Abstract: The paper presents a methodology for computing the chlorine concentration decay in a water
distribution system over an extended period of time. A numerical model of the distribution network,
designed for about 10000 inhabitants, is created in EPANET 2.0. The variable water demand over a 24 h
period is implemented via flow pattern statements. Both hydraulic and water quality analysis are
performed in order to obtain the time dependent flow within the network, as well as the time dependent
pressure and chlorine concentration at each node. A constant concentration of chlorine is injected
upstream, at the reservoir; then, the downstream residual is computed. Reactions occurring in the bulk
flow are modelled with a first-order decay law, where the instantaneous rate of reaction is assumed to
depend upon the chlorine concentration.
1. INTRODUCERE
Clorina este cel mai utilizat dezinfectant n sistemele de alimentare cu ap. Este
utilizat att ca dezinfectant primar n staiile de tratare a apei (pentru distrugerea
bacteriilor i viruilor), ct i pentru a preveni dezvoltarea micro-organismelor n
sistemele de distribuie a apei. Proprietile apei potabile furnizate de instalaiile
centrale sau de sursele locale de alimentare cu ap, de rezervoarele de nmagazinare,
precum i proprietile apei folosite pentru apa cald menajer, sunt reglementate prin
standard [1]. Concentraia clorului rezidual liber n apa dezinfectat prin clorinare are
valori admise ntre minim 0,05 mg/l (la capetele terminale ale conductelor de
distribuie) i maxim 0,5 mg/l.
1
. l. dr. ing., Catedra de Hidraulic i Protecia Mediului, Universitatea Tehnic de Construcii Bucureti
2
conf. dr. ing., Catedra de Hidraulic i Maini Hidraulice, Universitatea Politehnica Bucureti
3
ing., Secia Ing. Mediului, Divizia Energie-Mediu, Institutul de Studii i Proiectri Energetice, Bucureti
4
student an V, Specializarea Ingineria Mediului, Facultatea de Energetic, Univ. Politehnica Bucureti
n general, un sistem de alimentare cu ap urban cuprinde construciile i
instalaiile pentru captarea apei, tratarea apei, transportul apei ctre un rezervor (uzual
prin pompare), nmagazinarea apei n rezervor, (opional) repomparea apei i distribuia
apei. n prezenta lucrare, se va considera o schem simplificat a sistemului de
alimentare cu ap a unei localiti cu circa 10000 de locuitori, anume o schem format
dintr-un rezervor de nmagazinare, de unde apa ajunge gravitaional n reeaua mixt de
distribuie din aval: o reea inelar, prevzut cu ramificaii n anumite noduri.
Rezervorul (deschis la presiunea atmosferic, plasat n apropierea localitii la cota
178,5 m) asigur nmagazinarea cantitii de ap necesare pentru a realiza compensarea
orar a debitelor de consum cu cele de alimentare i pentru a asigura rezerva de ap
pentru stingerea incediilor. Reeaua de distribuie cuprinde toate conductele, instalaiile
i construciile accesorii, care au rolul de a transporta apa de la rezervor pn la cel mai
deprtat punct de consum, asigurnd debitele de ap la presiunea de serviciu necesar.
Schema sistemului de alimentare cu ap considerat (figura 1) este realizat cu
ajutorul interfeei grafice a programului EPANET 2.0, program elaborat de ctre
Agenia de Protecie a Mediului din SUA, destinat efecturii calculelor hidraulice i de
analiz a calitii apei n sisteme de distribuie complexe [2].
Fig. 3 Variaia debitului n reea la ora 13.00, dup 61 de ore de la nceperea simulrii
(a)
(b)
Fig. 6 Variaia debitului (a) i presiunii (b) n nodul 45, plasat n partea de sus a reelei
Pentru a simula transportul de clorin prin reea, se efectueaz urmtoarele
modificri: se selecteaz opiuni de calitate i la tipul parametrului se introduce
cuvntul clorin; la opiuni reacii, pentru coeficientul global n nucleul de curgere
se introduce valoarea 1.0 (aceasta indic rata cu care clorina se va descompune datorit
reaciilor de-a lungul timpului; aceasta rat se va aplica la toate conductele din reea); la
nodul corespunztor rezervorului se introduce valoarea 0.45 pentru calitatea iniial
( C 0 = 0,45 va fi concentraia de clorin, n mg/l, care intr n mod continuu n reea).
este ordinul reaciei. n prezenta lucrare se va considera o lege de reacie de ordinul nti
(n = 1) i un coeficient al ratei de reacie K b = 1 . Ali autori [5] indic o valoare
este concentraia n amonte la momentul iniial t = 0 , iar C este concetraia din aval la
momentul de timp t > 0 . Coeficientul K b este determinat ca pant a dreptei obinute (n
general, acesta crete cu temperatura apei). Se poate scrie astfel legea de descretere a
concentraiei de clorin:
(1) C = C 0 e Kb t ,
(a)
(b)
Fig. 7 Variaia concentraiei de clorin (mg/l) n reea dup (a) 3 ore i (b) 13 ore de la nceperea simulrii
Fig. 8 Variaia concentraiei de clorin (mg/l) n reea dup 72 de ore de la nceperea simulrii
3. CONCLUZII
Fig. 9 Variaia concentraiei de clorin (mg/l) n reea dup 24 de ore de la nceperea simulrii, pentru
cazul n care debitul la consumatori este meninut constant n timp
4. BIBLIOGRAFIE