CABLES TO BS 5467

CABLURI DE ENERGIE ARMATE CU


IZOLATIE DE XLPE SI MANTA DE PVC
CONFORM BS 5467

1. Conductor de cupru
2. Izolatie de XLPE
3. Manta interioara

TIP CABLU:
TENSIUNE NOMINALA:
STANDARD DE PRODUS:

XLPE/PVC/SWA/PVC
600 / 1000V
BS 5467

4. Sarma otel sau aluminiu


5. Manta exterioara de PVC

UTILIZARE
Cablu de energie pentru instalatii fixe, de interior sau exterior si pentru pozare
directa in pamant.

COD DE CULORI
NUMAR DE CONDUCTOARE
1
2
3
4
5
>5

XLPE

CULOARE
ALBASTRU SAU MARO
ALBASTRU MARO
MARO NEGRU GRI
ALBASTRU MARO NEGRU GRI
G/V ALBASTRU MARO NEGRU GRI
ALBE CU CIFRE NEGRE

NUMAR DE
CONDUCTOARE
x
SECTIUNEA
NOMINALA

No x mm2
1X50
1X70
1X95
1X120
1X150
1X185
1X240
1X300
1X400
1X500
1X630
1X800
1X1000
2X1.5
2X2.5
2X4
2X6
2X10
2X16
2X25
2X35
2X50
2X70
2X95
2X120
2X150
2X185
2X240
3X1.5
3X2.5
3X4
3X6
3X10
3X16
3X25
3X35
3X50
3X70
3X95
3X120
4X1.5
4X2.5
4X4
4X6
4X10
4X16
4X25
4X35
4X50

DIAMETRUL
EXTERIOR
(APROX)

GREUTATE
NETA
(APROX)

SUB
ARMARE

PESTE
ARMARE

EXTERIOR

mm

mm

mm

Kg/Km

12.2
14.1
15.8
17.5
19.7
21.9
24.6
27.1
30.9
34.6
38.9
44.1
48.8
7.6
8.6
9.7
10.8
12.4
14.8
14.7
16.8
18.5
21.1
23.9
26.9
29.8
33.5
38.3
8.3
9.2
10.3
11.6
13.2
16.1
17.0
19.1
21.6
25.0
28.5
31.6
9.1
10.1

14.7
16.6
18.3
20.0
22.9
25.1
27.8
30.3
34.9
38.6
42.9
49.12
53.8
9.4
10.4
11.5
12.6
14.2
17.3
17.2
20.0
21.7
24.3
27.9
30.9
33.8
38.5
43.3
10.1
11.0
12.1
13.4
15.7
18.6
20.2
22.3
24.8
28.2
32.5
35.6
10.9
11.9

17.7
19.6
21.5
23.2
26.3
28.7
31.4
34.1
38.9
42.8
47.3
53.9
58.8
12.0
13.6
14.7
15.9
18.0
20.0
20.4
23.4
25.3
28.1
31.9
35.1
38.2
43.3
48.3
13.0
14.1
15.3
16.6
19.5
21.6
23.6
25.9
28.4
32.0
36.7
40.0
14.0
15.0

800
940
1220
1490
1870
2290
2880
3520
4520
5680
7120
9220
11270
290
340
410
470
760
900
1000
1400
1800
2320
3160
3790
4500
5820
7220
310
380
450
700
820
1070
1550
1900
2360
3120
4310
5160
360
430

12.8
14.6
17.9
19.5
22.0
24.3

15.3
17.1
20.4
22.7
25.2
27.5

18.7
21.1
23.6
26.1
28.8
31.3

750
980
1300
1900
2300
2950

REZISTENTA
ELECTRICA
MAXIMA
LA 200C

SARCINA
ADMISIBILA

CADERE
DE
TENSIUNE

IN
AER

IN
PAMANT

/Km

mV/A/m

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
12.1
7.41
4.61
3.08
1,83
1,15
0,727
0,524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
12.1
7.41
4.61
3.08
1,83
1,15
0,727
0,524
0,387
0.268
0.193
0.153
12.1
7.41
4.61
3.08
1,83
1,15
0,727
0,524
0,387

231
295
362
420
483
555
654
745
851
963
1084
1178
1278
31
41
55
70
95
126
164
202
244
306
378
437
499
576
680
26
35
47
59
82
107
140
172
209
263
324
376
26
35
47
59
82
107
140
172
209

231
284
340
386
431
485
558
623
691
765
841
888
942
38
49
65
81
109
141
183
219
259
317
381
433
485
547
632
32
42
55
69
92
119
152
182
217
266
319
363
32
42
55
69
92
119
152
182
217

0.87
0.62
0.47
0.39
0.33
0.28
0.24
0.21
0.195
0.18
0.17
0.165
0.155
31
19
12
7.9
4.7
2.9
1.9
1.35
1.0
0.69
0.52
0.42
0.35
0.29
0.24
27
17
10
6.8
4.1
2.5
1.65
1.15
0.87
0.60
0.45
0.37
27
17
10
6.8
4.1
2.5
1.65
1.15
0.67

NUMAR DE
CONDUCTOARE
x
SECTIUNEA
NOMINALA
No x mm2

4X70
4X95
5X1.5
5X2.5
5X4
5X6
5X10
5X16
5X25
7X1.5
7X2.5
7X4
12X1.5
12X2.5
19X1.5
19X2.5
27X1.5
27X2.5
37X1.5
37X2.5
48X1.5

DIAMETRU
EXTERIOR
(APROX)

GREUTATE
NETA
(APPROX,)

REZISTENTA
ELECTRICA
MAXIMA
LA 200C

SARCINA
ADMISIBILA

SUB
ARMARE
mm

PESTE
ARMARE
mm

EXTERIOR
mm

Kg/Km

/Km

IN
AER
A

28.6
32.2
9.7
11.5
13.0
14.5
17.2
20.0
24.7
10.9
12.1
14.2
14.4
16.2
17.0
19.5
20.9
23.5
23.5
26.4
25.9

32.6
36.2
11.5
13.3
14.8
17.0
19.7
23.2
27.9
12.7
13.9
16.7
16.9
18.7
19.5
22.7
24.1
26.7
26.7
29.6
29.1

36.8
40.6
14.3
16.1
17.8
20.0
22.9
26.6
31.5
15.9
17.1
19.7
20.2
22.4
23.2
26.6
27.9
30.7
30.6
33.8
32.7

4230
5390
380
480
600
840
1130
1700
2320
440
560
700
730
950
940
1420
1320
1830
1650
2200
2000

0,268
0,193
12.1
7.41
4.61
3.08
1,83
1,15
0,727
12.1
7.41
4.61
12.1
7.41
12.1
7.41
12.1
7.41
12.1
7.41
12.1

263
324
26
35
47
59
82
107
140
16
21
29
12
17
11
15
9
12
8
11
7

CADERE
DE
TENSIUNE

IN
PAMANT
A

mV/A/m

266
319
32
42
55
69
92
119
152
20
26
34
15
20
13
18
11
15
10
13
9

0.60
0.45
27
17
10
6.8
4.1
2.5
1.65
27
17
10
27
17
27
17
27
17
27
17
27

Nota: Conductoarele pana la 16 mm sunt rotunde masive sau multifilare si compactizate


2
Conductoarele cu sectiunea de 25 mm sau mai mare sunt rotunde multifilare si compactizate cu exceptia cablurilor cu 2, 3 si 4 conductoare
la care conductoarele sunt de forma sector multifilar.

????????????????????????????

Nota : Incarcarile in curent sunt date


pentru o temperatura ambianta de
25oC, adancimea de pozare 0,5m,
temperatura a solului de 15oC , o
rezistivitate termica a solului de
1,2 Km/W si temperatura de max.
90oC a conductorului. Cablurile
monoconductoare sunt asezate in
formatie de trefla. Pentru alte conditii
se aplica factori de corectie.

Temperatura ambianta C
Factor de corectie

25
1,0

30
0,96

35
0,92

40
0,88

45
0,83

50
0,78

55
0,73

Temperatura solului C
Factor de corectie

10
1,03

15
1,0

20
0,97

25
0,93

30
0,89

35
0,89

40
0,82

Rezistivitatea termica a solului


Factor de corectie

0,9
1,06

1,0
1,04

1,2
1,0

1,5
0,92

2,0
0,82

2,5
0,74

3,0
0,68

Adancime de pozare m
Factor de corectie

0,5
1,00

0,6
0,98

0,8
0,96

1,0
0,94

1,25
0,92

1,50
0,91

1,75
0,89

RAZA MINIMA DE INDOIRE LA POZARE

8D

D = diametrul exterior al cablului