Kingspan X-dek
KS1000 XD Panouri pentru acoperiuri cu distane mari de rezemare
Insurer Approved
Luminatoare
KS1000 FF
Trapezoidal
KS1000 HTL
Hybrid Therma Light
KS1000 PC
Polycarb Rooflight
Pentru panourile FR i FA putei s verificai disponibilitatea modulului de 1000mm sau de 1200mm. Contactai Kingspan pentru detalii.
Detalii privind activitile Kingspan din Austria, Belarus, Bosnia i Heregovina, Bulgaria, Croaia, Republica Ceh, Danemarca, Estonia, Finlanda,
Germania, Ungaria, India, Letonia, Lituania, Polonia, Romnia, Rusia, Serbia, Slovacia, Slovenia i Ucraina, sunt disponibile pe site-ul nostru
www.kingspan.info
Systems
Introducere
Cuprins
Introducere
Caracteristici principale
Beneficiile sistemului
Versatilitatea designului
Acoperiuri verzi
Datele tehnice ale produsului
Avantajele i beneficiile XdekTM
Solutii de fixare
Tabele de ncrcri
1
3
4
5
6
7
9
10
11
DETALII CONSTRUCTIVE
Coam 13
Dolie 13
Pretiere 14
mbinare cap la cap
14
mbinare cu perete de zidrie
15
Parapet pentru fronton lateral
16
Parapet pentru fronton n coam
16
Luminator tip cupol
17
Trap de fum
17
Jgheab de parapet
18
Parapet
18
Parapet cu sifon
19
Dolie cu sifon
19
Jgheab exterior
20
Rost de dilatare
20
Manipularea in santier
21
Materiale de etansare
21
Strapungerile acoperisului
21
Inspectiile
22
Viteza de constructie
22
Kingspan X-dek
Kingspan X-dek
Caracteristici principale
Caracteristici principale
X-dekTM este un sistem izolator structural de acoperi, cu mbinare cap la cap
Printre caracteristicile principale se numr:
Structur & Design
Instalare rapid
Beneficiile sistemului
Suprafaa interioar
Garanie
Sistemul de acoperi X-dekTM este acoperit de Garania Kingspan, care asigur performanele termice i structurale ale panourilor
pentru o perioad de pn la 25 de ani.
Kingspan X-dek
Sistem structural de acoperi alctuit din panouri prefabricate, cu mbinare cap la cap.
Respect toate reglementrile naionale privind sigurana.
Adecvat pentru mbinarea cap la cap, cu distane ntre punctele de reazem de pn la 6 metri.
Montare rapid, cu o singur component i un singur sistem de fixare pn la 1.200 m2 pe zi.
Sunt disponibile soluii pentru ncheierea ciclului de via.
Valoarea U de 0,19 W/m2K (pentru grosimea de 100mm).
Sistemul de acoperi X-dekTM poate contribui semnificativ la etaneitatea acoperiului, datorit absenei cavitilor ntre
suprafaa din oel i izolaie
Este un sistem de panouri izolatoare FireSafeTM.
Poate constitui o parte a sistemului plan de acoperi: X-dek TR20 (XB), X-dek TR27(XG), X-dek Steel (XD) sau poate fi folosit ca i
un sistem unic i complet: X-dek PVC (XM).
Kingspan X-dek
Versatilitatea designului
Produsele compatibile cu sistemele de acoperi X-dekTM includ:
Versatilitatea designului
Acoperiuri verzi
Acoperiurile verzi
Acoperiurile cu vegetaie extensiv sunt zone de vegetaie
asemntoare celor naturale, care se dezvolt n mod natural
i nu necesit multe ngrijiri din partea omului. Acestea sunt
alctuite din plante adaptate pentru condiii extreme i au o
mare capacitate de regenerare. Aceste grdini sunt realizate din
muchi, plante atrgtoare i erbacee. Vegetaia este lsat s se
dezvolte n condiii naturale.
Lucrrile de impermeabilizare
Fiecare panou de acoperi KS1000 X-dek (cu excepia X-dek PVC) trebuie s fie finisat cu o membran impermeabil. Panourile KS1000
XD pot fi utilizate cu membrane aplicate pe antier in mod convenional pentru acoperiuri plane, care asigur arhitectului posibilitatea de a alege dintr-o gam vast de finisaje. Datorit tipului de finisaj al suprafeei exterioare (oel, TR20 sau TR27), pot fi utilizate
variate tipuri de membrane i diferite tehnici de fixare. Tabelul de mai jos include tipurile de finisaj pentru suprafaa exterioar.
Opiuni pentru suprafaa exterioar a panourilor de acoperi KS1000 XD, n raport cu soluiile de finisaj impermeabil
(Tabel cu modul de aplicare)
Membrane polimerice
PVC, TPO, EPDM,
Lipit
Oel, TR27
(PVC cptuit cu material textil)
Montare mecanic
Termosudat
Montare mecanic
Oel, TR27
TR20
Oel, TR20
Montarea unei anumite membrane pentru acoperi trebuie s se efectueze conform instruciunilor Furnizorului, corelate cu metoda de
fixare a membranei. Impermeabilitatea i durata de via a acoperiului depind ntr-o msur foarte mare de modul n care a fost fixat
membrana exterioar.
Kingspan X-dek
Kingspan X-dek
Material oel
Tabla interioar:
Utilizare
Biologic
Tabla exterioar:
Oel zincat la cald, conform EN 10326:2004. Oel din categoria
S220GD+Z275 oel galvanizat cu o grosime de 0,7 mm i
cu o acoperire cu un film transparent de 5 microni , pentru
fixarea ulterioara a hidroizolatiei. Profil exterior disponibil:
MiniBox sau Flat.
Toleranele produsului
Nucleul de izolare
Tiere la lungime
- 5 mm
+ 5 mm
Lime
-2 mm
+2 mm
Grosime
-2 mm
+2 mm
Tolerana rectangularitii
captului tiat
-3 mm
+3 mm
Elemente de etanare
-2 mm
+2 mm
Lungimi disponibile
Lungimea standard a panourilor este cuprins ntre 2,5 i 13,5 metri.
Pot fi furnizate panouri cu lungimea maxim de 13,5 15 metri, pentru
acestea fiind necesare costuri suplimentare de transport. Toate panourile sunt fabricate cu o pretiere; pretierea standard este de 50 mm, iar
cea maxim disponibil de 630 mm.
50630mm
Kingspan X-dek
Rezisten la foc
Panourile de acoperi Kingspan KS1000 X-dek au fost testate
conform standardului EN 13501 + A1:2010, n calitate de
elemente de acoperi portante. Performana la focul exterior
i clasificrile de rezisten la foc din interior sunt prezentate
n tabelul de mai jos:
Grosimea izolaiei [mm]
80
Tip Panou
100
BROOF(t1);
REI15
BROOF(t1);
REI15
KS1000 X-dek
TR27 (XG)
BROOF(t1);
RE20
BROOF(t1);
REI20
KS1000 X-dek
PVC
BROOF(t1);
REI30
BROOF(t1);
REI30
KS1000 X-dek
Steel (XD)
BROOF(t1);
REI30
BROOF(t1);
REI30
RA2 [dB]
RW [dB]
25
22
26
23
21
24
Performane
KS1000 X-dek
TR20(XB) PVC(XM)
22
20
23
Izolare termic
= 0,022 W/mK
Calitate i durabilitate
Grosimea panoului
(mm)
Valoarea R
[(m2K)/W]
Valoarea U
[W/m2K]
80 / Opiunea I
4,21
0,23
80 / Opiunea II
4,03
0,24
Panourile izolatoare Kingspan sunt confecionate din materiale de cea mai nalt calitate, utiliznd cele mai avansate
echipamente de producie, respectnd cu strictee prevederile standardelor de calitate i control, standardul ISO9001,
pentru a asigura sigurana n utilizare pe termen lung i o
durat mare de via.
100 / Opiunea I
5,12
0,19
Garanie
0,20
100 / Opiunea II
Kingspan X-dek
4,86
Soluii de fixare
AVANTAJE I BENEFICII
Limea minim a reazemului la extremiti trebuie s fie de 40 mm, limea reazemului intermediar (n funcie de calculele de
rezisten static) trebuie s fie de minim 100 mm.
Elementele de fixare trebuie s fie aplicate pentru fiecare cut peste elementul de reazem; proiectantul trebuie s specifice cantitatea
exact de elemente de fixare, n funcie de condiiile locale de suciune a vntului.
Pentru rezemare dubl, aranjarea panourilor poate fi de dou feluri: standard sau n form de tabl de ah vezi mai jos.
Kingspan recomand aranjarea n form de tabl de ah pentru aplicaiile in care panourile au rezemare dubl.
23
12
22
2
3
11
2
1
Kingspan X-dek
Kingspan X-dek
10
Aranjarea standard
(ncrcare diferit pentru fiecare grind)
21
Strat exterior
PVC/TR20/TR27/ PVC
Caz de ncrcare
Capacitate portant
ULS
80
Rezisten la incovoiere
SLS
Capacitate portant
ULS
Rezisten la incovoiere
SLS
100
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
2,0
Caz de ncrcare
2,5
3,0
3,5
4.0
4.5
5.0
5.5
6.0
6,850
7,090
4,570
4,730
6,850
7,095
4,570
4,730
5,355
5,250
3,400
3,500
5,355
5,250
3,400
3,500
4.704
3.329
2.622
2.500
4.704
3.433
2.619
2.350
3.561
2.417
1.757
1.728
3.639
2.559
1.777
1.717
2.758
1.785
1.220
1.240
2.885
1.949
1.251
1.300
2.279
1.529
0.929
0.946
2.378
1.487
0.963
0.969
1.915
1.329
0.725
0.740
1.993
1.145
0.760
0.740
50
40
1,1 mm
2,5
3,0
3,5
4.0
4.5
5.0
5.5
6.0
6,5
Rezemare simpl
Presiune [kN/m]
15,600
12,435
9,915
7,215
5,566
4,367
3,475
2,844
2,337
1,968
Capacitate portant
ULS
Suctiune [kN/m]
21,060
13,545
9,450
6,990
4,833
3,848
3,146
2,565
2,228
1,917
80
Presiune [kN/m]
10,400
8,290
6,610
4,810
2,889
1,990
1,391
1,017
0,728
0,535
Rezisten la incovoiere
SLS
Suctiune [kN/m]
14,040
9,030
6,300
4,550
3,100
2,200
1,670
1,300
1,040
0,860
Presiune [kN/m]
15,600
12,435
9,915
7,215
5,674
4,452
3,543
2,900
2,383
2,006
Capacitate portant
ULS
Suctiune [kN/m]
21,060
13,545
9,450
6,990
4,833
3,848
3,146
2,565
2,228
1,917
OBSERVAII:
Presiune [kN/m]
10,400
8,290
6,610
4,810
2,943
2,027
1,417
1,036
0,741
0,545
Rezisten la incovoiere
100
ULS Starea Limit Ultim ncrcrile indicate trebuie comparate cu valorile de incrcri factorizate (design)
SLS
Suctiune [kN/m]
14,040
9,030
6,300
4,550
3,100
2,200
1,670
1,300
1,040
0,860
SLS Starea Limit de Serviciu ncrcrile indicate trebuie comparate cu valorile caracteristice (nefactorizate)
amin Valorile
(mm) de mai sus referitoare la ncrcri sunt valabile50pentru tabla interioar standard din oel avnd minim
40 fy=350MPa (S350GD)
Deflecia maxim admis (SLS): L / 200
Greutatea proprie a panourilor este inclus n datele menionate mai sus.
amin = limea minim a suporturilor la capete.
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Capacitate portant
ULS
80
Rezisten la incovoiere
SLS
Capacitate portant
ULS
Rezisten la incovoiere
SLS
100
Strat interior
Distan ntre reazeme [m]
2,0
2,5
Rezemare dubl
9,990
7,050
14,865
10,230
6,660
4,700
9,910
6,820
9,990
7,050
14,865
10,230
6,660
4,700
9,910
6,820
3,0
3,5
4,0
4,5
5,0
5,5
6,0
5,200
7,500
3,470
5,000
5,200
7,500
3,470
5,000
3,975
5,700
2,650
3,800
3,975
5,700
2,650
3,800
2,853
3,098
5,466
4,981
3,187
3,108
5,466
4,662
2,316
2,388
4,107
3,816
2,448
2,746
3,911
3,704
1,927
1,886
3,189
3,014
1,927
2,460
2,903
3,014
1,561
1,702
2,506
2,352
1,553
2,161
2,398
2,379
1,285
1,551
2,015
1,879
1,271
1,924
2,015
1,920
amin (mm)
90
40
160
120
PVC/TR20/TR27/ PVC
Caz de ncrcare
Capacitate portant
ULS
80
Rezisten la incovoiere
SLS
Capacitate portant
ULS
Rezisten la incovoiere
SLS
100
0,9 mm
bmin (mm)
Strat exterior
Caz de ncrcare
0,9 mm
Rezemare simpl
10,380
8,260
15,780 10,155
6,920
5,510
10,520
6,770
10,380
8,260
15,780 10,155
6,920
5,510
10,520
6,770
PVC/TR20/TR27/ PVC
amin (mm)
Strat exterior
PVC/TR20/TR27/ PVC
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
Strat interior
1,1 mm
2,5
Rezemare dubl
14,085
9,855
21,795
14,755
9,390
6,570
14,530
9,850
14,085
9,855
21,795
14,755
9,390
6,570
14,530
9,850
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,245
10,320
4,830
6,880
7,245
10,320
4,830
6,880
5,520
7,620
3,680
5,080
5,520
7,620
3,680
5,080
4,320
5,292
5,466
4,981
4,320
5,292
5,466
4,662
3,450
4,185
4,107
3,816
3,450
4,185
3,911
3,704
2,805
3,416
3,189
3,014
2,805
3,416
2,903
3,014
2,310
2,862
2,506
2,352
2,310
2,862
2,398
2,379
1,920
2,417
2,015
1,879
1,920
2,417
2,015
1,920
1,620
2,093
1,188
1,705
1,620
2,093
1,242
1,783
amin (mm)
90
40
bmin (mm)
160
120
OBSERVAII:
ULS Starea Limit Ultim ncrcrile indicate trebuie comparate cu valorile de incrcri factorizate (design)
SLS Starea Limit de Serviciu ncrcrile indicate trebuie comparate cu valorile caracteristice (nefactorizate)
Valorile de mai sus referitoare la ncrcri sunt valabile pentru tabla interioar standard din oel avnd minim fy=350MPa (S350GD)
Deflecia maxim admis (SLS): L / 200
Greutatea proprie a panourilor este inclus n datele menionate mai sus.
amin = limea minim a reazemelor la capete; bmin = limea minim a reazemelor intermediare
80
100
80
100
0,7 mm
Tip de ncrcare [kN/m]
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
0,9 mm
3,0
Rezemare simpl
8,47
6,23
9,49
7,09
102
91
8,96
6,61
10,17
7,72
108
97
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
4,79
5,57
82
5,15
6,15
88
3,82
4,52
76
4,15
5,06
82
3,12
3,77
70
3,45
4,26
77
2,65
3,16
68
2,91
3,61
73
2,15
2,56
60
2,47
2,95
68
1,70
2,12
55
2,01
2,46
63
1,35
1,78
49
1,63
2,07
56
1,05
1,52
41
1,31
1,77
44
0,80
1,28
40
1,02
1,53
43
3,0
Rezemare simpl
9,85
7,41
11,21
8,31
119
108
10,32
7,79
11,90
8,97
125
114
100
1,1 mm
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
7,5
5,56
6,50
97
6,03
7,10
103
4,50
5,26
89
4,85
5,82
96
3,67
4,36
83
4,00
4,88
90
3,05
3,51
77
3,37
3,98
85
2,38
2,84
67
2,75
3,24
77
1,87
2,35
59
2,20
2,69
69
1,49
1,97
43
1,78
2,27
61
1,16
1,68
45
1,45
1,94
55
0,89
1,45
40
1,14
1,68
48
OBSERVAII:
Valorile de mai sus referitoare la ncrcri sunt caracteristice. Pentru fiecare valoare, au fost luate n considerare cazuri de ncrcri individuale i combinate, cu factori de ncrcare i de
temperatur corespunztoare. Pentru valorile intermediare, poate fi utilizat interpolarea liniar.
Valorile au fost calculate cu ajutorul metodei de stare limit n conformitate cu standardul EN 14509, lund n considerare sarcinile i temperaturile impuse.
Valorile de mai sus referitoare la ncrcri se aplic pentru panouri cu tabla standard din oel avnd specificaiile:
fy=350MPa (S350GD) sau mai mare pentru stratul INTERIOR din oel profilat trapezoidal;
fy=220MPa (S220GD) sau mai mare pentru stratul EXTERIOR din oel profilat MiniBox. Pentru caracteristici ale panoului avnd stratul exterior din oel FLAT, v rugm s contactai
Departamentul Tehnic Kingspan.
Deflecia maxim admis n jos i n sus: L / 200
Greutatea proprie a panourilor este inclus n datele menionate mai sus.
amin = limea minim a suporturilor de capt; bmin limea minim a suporturilor intermediare
Kingspan X-dek
11
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
bmin (mm)
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
bmin (mm)
80
100
0,9 mm
3,0
Rezemare dubl
8,47
6,23
9,49
7,09
102
91
205
182
8,96
6,62
10,17
7,72
108
97
216
193
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
7,5
4,79
5,57
82
165
5,15
6,15
88
177
3,82
4,52
76
152
4,03
5,06
80
160
3,13
3,77
70
141
3,44
4,26
77
155
2,61
3,19
66
132
2,89
3,65
73
146
2,22
2,75
62
125
2,47
3,16
69
139
1,90
2,40
59
118
2,02
2,76
63
126
1,62
2,11
56
111
1,71
2,44
58
117
1,40
1,87
52
105
1,47
2,18
55
110
1,20
1,68
49
99
1,27
1,95
52
104
0,7 mm
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
bmin (mm)
Presiune [kN/m]
Suctiune [kN/m]
amin (mm)
bmin (mm)
7,5
80
0,7 mm
Tip de ncrcare [kN/m]
0,7 mm
1,1 mm
3,0
Rezemare dubl
9,85
7,41
11,21
8,31
119
108
238
216
10,32
7,79
11,90
8,97
125
114
249
227
3,5
4,0
4,5
5,0
5,5
6,0
6,5
5,66
6,50
97
194
6,03
7,10
103
207
4,49
5,26
89
178
4,84
5,82
96
191
3,67
4,36
83
165
4,00
4,88
90
179
3,05
3,70
77
154
3,36
4,17
85
169
2,58
3,18
73
145
2,87
3,61
80
161
2,21
2,77
69
137
2,42
3,16
75
150
1,91
2,28
65
130
2,07
2,80
70
140
1,66
2,16
62
124
1,79
2,49
66
132
1,46
1,93
59
119
1,56
2,24
63
126
OBSERVAII:
Valorile de mai sus referitoare la ncrcri sunt caracteristice. Pentru fiecare valoare, au fost luate n considerare cazuri de ncrcri individuale i combinate, cu factori de ncrcare i de
temperatur corespunztoare. Pentru valorile intermediare, poate fi utilizat interpolarea liniar.
Valorile au fost calculate cu ajutorul metodei de stare limit n conformitate cu standardul EN 14509, lund n considerare sarcinile i temperaturile impuse.
Valorile de mai sus referitoare la ncrcri se aplic pentru panouri cu tabla standard din oel avnd specificaiile:
fy=350MPa (S350GD) sau mai mare pentru stratul INTERIOR din oel profilat trapezoidal;
fy=220MPa (S220GD) sau mai mare pentru stratul EXTERIOR din oel profilat MiniBox. Pentru caracteristici ale panoului avnd stratul exterior din oel
FLAT, v rugm s
contactai Departamentul Tehnic Kingspan.
Deflecia maxim admis n jos i n sus: L / 200
Greutatea proprie a panourilor este inclus n datele menionate mai sus.
amin = limea minim a suporturilor de capt; bmin limea minim a suporturilor intermediare
Kingspan X-dek
12
Tabele de ncrcri
D0.0.1.a.
D0.0.3.
404
K
04
P
D8.9.
16
P
08
P
04
P
401c
K
08
P
16
P
04
P
04
P
D0.0.4.
404
K
Orificiu preliminar, umplut cu spum poliuretanic dup montarea unui element de fixare
04
P
04
P
Kingspan X-dek
13
Kingspan X-dek
14
Detalii
constructive
la 200 mm
406
K
min. 300 mm
D5.5.1.
2x la 500 mm
08
P
la 500 mm
183
K
la 500 mm
07
P
Orificiu preliminar, umplut cu spum poliuretanic dup montarea unui element de fixare
Membran impermeabil lipit sau fixat mecanic
08w
P
D16.4.1.c.
la 200 mm
28
P
31
P
la 200 mm
04
P
112
K
Mastic de etanare
31
P
la 200 mm
31
P
406
K
155
K
min. 300 mm
D17.4.1.
la 200 mm
D5.5.2.a
Orificiu preliminar, umplut cu spum poliuretanic dup montarea unui element de fixare
la 300 mm
08
P
la 500 mm
183
K
la 300 mm
07
P
08w
P
04
P
04
P
14
P
106
K
04
P
la 300 mm
Kingspan X-dek
15
Kingspan X-dek
07
P
16
Detalii
constructive
D44.1.1.a.
D6.7.1.
la 300 mm
minim 150 mm
07
P
28
P
28
P
130
K
08
P
la 300 mm
la 300 mm
la 300 mm
08
P
la 300 mm
la 300 mm
07
P
Supraplin
106
K
28
P
la 300 mm
04
P
02
P
04
P
D46.1.1.a.
D6.9.1.
07
P
2x la 500 mm
la 300 mm
183
K
la 500 mm
07
P
la 300 mm
la 300 mm
28
P
la 300 mm
04
P
04
P
Kingspan X-dek
17
Kingspan X-dek
18
Detalii
constructive
D6.8.1.
D0.5.a.
150 450 mm
07
P
la 300 mm
08
P
la 500 mm
130
K
08
P
la 300 mm
Metal acoperit cu membran
407
K
07
P
08
P
03
P
la 300 mm
>80 mm
04
P
02
P
04
P
28
P
D8.8.
04
P
102
K
08
P
D20.2.
Evacuare pe acoperi
Izolaie aplicat pe antier
04
P
04
P
28
P
04
P
04
P
28
P
04
P
Kingspan X-dek
19
Kingspan X-dek
20
Detalii
constructive
Membran impermeabil
lipit sau fixat mecanic
Manipularea n antier
n general, panourile sunt depozitate n palei, aranjate cap la cap. Pentru rotirea
panourilor (50%), se recomand utilizarea unui dispozitiv special cu pomp cu
vid cu o unitate de rotire la 180. Echipamentul se numete RotaBoy. Acesta
poate fi obinut direct de la productorul Viavac sau poate fi nchiriat de la
sediul local ViaVac sau de la reprezentatul acestuia. Pentru a afla adresa celui mai
apropiat sediu, accesai site-ul http://www.viavac.com/.
Atunci cnd panourile sunt furnizate mpreun cu o folie protectoare din plastic,
aceasta trebuie ndeprtat imediat dup instalarea pe antier.
Inspeciile
Se recomand ca acoperiurile fabricate din panouri KS1000 XD s fie inspectate cel puin o dat pe an, conform regulilor Standard de
Inspecie i ntreinere Kingspan. n timpul inspectrii acoperiului, toi participanii trebuie s respecte regulile i reglementrile n materie
de sntate i siguran.
21
P
03
P
Aplicat pe antier
Viteza de construcie
La poziionarea strpungerilor acoperiului, trebuie s luai ntotdeauna n considerare poziia cutelor panoului.
Atunci cnd strpungerile acoperiului sunt mai mari de 300 mm, deschiderile
trebuie ranforsate suplimentar cu elemente de sprijin adiionale care s compenseze pierderea din capacitate a panoului.
Unitile montate deasupra acoperiului trebuie verificate de un inginer de
rezisten cu privire la sarcinile suplimentare care pot fi aplicate pe panou i
acesta v poate recomanda un sprijin suplimentar necesar acestor elemente.
Dimensiunea proiectului
5000 m2
Dimensiunea proiectului
10000 m2
5000 m2
Dimensiunea proiectului
Sptmni 1
Kingspan X-dek
21
Kingspan X-dek
10000 m2
22
Dimensiunea proiectului
10
Manipularea n antier
Viteza de construcie
Strpungerile acoperiului