Analiza schemei electrice monofilare a unei statii electrice reale

Statia Jugureanu 110/20 kV

Student: Moise Iulian Marian


Profesor coordonator: Gabriela Nicoleta Sava

-NUMELE STATIEI: JUGUREANU 110/20 KV


-DESTINETIE (CONSUMATORI)
-110 KV-COLTEA,POGOANELE,FAUREI
DUDESTI
-20 KV-CIRESU, RUSETU,PADINA,PETROL
-SCHEMA(110 KV)- UN SISTEM DE BARE
COLECTOARE

LOCALIZARE: -JUGUREANU, JUDETUL


BRAILA

DESTINATIE

-110KV; 20KV

SCHEMA ELECTRICA MONOFILARA 110


KV

SE IDENTIFICA:

Un sistem de bare colectoare


6 celule-1 celula de masura
-4 cellule de linie
-1celula de sistem

SEPARATOR DE BARE-SEPARATOR TRIPOLAR DE


EXTERIOR

INTRERUPTOR:IUP-CU ULEI
PUTIN

SEPARATOR DE LINII

DESCARCATOR-SIEMENS

TRANSFORMATOR DE CURENT PENTRU MONTAJ IN INSTALATIILE


EXTERIOARE TIP SUPPORT CU IZOLATIE IN ULEI (CESU)

*TRANSFORMATOR DE TENSIUNE PENTRU MONTAJ EXTERIOR


MONOPOLAR CU IZOLATIE IN ULEI(TEMU)

TRANSFORMATOR DE PUTERE
10MVA

BARE COLECTOARE

CELULA DE LINIE- POGOANELE


*SEPARATOR DE BARESTE(110KV;1600A)
*INTRERUPTOR ULEI
PUTIN(110KV;1250A;
3000MVA)
*TRANSFORMATOR DE CURENT(110KV)
*SEPARATOR DE LINII
*SEPARATOR LEGARE LA PAMANT
*TRANSFORMATOR DE TENSIUNE

FOAIE DE MANEVRA

Tema :aducerea in functiune a celulei de linie(pogoanele) din starea operative


rezerva calda

Scop: alimentarea cu energie a liniei (Pogoanele)

SOI: celula de linie Pogoanele se afla in rezerva calda, intreruptorul (iup) este brosat

Se verifica SOI

Se conecteaza intreruptorul iup cu ccordul dispecerului

Se verifica pozitia conectat a intreruptorului

Se verifica prezenta tesiunii pe linia Pogoanele

Se confirma catre dispeceratul energetic teritorial starea in funciune a liniei


Pogoanele

IMBUNATATIRI

Schimbarea transformatorului de putere(este foarte


vechi)
Inlocuirea intreruptoarelor

DEZAVANTAJE

Prezenta unei singure bare colectoare-daca apare o


defectiune pe bara, se intrerupe alimentarea cu energie
peste tot.