REGULI INTERNE DE PROIECTARE

ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI INTERNE DE PROIECTARE

POPP & ASOCIAŢII

ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Conform:

P100-1:2011
CR 2-1-1.1:2005
CR 2-1-1.1:2011
SREN 1992-1-1:2004
SREN 1992-1-2:2004
SREN 1998-1:2004
NE 012/2-2010

00 12.10.2011 IONEL BONTEA


REVIZIE DATA MODIFICĂRI SEMNĂTURA EMITENTULUI
REVISION DATE MODIFICATIONS THE ISSUER'S SIGNATURE

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 1 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI PRIVIND ALEGEREA STRATULUI DE ACOPERIRE CU BETON

Acoperirea minimă din condiţii de durabilitate:

cnom=cmin+Δcdev= cmin+10mm
cmin=max(cmin,b; cmin,dur; 10mm)

Pentru cazurile obișnuite (clasa structurală S4 – durata de viaţă 50 ani), cnom (mm):

Păci Stâlpi, pereţi și grinzi Fundaţii


(XC1) – Φ+10 mm (XC1) (XC2/XC3)
Turnate pe Fără cofraj
beton de lateral
6≤Φ≤10 12≤Φ≤14 16≤Φ≤20 Φsw≤14 Φsw>14 egalizare, (turnat în
cu cofraj contact cu
lateral solul)
20 25 30 25 30 40 75

Notă: Dacă dimensiunea nominală a celei mai mari granule este mai mare de 32 mm, cmin,b
se majorează cu 5 mm.
Pentru alte clase de expunere – consultă anexa 1.

Acoperirea minimă din condiţii de rezistenţă la foc:

În general, necesitatea determinării altor acoperiri faţă de cele calculate mai sus, intervine în
situaţiile în care elementele separă spaţii cu funcţiuni diferite (ex.: casa scărilor, lifturi, shafturi,
parcaje). Acopririle de mai jos sunt raportte la etrier sau bară orizontală pereţi.

Tip
Stâlpi Pereţi Grinzi Plăci
element
RF 120<RF≤180 120<RF≤180 240 180 180
120 RF≤120 RF≤120 RF≤90
(minute) (subsol) (scări, shaft) (subsol) (cota0) (cota0)
cRf cnom 45 cnom 35 45 cnom 40 cnom 40

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 2 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI PRIVIND DISTANŢELE MINIME ÎNTRE ARMĂTURI

Dimensiunea maximă a Grinzi – o distanţă la partea


Caz general
agregatului ≥ 16mm superioară
min.(Φmax, 20 mm) min.(Φmax, dg+5 mm) 50 mm

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 3 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI PRIVIND LUNGIMILE DE ANCORARE ALE ARMĂTURILOR

Lungimi de ancorare pentru armăturile din grinzi şi stâlpi


care contribuie la preluarea forţelor seismice

Lungimile se aleg din tabele de mai jos și reprezintă 1,20xlbd+5dBl.


Pentru stâlpii întinşi din fundaţii, lungimea de ancoraj se măreşte
cu 25%.

Conditii de aderenta bune (bare la partea inferioara) si otel beton S500 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45 C40/50 C45/55  C50/60 
6  51  43  38  32  30  27  24  23  21 
8  68  58  51  43  39  36  32  30  28 
10  85  72  63  54  49  45  40  38  35 
12  101  86  76  64  59  54  48  45  42 
14  118  101  89  75  68  63  56  53  49 
16  135  115  101  86  78  72  64  60  56 
18  152  129  114  96  88  80  72  67  63 
20  169  144  126  107  97  89  80  75  70 
22  185  158  139  118  107  98  88  82  77 
25  211  179  158  134  122  112  100  94  88 
28  236  201  177  150  136  125  112  105  98 
32  270  230  202  171  156  143  128  120  112 
   85 Ø  72 Ø  63 Ø  54 Ø  49 Ø  45 Ø  40 Ø  38 Ø  35 Ø 

Conditii de aderenta bune (bare la partea inferioara) si otel beton PC52 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45 C40/50 C45/55  C50/60 
6  36  31  27  23  21  20  18  17  16 
8  48  41  36  31  28  26  24  22  21 
10  60  51  45  39  35  33  29  28  26 
12  72  62  54  46  42  39  35  33  31 
14  84  72  63  54  49  46  41  39  36 
16  96  82  72  62  56  52  47  44  42 
18  108  92  81  69  63  58  53  49  47 
20  120  102  90  77  70  65  58  55  52 
22  131  113  99  85  77  71  64  60  57 
25  149  128  113  96  88  81  73  69  65 
28  167  143  126  108  98  91  82  77  72 
32  191  163  144  123  112  104  93  88  83 
60 Ø  51 Ø  45 Ø  39 Ø  35 Ø  33 Ø  29 Ø  28 Ø  26 Ø 

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 4 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

Conditii de aderenta nesatisfacatoare (bare la partea superioara) si otel beton S500 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45  C40/50  C45/55  C50/60 
6  72  60  53  45  41  37  33  31  29 
8  95  80  71  60  54  49  44  41  39 
10  119  100  88  75  68  62  55  51  48 
12  143  120  106  89  81  74  66  62  58 
14  166  140  123  104  94  86  77  72  68 
16  190  160  141  119  108  98  88  82  77 
18  214  180  158  134  121  111  98  92  87 
20  237  200  176  149  135  123  109  102  96 
22  261  220  193  163  148  135  120  113  106 
25  297  249  219  186  168  154  137  128  120 
28  332  279  246  208  188  172  153  143  135 
32  380  319  281  237  215  196  175  164  154 
119 Ø  100 Ø  88 Ø  75 Ø  68 Ø  62 Ø  55 Ø  51 Ø  48 Ø 

Conditii de aderenta nesatisfacatoare (bare la partea superioara) si otel beton PC52 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45  C40/50  C45/55  C50/60 
6  50  43  38  32  29  27  24  23  21 
8  67  57  50  43  39  36  32  30  28 
10  84  71  62  53  48  44  40  37  35 
12  100  85  75  64  58  53  47  45  42 
14  117  99  87  74  67  62  55  52  49 
16  134  113  100  85  77  71  63  59  56 
18  150  127  112  95  87  79  71  67  63 
20  167  141  124  106  96  88  79  74  70 
22  184  155  137  116  106  97  86  81  77 
25  209  176  155  132  120  110  98  92  87 
28  234  197  174  148  134  123  110  103  97 
32  267  225  199  169  154  141  126  118  111 
84 Ø  71 Ø  62 Ø  53 Ø  48 Ø  44 Ø  40 Ø  37 Ø  35 Ø 

Lungimea minimă a ciocurilor (incluzând zona dreaptă de 10Ф și zona de racordare) pentru
barele longitudinale și etrieri este de:
- 13Ф pentru bare cu Ф≤16
- 15Ф pentru bare cu Ф>16

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 5 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

Lungimi de ancorare pentru armăturile din grinzi şi stâlpi care nu contribuie la


preluarea forţelor seismice şi armăturile din pereţi și planşee

Lungimile se aleg din tabele de mai jos. Pentru detalii privind


stabilirea lungimilor de ancorare se va consulta Anexa 2.

Conditii de aderenta bune (bare la partea inferioara) si otel beton S500 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45 C40/50 C45/55  C50/60 
6  40  34  29  25  22  20  18  17  15 
8  53  45  39  33  29  27  24  22  20 
10  66  56  49  41  37  33  29  27  25 
12  80  67  58  49  44  40  35  33  30 
14  93  78  68  57  51  46  41  38  35 
16  106  89  78  65  58  53  47  43  40 
18  119  100  87  73  66  60  53  49  45 
20  132  111  97  81  73  66  58  54  50 
22  145  123  107  89  80  73  64  60  55 
25  165  139  121  101  91  83  73  68  63 
28  185  156  136  113  102  92  81  76  70 
32  211  178  155  129  116  106  93  86  80 
   66 Ø  56 Ø  49 Ø  41 Ø  37 Ø  33 Ø  29 Ø  27 Ø  25 Ø 

Conditii de aderenta bune (bare la partea inferioara) si otel beton PC52 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45 C40/50 C45/55  C50/60 
6  28  23  20  17  15  14  12  12  11 
8  37  31  27  23  20  19  16  15  14 
10  46  39  34  28  25  23  20  19  18 
12  55  46  40  34  30  28  24  23  21 
14  64  54  47  39  35  32  28  26  25 
16  73  62  54  45  40  37  32  30  28 
18  82  69  60  50  45  41  36  34  32 
20  91  77  67  56  50  46  40  38  35 
22  100  85  74  62  55  50  44  41  38 
25  114  96  84  70  63  57  50  47  44 
28  128  108  94  78  70  64  56  52  49 
32  146  123  107  89  80  73  64  60  56 
46 Ø  39 Ø  34 Ø  28 Ø  25 Ø  23 Ø  20 Ø  19 Ø  18 Ø 

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 6 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

Conditii de aderenta nesatisfacatoare (bare la partea superioara) si otel beton S500 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45  C40/50  C45/55  C50/60 
6  57  48  42  35  32  29  25  23  22 
8  76  64  56  47  42  38  33  31  29 
10  95  79  69  58  52  47  42  39  36 
12  114  95  83  70  63  57  50  46  43 
14  133  111  97  81  73  66  58  54  51 
16  152  127  111  93  83  75  66  62  58 
18  171  142  124  104  94  85  75  69  65 
20  190  158  138  116  104  94  83  77  72 
22  209  174  152  127  114  104  91  85  79 
25  237  198  173  144  130  118  103  96  90 
28  265  221  193  162  145  132  116  108  101 
32  303  253  221  185  166  150  132  123  115 
95 Ø  79 Ø  69 Ø  58 Ø  52 Ø  47 Ø  42 Ø  39 Ø  36 Ø 

Conditii de aderenta nesatisfacatoare (bare la partea superioara) si otel beton PC52 
Ø  C12/16  C16/20  C20/25  C25/30 C30/37 C35/45  C40/50  C45/55  C50/60 
6  40  33  29  24  22  20  18  16  15 
8  53  44  38  32  29  26  23  22  20 
10  66  55  48  40  36  33  29  27  25 
12  79  66  57  48  43  39  35  32  30 
14  92  77  67  56  50  46  40  37  35 
16  105  87  76  64  58  52  46  43  40 
18  118  98  86  72  65  59  52  48  45 
20  131  109  95  80  72  65  57  53  50 
22  144  120  105  88  79  72  63  59  55 
25  164  136  119  100  90  81  72  67  62 
28  183  153  133  112  100  91  80  74  70 
32  209  174  152  127  115  104  91  85  79 
66 Ø  55 Ø  48 Ø  40 Ø  36 Ø  33 Ø  29 Ø  27 Ø  25 Ø 

Lungimea minimă a ciocurilor (incluzând zona dreaptă de 5Ф și zona de racordare) pentru


barele longitudinale și etrieri este de:
- 8Ф pentru bare cu Ф≤16
- 10Ф pentru bare cu Ф>16

Notă: pentru pereţi se vor utiliza lungimile indicate mai sus, majorate cu 30% în zona A
pentru clasa de ductilitate DCH şi cu 20% în zona A pentru clasa de ductilitate DCM

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 7 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

Lungimi de ancorare pentru armăturile din grinzi de cuplare a pereţilor

Pentru barele drepte, lungimile de ancorare sunt indicate în figura de mai jos

Pentru diametre mai mari de Ø22mm, se recomandă ca barele să se îndoaie la capete şi se


sudează.

În cazul carcaselor înclinate, lungimile de ancorare sunt indicate în figura de mai jos

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 8 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI PRIVIND BORDAREA GOLURILOR DIN PEREŢI ŞI PLANŞEE

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 9 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI PRIVIND LUNGIMILE DE ÎNNĂDIRE ALE ARMĂTURILOR

Calculul lungimii de înnădire pentru grinzi, stâlpi, planşee

În toate situaţiile de proiectare se va considera l0=1,5 x lbd (această relaţie din SR EN


1992-1-1:2004 corespunde cazurilor curente de proiectare, în care sunt suprapuse în aceeaşi
secţiune mai mult de 50% din armaturi).

Prevederi constructive
Se limitează la 4Φ sau 50mm distanţa liberă între barele suprapuse; dacă această condiţie
nu este îndeplinită se măreşte ls cu o valoare egală cu distanţa liberă între bare (SREN 1992-1-
1:2004);
Suprapunerile vecine sunt distanţate longitudinal cu cel puţin 0,3xl0 (SREN 1992-1-1:2004);
În cazul suprapunerilor vecine se respectă o distanţă liberă minimă de 2Φ sau 20mm între
barele adiacente (SREN 1992-1-1:2004);

Distanţa s dintre armăturile transversale în zona de suprapunere nu trebuie să depăsească:


s=min{h/4;100} (SREN 1998-1-1:2004);

Excepţie fac armăturile de moment negativ ale grinzilor suprapuse în câmp, a căror lungime
de înnădire se stabileşte în funcţie de efortul de compresiune dezvoltat în acestea. Simplificat se pot
folosi lungimile de suprapunere din tabelul de mai jos, considerate acoperitoare pentru situaţiile
curente de proiectare (PREVEDERE INTERNĂ):

BST500S PC52
<C30/37 45Φ 30Φ
≥C30/37 30Φ 30Φ

Aria necesară a armăturii transversale în zona de suprapunere se calculează (conf. SREN):


Ast=s x (dbl/50) x (fyld/fyvd) ; dbl - diametrul barelor suprapuse

În zonele critice de la baza stâlpilor se vor respecta următoarele prevederi:


• este interzisă înnădirea barelor prin suprapunere în zona potenţial plastică ;
• dacă înnădirea barelor în zona critică de la baza elementului nu poate fi evitată prin
prevederea unor carcase continue, se va proceda la înnădirea barelor folosind
dispozitive mecanice cu agrement tehnic.
• Se va specifica acest lucru în memoriile tehnice şi caietele de sarcini

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 10 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

Calculul lungimii de înnădire pentru pereţi

În zonele critice de la baza pereţilor se vor respecta următoarele prevederi:

• este interzisă înnădirea prin suprapunere a barelor de la extremităţile peretelui


în zona potenţial plastică (zona A) ;
• dacă înnădirea barelor în zona critică de la baza elementului nu poate fi evitată prin
prevederea unor carcase continue, se va proceda la:
¾ înnădirea barelor folosind dispozitive mecanice agrementate (prima opţiune);
¾ sudură “cap-la-cap” (cochilie, eclise) ;
• Se va specifica acest lucru în memoriile tehnice şi caietele de sarcini

Înnădirea armăturilor verticale din inima peretelui în zona A, se poate realiza prin
suprapunere cu respectarea prevederilor din P100/2011. Pentru cazurile curente se pot admite
lungimile de suprapunere din tabelul de mai jos.

Pentru armătura verticală din inima peretelui din zona B lungimile de suprapunere se reduc
cu 10Φ;

Armăturile orizontale se înnădesc, de regulă, prin petrecere pe lungimi de cel putin 50db la
construcţii proiectate pentru DCH şi 40db la construcţii proiectate pentru DCM ;

Barele verticale se vor executa fără cârlig ;

Calculul lungimii de înnădire în cazul utilizării plaselor sudate

In cazul utilizării plaselor sudate lungimile de înnădire se iau egale cu un ochi + 50mm≥40Φ;

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 11 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL
REGULI INTERNE DE PROIECTARE
ELEMENTE DE STRUCTURĂ DIN BETON ARMAT

Project No. Apr. / App. Cod / Code Fază / Phase Corp / Block Tip / Type Nr. / No. Rev. / Rev. Data / Date

--------/--.--.---- RIP 01 00 12.10.2011

REGULI PRIVIND ALEGEREA DISTANŢIERILOR SUB FORMĂ DE CAPRE

Reguli de alegere a tipului şi numărului de capre din condiţii de rezistenţă:

Planşeu Planşeu Radier Radier


Tip de planşeu
hpl ≤20cm 40cm≤hpl ≤20cm hrad ≤60cm 60cm≤hrad ≤100cm
Număr minim
de capre din
2Ф8/m2 PC52 2Ф10/m2 PC52 3Ф12/m2 PC52 3Ф14/m2 PC52
condiţii de
rezistenţă

Reguli specificate în norme:


Conform indicativ NE 012/2-2010, Art. 8.3.7: dispunerea distanţierilor va fi de
cel puţin 1 buc/m2 în câmpul reţelelor la plăci şi pereţi, şi de cel puţin 4 buc/m2 la reţelele
plăcilor în consolă.

Reguli de reprezentare:
Conform caietului de sarcini desen, la reprezentarea pe planuri a distanţierilor sub formă de
capre se va ţine seama de următoarele :

• Pentru fiecare zonă de planşeu de o anumită


înălţime se va utiliza un singur tip de capră
• La definirea suprafeţelor pe care se montează
capre nu se vor lua în calcul "amprenta"
pereţilor, grinzilor şi carcaselor care fac parte
din armarea planşeului
• H capră = H placă-acop inf-acop super-Ø1
inf-Ø3 sup-Ø4 sup
• a = 1.5xpas armătură inferioară (rând 1)
• b = 1.5xpas armătură superioară (rând 3)

Creat de / Created by Popp & Asociatii/PA_RIP_01_r00_12.10.2011 - 12 / 12 -


© Nici o parte din acest document nu poate fi copiată, modificată sau multiplicată fără acordul scris al POPP & ASOCIAŢII SRL
© No part of this document may be copied, changed or multiplied without the written permission of POPP & ASOCIAŢII SRL