA:
Bratul de parghie a fost considerat de la partea superioara a paharului pana la partea
inferioara a blocului de fundatie 1.30m+1.30m=2.60m.

Limitarea excentricitatilor

2 2
(eL ) (eB ) 1
+ ≤
L 2
B 2
9

M BEdf 3152.00 KNm


e L= = =0.773 m
N Edf 4076.00 KN

M LEdf 2931.00 KNm


eB = = =0.773 m
N Edf 4076.00 KN

( 0.773 )2 ( 0.773 )2
+ =0.014+ 0.014=0.028<0.111
6.502 6.502
Calculul presiunilor

N Edf 6× M Edf
Pmax = +
L × B B × L2

4076.00× 10 2 6 ×3152.00 ×10 4 daN


Pmax = + 2
=0.964+ 0.688=1.652
650.00× 650.00 650.00× 650.00 cm2

N Edf 6 × M Edf
Pmin = +
L× B B × L2

4076.00× 10 2 6 ×3152.00 ×104 daN


Pmin = − 2
=0.964−0.688=0.276
650.00× 650.00 650.00 ×650.00 cm2

N Edf
Pefectiv =
L× B

4076.00× 10 2 daN
Pefectiv = =0.964
650.00× 650.00 cm2

( Pmax + Pmin ) 1.652+ 0.276 daN


Pmed = = =0.964
2 2 cm 2

( Pmax −P min ) ( L−lx )


P0=P min +
L

(1.652−0.276 ) ( 6.50−2.75 ) daN


P0=0.276+ =0.276+0.793=1.069
6.50 cm 2
Aria comprimata a bazei fundatiei

ACL=1.50 ( L−2× e L ) B=1.50 ( 6.50 m−2 × 0.719m ) 6.50 m=49.35 m 2


ATOTALA =6.50 m× 6.50 m=4 2.25 m 2

Armarea fundatiei

f CK =20 MPa valoarea caracteristica a betonului


γ C =1.50 Coeficientul ∂ de siguranta pentru beton

f CK 20.00
f CD = = =13.33 MPa
γ C 1.50

f CD =13.33 MPa valoarea de calcul a rezistentei betonului

f YK =500.00 MPa valoarea caracteristica a rezistentei la intindere a otelului B500

γ S =1.15 Coeficientul ∂de siguranta pentru otel

f YK 500.00
f YD = = =435.00 MPa
γS 1.15

d=H 0=H−cnom =1300−50=1250.00mm

Armarea longitudinala directie X

l 2X l 2X
[
M X =B P0
2
+ ( Pmax −P 0 )
3 ]
2.752 2.752
[
M X =6.50 107.00
2
+ ( 165.20−1 07.00 )
3 ]
=3583.45 KNm
B=6500.00 mm
MX 3 583.45 ×106
m X= 2
= =0.026 4
f CD × B × d 13.33 ×6500.00 ×1250.002

ω X =1−√ 1−2 m=1−√ 1−2 ×0.026 4=1−0. 973=0.0 27

f CD 13.33 2
A=ω X × B × d =0.0 27 × 6500.00× 1250.00 =6722.45mm
f YD 435.00

f CTM
A Smin=0.26 B ×d
f YK
2.20
A Smin=0.26 6500.00 ×1250.00=9295.00 mm2
500.00

n bare=4 2

∅ bare =20.00 mm

π × ∅bare 2 3.14 ×202 2


A Sefectiv=n bare =4 2 =13 188 .00 mm
4 4
A Sefectiv 13 188 .00
Pefectiv = = =0.1 6 %
d × B 1250 ×6500