Sunteți pe pagina 1din 41

GHID DE MONTARE SI ACTIVARE

INTRERUPTOR DE MANEVRA - SEPARATOR


(IMS) PE STALPI August 2008
Ed. II 1/41

GHID DE MONTARE SI ACTIVARE

INTRERUPTOR DE MANEVRA - SEPARATOR (IMS)

PE STALPI

Modificari ed. 2: s-a inserat instructiunea pentru instalare UP si activare in Telecontrol (cap. 6)

P.Stoian
2 As. Tehnica L.Guida A.Pieropan G. Oprea/M. Stirbulescu 29.08.2008
L.Albano
Ed. Unitatea Redactat Verificat Aprobat Data

Copyright SC Enel Distributie Banat SA şi SC Enel Distributie Dobrogea SA toate drepturile rezervate.
Reproducerea si/sau cedarea, totala sau partiala, sub orice forma, pe orice fel de suport si cu orice mijloc sunt
interzise fara aprobarea scrisa a SC Enel Distributie Banat SA şi SC Enel Distributie Dobrogea SA.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 2/41

CUPRINS

1. INTRODUCERE 3

2. SPECIFICATII TEHNICE DETALIATE 3

3. LUCRARI PREMERGATOARE INSTALARII IMS 3

4. GRESELI DE MONTAJ 3

5. ALIMENTAREA UP MONTAT PE STALP SI PUNEREA LA PAMANT A UP 14

6. INSTRUCTIUNE DE ACTIVARE UP – IMS IN TELECONTROL 16

7. DESCRIERE RGDAT PENTRU LEA MT 29

8. INSTALAREA RGDAT IN UP 39
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 3/41

1. INTRODUCERE
Scopul acestui ghid de montaj este acela de a clarifica toate aspectele tehnice legate de montarea
corecta pe stalpi a IMS si UP echipate cu RGDAT OUTDOOR. In prezent telecontrolul retelelor de MT
este realizat prin intermediul sistemului STM si a unitatilor periferice (UP) insa prin echiparea IMS
montate pe stalpi cu dispozitive detectoare de defect (RGDAT) se va putea realiza si automatizarea
LEA MT. In prezent telecontrolul LEA MT prin intermediul IMS+UP+STM permite operatorului de
distributie sectionarea liniei de la distanta dar nu ofera acestuia informatii despre tronsonul defect.
Prin instalarea dispozitivelor RGDAT si in LEA MT se va putea realiza comanda de la distanta a IMS
operatorul avand la dispozitie si informatii despre tronsonul de linie defect lucru ce va imbunatatii
timpii de reactie ai operatorului de distributie scazand astfel timpii de nealimentare.
Dat fiind faptul ca instalarea dispozitivelor RGDAT in LEA MT apartinand ENEL BANAT si
DOBROGEA este experimentala se va avea in vedere ca la montarea IMS sa se rezerve un spatiu
suficient pentru montarea ulterioara a consolei de sustinere pentru senzorii de curent si tensiune
necesari transmiterii de semnale catre RGDAT.

2. SPECIFICATII TEHNICE DETALIATE


Specificatiile tehnice si documentatiile tehnice unificate de referinta ce trebuie respectate sunt:

• DX1222 Unitate periferica (UP) pentru telecontrol si pentru supravegherea IMS


pe stalpi
• DY1059 Dispozitiv de detectare a defectelor, directional si minimal de tensiune (RGDAT).
• DK4517 Selectarea tronsonului de retea defect cu ajutorul UP
• DS3170 Specificatie tehnica pentru consola si izolatori de sustinere pentru
senzorii de curent si tensiune.

3. LUCRARI PREMERGATOARE INSTALARII IMS


După ce s-a constituit lista IMS din LEA MT ce urmează a fi telecontrolate este necesara verificarea
urmatoarelor aspecte:
• Stalpul pe care va fi montat IMS sa nu aibă o inaltime mai mica de 10,3 m de la nivelul solului.
• IMS se va instala astfel incat distanta de la bornele IMS la sol sa fie de 7 m atat in zonele cu
circulatie frecventa cat si in zonele cu circulaţie redusa.
• Consola si izolatoarele de sustinere necesare pentru fixarea senzorilor trebuie sa fie conforme
cu specificaţiile DS 3170 .

4. GRESELI DE MONTAJ
Pentru o functionare optima a IMS si a sistemului de telecontrol in ansamblu se impune eliminarea
tuturor erorilor ce pot sa apara la faza de montaj a echipamentelor aferente telecontrolului in LEA MT.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 4/41

Observatii referitoare la modul de montaj a IMS pe stalpul 1716/46 din LEA 20 kV


Musicescu(Timisoara)

In aceasta imagine se
EROARE
observa o montare
incorecta a conductorului
LEA 20 kV la bornele IMS.

Conductorul LEA 20 kV este din OlAl


preizolat si este conectat prin
intermediul unui papuc de aluminiu la o
placuta de cupru fixata de borna IMS.
EROARE

In schimb in cazul acestui montaj efectuat la Tulcea legătura la bornele IMS este realizata prin
intermediul unei plăcute de aluminiu.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 5/41

EROARE

Conductorul LEA 20 kV este din Ol Al


preizolat si este racordat prin intermediul unui
papuc de aluminiu la o placuta de aluminiu
fixata de borna IMS.

Aceste greseli de montaj au fost generate de interpretarea gresita a textului din cadrul
„GHID DE MONTARE SEPARATOARE TELECOMANDATE PE STALPI DE BETON
DOBROGEA”:
a. In vederea racordarii bornelor separatorului telecomandat la clemele de
racord in retea este necesar sa fie prevazute placute Cu – Al, deoarece bornele
separatorului sunt de Φ 16 iar papucii de racord ai cablurilor au gaura Φ 12.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 6/41

Pentru realizarea unei conexiuni corecte intre conductorul LEA MT si bornele IMS este recomandata
folosirea unor papuci bimetalici (aluminiu/cupru) ca si cei prezentati in
figura fig. 1 si 2.

fig.1

fig.2
.

Sau ca si alternativa la folosirea unui papuc bimetalic se va putea folosii o plăcuta bimetalica.

In imaginea de mai jos este vizibila o conexiune la bornele IMS efectuata corect prin intermediul unui
papuc bimetalic Cu – Al.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 7/41

CORECT

Montaj corect cu
utilizarea papucilor
bimetalici Cu - Al.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 8/41

La montarea conductoarelor flexibile pentru legare la priza de pamant nu trebuie sa existe „rezerva”
sub forma de spire, fixate pe stalp (in cazul in care conductorul este prea lung nu trebuie lasat ca si
rezerva sub forma de spire).

Nu se vor lasa rezerve sub


forma de spire fixate pe stalp.
EROARE
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 9/41

Conductorul de legare la
priza de pamant a celor doua
seturi de descarcatoare nu
se vor fixa pe stalp cu spire
metalice si de asemena
EROARE traseul conductorului nu
trebuie sa traverseze prin
interiorul unor posibile spire
in scurcircuit .

Montajul corect se va realiza prin utilizarea unor fasete din nylon rezistente la UV.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 10/41

Nu se vor utiliza platbande ruginite pentru legarea la pamant a confectiilor metalice de pe stalp.

Nu se vor utiliza platbande ruginite.

Conductorul flexibil si
platbandele de coborare la
priza de pamant NU trebuie
sa obstructioneze numarul
de identificare a stalpului,
numar ce trebuie sa fie
inscris pe o placuta
indicatoare.

Se va avea in vedere ca identificarea stalpului sa fie foarte clara.


Se recomanda folosirea unor plăcute indicatoare montate la o distanta suficienta fata de sol si in
locuri cu vizibilitate sporita.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 11/41

Din aceasta imagine se poate observa ca transformatorul de tensiune (TT) pentru alimentarea la 230
V a UP nu a fost alimentat asa cum este specificat in “GUIDA TECNICA AL TELECONTROLLO
DELLE CABINE SECONDARIE E IMS DA PALO NELLE RETI MT” pag. 35/36

ATENTIE!
Cablul de alimentare la 230 V ca a UP-ului provenit de la secundarul transformatorului de tensiune
(TT) montat pe IMS nu poate fi scos de sub tensiune decat prin deconectarea liniei de MT, drept
urmare in faza de montare se va executa legarea pe partea de 20 kV a bornelor transformatorului la
doua faze ale LEA MT dinspre sursa, iar secundarul transformatorului de tensiune se va lasa in gol.
In faza de montare a UP este necesara scoaterea de sub tensiune a LEA MT pe timpul efectuarii
legaturilor si a probelor de functionare.

Conectarea TT
intre doua faze
ale LEA MT
spre sursa.

Se va executa o legatura
scurta de la borna de
legare la pamant a
carcasei IMS la platbanda
generala de legare la priza
de pamant.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 12/41

A) Cutie
B) Suport de susţinere al IMS
C) Punct de prindere pe stâlp
D) Comanda
E) Izolatori de trecere
F) Punct de prindere pentru montaj(ridicare)
Dimensiuni de fixare TT G) Semnalizator al stării(inchis/deschis)
H) Suport de prindere pentru TT
I) Borna de legare la priza de pamant
L) Valva SF6
M) Valva suprapresiune
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 13/41

IMS inchis

LEGENDA
N) Stâlp
O) Comanda manuala
P) Blocaj mecanic in poziţia deschis cu posibilitatea de încuiere cu lacăt
Q) Pârghie de acţionare
R) Tija acţionare manuala
S) Plăcuta de identificare
T) Borne de legare la priza de pamant a carcaselor
V)Cablu pentru comanda motorizata a IMS(comanda vine de la UP)
Z) Transformator de tensiune de servicii proprii(TT ce alimentează UP)
Y) Cablu de legătura de la TT la UP
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 14/41

5. ALIMENTAREA UP MONTAT PE STALP SI PUNEREA LA


PAMANT A UP
Circuitul de alimentare al UP este in schema normala de functionare alimentat la 230V ca, in caz de
avarie alimentarea fiind preluata pentru o perioada de timp de cele doua baterii cu care UP este
echipat. Alimentarea UP se face de la transformatorul de tensiune bifazat 20 kV / 0,23 kV (DY550),
fixat pe partea superioara a IMS pe un suport special si conectat la LEA MT prin doua conductoare
astfel încât acesta sa fie alimentat si cu separatorul deschis.
Secundarul TT se va lega la bornele de alimentare ale UP iar in faza de montaj din motive de
securitate se va solicita scoaterea de sub tensiune a LEA MT.
UP se va lega la pamant printr-un surub de legare la pamant dispus in interiorul carcasei
aproape de intrarea cablurilor in carcasa UP. Stalpul pe care se va monta UP-ul va trebuii sa
aiba o instalatie de legare la priza de pamant corect executata, la aceasta legandu-se si UP-ul.

Borna de faza, la
aceasta se conecteaza
conductorul de faza care
alimenteaza UP

Borna de nul, la aceasta


se conecteaza
conductorul de nul care
alimenteaza UP

Borna pentru
legarea la priza de
pamant
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 15/41

Atentie!
Exista transformatoare de tensiune (TT) prevazute cu doua tensiuni de alimentare MT
(15kV si 20 KV); in acest caz legaturile pentru tensiune 20 KV se executa conform figurii
de mai jos.

FAZA

NUL
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 16/41

6. INSTRUCTIUNE DE ACTIVARE UP – IMS IN TELECONTROL


GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 17/41

La montarea IMS trebuie sa se tina cont de instructiunile de montare ale


producatorului de IMS.
Urmatoarele instructiuni se refera la producatorul “OEMB”.
In cazul utilizarii IMS de la producatorul “ELETTROMECCANICA ADRIATICA” se va
consulta manualul de utilizare (Man_IMS_EA.pdf), vezi figura pag.18.

IMS OEMB blocat in pozitie DESCHIS


GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 18/41

Particulare IMS
Elettromeccanica Adriatica

Microintrerupator
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 19/41

IMS OEMB
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 20/41

SCHEMA IMS OEMB DESCHIS FARA BLOCAJ - LACAT

OEMB: schema IMS Aperto senza Blocco/ lucchetto


GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 21/41

Cleme interne ale comenzii IMS OEMB


GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 22/41

CLEME LEGATURA IMS SI UP

Clema IMS
Morsettiera IMS
OEMB
OEMB

+M -M 2 6 4 3 1 5
Clema UP
Morsettiera COL G.P.
UP-COL

Morsettiera unificata
CLEMA UNIFICATA spec.
SI CLEMA DX1222
UP COL G.P.

+M
Morsettiera UP COL

-M
Morsettiera IMS

2 Clema UP COL G.P.


6
4
3
1
5
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 23/41

INSTRUCTIUNE OPERATIVA
pentru punere in functiune si activare Telecontrol

• Instalare dulap UP si antena pentru GSM , vezi foto pag 23-24.


• Sistematizare cabluri comanda IMS si alimentare TT cu tub de protectie rezistent la UV (daca e
prevazut in proiect) , lasand o rezerva in partea de sus, ca in foto pag 25, fixare de-a lungul
stalpului cu fasete resistente la UV.
Legatura echipotentiala si la pamant a cutiei interne utilizand un surub de trecere din exterior.
• Pentru IMS “OEMB”: Verificarea miscarii mecanice deschis/inchis a IMS si functiunea Blocaj
electric inseriat numai in pozitie DESCHIS, conform instructiunilor constructorului, pag. 17 si
posibilitatea verificarii functiunii Blocaj electric cu aparat de masura , in Ω pe firele 4 si 5/6 ale
cablului de comanda IMS releu inchis si deschis IMS; Rezistenta cca 172 Ω cu S4 inchis (ca in
schema OEMB pag 19).
• Pentru IMS “ELETTROMECCANICA ADRIATICA”:Verificarea blocajului electric se face cu un
Tester direct pe contactul de actionare mecanica (inchis in pozitie normala, deschis in pozitie
de blocare, vezi pagina 18.

Dupa cele scrise mai sus si efectuate cu rezultat pozitiv sunt necesare urmatoarele:
• Legarea firelor de comanda IMS ca in schema de la pag.21.
• Verificarea pozitiei comutatorului de la sursa de alimentare, care este in pozitia 230V si legare
cablu care coboara de la TT.
• Legarea cablului de la baterie si strangerea suruburilor si acoprirea cu capace aflate in dotarea
bateriei.
• Alimentare UP si IMS (motorul) inchizand intrerupatorii.
• Pozitionare comutator local si efectuare probe de Deschidere si Inchidere cu butoanele UP,
verificand coreuta miscare a IMS.
• Verificarea indicatiei corecte a pozitiei DESCHIS indicata pe IMS (verde) si pe UP semnal
luminos (led verde)
• Verificarea indicatiei corecte a pozitiei INCHIS indicata pe IMS (rosu) si pe UP semnal luminos
(led rosu)
• Verificarea functionarii Modul GSM, intensitatea campului cu aparatul “Apiterm”.
• Pozitionare comutator in Telecontrol si efectuare probe de la Centrul Operativ (conexiune
GSM, alarma spontana, in particular semnalul de “lipsa tensiune c.a., pozitie corecta si
concordata D/I al IMS, probe de comanda D si I”
• Terminate toate probele se pune in functiune linia, se verifica tensiunea de alimentare 230V
c.a. pe UP si semnalul de revenire tensiune c.a. cu Centrul Operativ.
• Se aplica eticheta indicatoare adeziva pe UP si a 2 placuta a IMS aflata in dotare.

Inainte de inchiderea UP, se pozitioneaza termostatul rezistentei de incalzire la 18°C si se inchid


usile UP verificand cu Centrul Operativ semnalul de “usa inchisa”, iar in acest moment IMS si UP
sunt gata pentru exploatare.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 24/41

UP instalata pe stalp in b.a.c. la Deva: in particular fixare cu banda in OL inox cu scula tip “Band-it”.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 25/41

Cabluri de comanda si alimentare UP

In particular
intrare cabluri
in UP.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 26/41

Legatura la pamant si echipotentiala a dulapului UP.

Gaurire cu burghiu
de 6mm si
introducere surub
de otel inoxidabil.

Legare cablu, ca in
foto, cu surub din
otel inoxidabil.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 27/41

Cablu de
comanda trece
prin mijlocul tijei
de comanda.

Rezerva de
cabluri de
comanda si
alimentare
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 28/41

La terminarea lucrarii se aplica etichetele adezive pe dulapul UP si ce-a de a


doua eticheta metalica aflata in dotarea IMS, vezi foto din pag. 25 si 26.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 29/41

7. DESCRIERE RGDAT PENTRU LEA MT


Dispozitivul de protectie RGDAT este compus din:
• Unitatea de control: O unitate de procesare a semnalelor care consta intr-o cutie metalica in
care se introduc toate cablurile ce transmit diferite semnale de la echipamentele Fig 1

• Transformatoarele de curent si tensiune: Sunt trei senzori de curent si tensiune pentru MT


care masoara curentul si tensiunea de pe fiecare faza si se montează cu senzorul de curent inseriat
pe calea de curent intre borna descărcătorului cu ZnO si borna IMS in cazul montajului pe stalp, Fig 2

• Cablu de comanda (cablu de conexiune la UP): Un cablu cu mufe de conexiune pentru


interfatarea conexiunii la distanta prin care se receptioneaza semnalul de alimentare si se transmit
diverse semnalizări.

• Consola de sustinere cu izolatoare compozite conform DS 3170: Consola pentru susţinerea


senzorilor de curent si tensiune.

7.1. Instalare RGDAT pentru LEA MT ( RGDAT OUTDOOR)

Dispozitivul RGDAT OUTDOOR se va putea monta doar pe acei stalpi care au o inaltime de la sol de
minim 10,3 m si care la montare respecta toate distantele de siguranta si de functionare.

Instalarea consolei de sustinere cu izolatori pentru transformatroarele de curent si


tensiune

Se vor respecta cotele indicate in desenul urmator.


GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 30/41

Vedere din fata


GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 31/41

Vedere laterala
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 32/41

Consola de sustinere din otel zincat


Consola de sustinere a izolatorilor
suport din otel zincat
Izolator
Izolatorsiliconic pentru
de sustinere 24 tip
24 kV kV
compozit

Senzorii de curent si tensiune se vor fixa pe consola de susţinere prin intermediul a 3 izolatori de
susţinere 24kV, tip compozit.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 33/41

După fixarea pe stâlp a consolei de susţinere echipata cu senzorii de curent si tensiune se vor fixa de
consola si de stâlp tuburile de protecţie aferente cablurilor secundare ale senzorilor de curent si
tensiune.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 34/41

Elemente care nu sunt


incluse in kit-ul de livrare al
consolei de sustinere.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 35/41

Pentru o buna functionare a senzorilor de curent si tensiune acestia trebuie sa fie alimentati printr-o
bucata de cablu rectilinie cu o lungime de minim 500 mm din centrul senzorului de curent spre fiecare
din capetele acestuia.

500 mm
500 mm

Cele trei tuburi de protecţie in care sunt introduse cablurile provenite de la secundarele senzorilor de
curent si tensiune se vor introduce intr-o cutie de conexiuni din care va iesi un singur cablu protejat cu
tub din PVC si care se va conecta la RGDAT situat in cutia UP.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 36/41

Tub de protectie
Racord pentru tubulatura de
protecţie
Capac cu garnitura
Cutie de derivaţie Cod:LEGR386573+LEGR865

Cutie de derivaţie
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 37/41

Cablul de conectare la UP si si cablul de conectare la secundarele senzorilor de curent si tensiune


sunt de tipul 3 x 0.25 mmp, siliconice si cu o lungime de 9,5 m.
Aceste cabluri NU SE VOR TAIA NICIODATA deoarece sistemul este calibrat pentru o lungime a
cablurilor de 9,5 m.

Instalarea dispozitivelor de telecontrol pentru posturile de transformare zidite cu


alimentare din LEA

Precizările făcute la punctele anterioare sunt valabile si pentru acest tip de instalaţii.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 38/41
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 39/41

8. INSTALAREA RGDAT INTR- UN UP


RGDAT se va fixa pe usa interioara a UP unde a fost montata si structura de fixare pentru acesta.
Conductorul de legare la pamant a RGDAT se va lega la cutia de cleme M10 fiind dimensionat
corespunzator.
In acest moment se pot monta senzorii de curent si tensiune conform instructiunilor de mai sus.

RGDAT dispune de un dispozitiv de detectare directionala a defectului caruia i se poate seta directia
de detectie. La montaj se va stabilii direcţia de detecţie a defectului(spre sursa sau spre consumator)
iar de la punctul central printr-o configurare de la distanta acest sens de detecţie se va putea inversa.
Astfel se poate asigura o montare uniforma. Secundarele senzorilor de curent trebuie sa fie legate la
RGDAT înainte de a fi parcurse de curent deoarece nu sunt prevăzute cu o conexiune de
scurcircuitare aceasta realizându-se prin conectarea la RGDAT.
In cazul in care se doreşte înlocuirea RGDAT sau verificarea semnalelor provenite de la secundarele
senzorilor de curent si tensiune, IMS trebuie sa se afle in poziţia „deschis” (pe linie poate insa sa
existe tensiune)

In final se va putea conecta cablul de comunicaţie intre RGDAT si portul pentru RGDAT de pe placa
de baza a UP. Acest cablu alimentează aparatul. Daca acest ultim cablu este conectat, RGDAT
începe sa funcţioneze iar in primele secunde de la conectarea cablului va avea toate ledurile aprinse
după care se vor aprinde doar ledurile ce semnalizează local anumite stari.

C O L G IO V AN N I PA OLO S.p.A.

RGDAT ce se
COL GIOVANNI PAOLO S.p.A.

instaleaza in
interiorul UP de
tip Col G.P. si se
fixeaza pe usa RGDAT ce se
RGD AT ce se va introduce in RGDAT ce se va introduce in
UP U P-ului de tip COL
interiorul instaleaza in
interiorul UP-ului de tip COL
GIOVANNI si se va fixa pe usa
GIOVAN N I si se va fixa pe usa
UP-ului. interiorul UP de
UP-ului.

tip Col G.P. si se


fixeaza pe usa
UP

45
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 40/41

R GD AT ce se va introduce in
interiorul U P-ului de tip CO L
G IO VAN N I si se va fixa pe usa
U P-ului.

45

Modulul RGDAT- Outdoor tip SGE trebuie instalat pe usa dulapului UP.
GHID DE MONTARE SI ACTIVARE
INTRERUPTOR DE MANEVRA - SEPARATOR
(IMS) PE STALPI August 2008
Ed. II 41/41

185

47,5
55

250
150
45

45