Sunteți pe pagina 1din 58

REELE TERMICE MANUAL TEHNIC

Sistem Uponor - evi Preizolate pentru nclzire i alimentri cu ap

RE E L E T E R M I C E U P O N O R - manual M A N U A L tehnic T E H N I C 0 5 / 2 0 11

Cuprins
Descrierea sistemului i domeniile de utilizare Descrierea sistemului.....................................................4 Domenii de utilizare........................................................5 Flexibilitate i stabilitate datorit unei construcii unice a evi............................................................................7 Tipuri de produse Uponor Thermo...............................................................8 Uponor Aqua...................................................................9 Uponor Quattro.............................................................10 Accesoriile sistemului Sistemul de racordare...................................................11 Cciuli de capt............................................................13 Setul de izolare.............................................................14 Cminele Uponor..........................................................15 Accesorii pentru traversarea pereilor ..........................16 Accesorii suplimentare ................................................18 Proiectare Bazele proiectrii..........................................................19 Proiectarea traseului evii ...........................................20 Exemple de instalare ...................................................21 Dimensionarea evilor de nclzire Tabele pierdere de presiune ........................................23 Diagrama pierderi presiuni...........................................25 Bazele dimensionrii instalaiilor...................................26 Tabele de dimensionare rapid.....................................27 Pierderea de cldur.................................................... 29 Dimensionarea evilor pentru ap cald Tabel pierderi de presiune.............................................31 Diagram pierderi de presiune .....................................32 Instalare Ghid valori pentru procesul de instalare........................33 Manipularea evii ......................................................... 34 Instruciuni de montaj................................................... 38 Testarea la presiune i la scurgeri Testarea la presiune i scurgeri conform cu DIN 1988 Part 2............................................................48 nregistrarea testelor de presiune conform cu DIN 1988 Part 2 pentru evile de ap...........................49 Testarea la presiune i scurgeri pentru evile de nclzire conform cu DIN 18380........................................................50 nregistarea testelor de presiune conform DIN 18380 pentru evi de nclzire .......................................................51 Specificaii tehnice Proprietile evilor Uponor PE-Xa................................52 Proprietile pe termen lung..........................................53 Proprietile materialului nveliului evii.......................54 Proprietile materialului izolator ..................................54 Anexe Tabele...........................................................................55

Toate informaiile tehnice i legale coninute n acest catalog au fost selectate cu atenie, conform cu cele mai bune cunotine ale noastre. Nu putem fi fcui rspunztori pentru orice eroare aa cum ele nu pot fi excluse complet. Ghidul tehnic, incluznd toate seciunile este protejat prin copyright. Toate utilizrile n afara celor permise de legea copyrightului, nu sunt permise fr aprobarea Uponor. Aceasta se aplic n special la reproducere, reprintare, procesare, stocare i procesare n sisteme electronice, traduceri i microfilmare. Coninutul ghidului tehnic poate fi modificat fr ntiinare prealabil. Copyright 2011 Uponor
E L E T E H RN MIIC CE UPONO RE R - manual tehnic 0 5 / 2 0 11 3

Descrierea sistemului i domeniile de utilizare


Descrierea sistemului
De la teorie la practic Aceasta este ideea fundamental din spatele sistemului nostru de evi preizolate flexibile. Flexibilitatea materialului, tehnica de conectare, durata serviciului de via i robusteea, bine testate, ale evii noastre preizolate, asigur n final, c dvs. ca expert, putei ndeplini proiectele rapid, economic i sigur. Acelai lucru, fie c discutai despre o reea extins sau despre o conectare a unei cldiri. Apa cald, apa de but, apa de rcire i apa rezidual sunt transportate sigur, ca i alte multe materiale lichide pentru aplicaiile industriale. Serviciile pe care le oferim n asociere cu sistemele de evi preizolate ofer de asemenea, suport complet la orice faz a proiectului dvs.

Calitate, semnat i parafat Calitate fr compromisuri, este politica noastr de baz. Controlul calitii extins al produciei este doar unul din aspectele sistemului nostru de management al calitii. i noi ne asigurm n mod regulat c organismele de inspecie independente certific faptul c produsele noastre ntrunesc cele mai riguroase standarde. Aprobrile i certificrile Kiwa KOMO Compatibilitatea ntre componente (Thermo Single, Thermo Twin, Cciuli de capt, gama de fitinguri cu colier de strngere i seturile de izolare) este examinat de dou ori pe an conform sistemului de aprobare BRL 5609. Aprobarea certific durata de via a sistemului de cel puin 30

ani i absena scurgerilor la o presiune a apei de 0.3 bar i o temperatur a mediului de 30 C. n plus, pierderile de cldur, rezistena la sarcini statice ca i comportamentul evilor, sunt verificate conform cu specificaiile. Certificarea DIN Certco Certificarea anual conform VDI 2055 verific valorile pierderilor de cldur. Graficele pierderilor de cldur pentru eava prerizolat flexibil sunt realizate pe aceast baz . Certificarea se bazeaz pe cerinele definite, i nseamn c valorile sunt o bun reflectare a condiiilor reale.

condiiile definite, sunt indicate pentru ncrcare cu trafic greu, (SWL 60 = 60 t) conform cu foaia de lucru ATV-A 127. Rigiditatea inelului mantalei exterioare de protecie a evii este certificat conform EN ISO 9969. Conductivitatea termic minim neschimbat a izolaiei Testele de material conform EN 15632 la 80 C demonstreaz c materialul nostru izolator, absoarbe mai puin de 1 % ap din volum. Aceast absorbie redus nseamn c proprietile izolatoare sunt practic neschimbate.

Certificarea la sarcini statice Certificarea bazat pe ATV DVWKA127, demonstreaz c evile noastre, instalate n conformitate cu

Livrat la lungimea cerut i instalat direct din colac.

Conectare uoar, permanent i practic.

Flexibil i rapid introdus prin peretele exterior la punctul central de distribuie.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Domeniile de utilizare

Calitate nu cantitate. Uponor v ofer produse inteligente pentru aproape toate tipurile de aplicaii Este o marc a unui sistem de evi de calitate care ofer soluii profesionale unui mare numr de posibile utilizri cu numai cteva componente. Performanele evilor preizolate flexibile de la Uponor, le recomand pentru o gam variat de aplicaii.

Uponor Thermo eav simpl (Single Thermo) sau dubl (Twin Thermo) pentru nclzire. Versiunea Thermo Twin include turul i returul ntr-un sistem cu o singur eav.

Uponor Aqua evi simple sau duble pentru ap i nclzire. Versiunea Aqua Twin include un circuit integrat de recircu lare a apei.

Uponor Quattro Soluia toate ntr-o singur eav, pentru ap potabil i nclzire, ntr-o singur eav flexibil. Ideale, economice i practice.

Informaii rapide i eseniale despre produs

Pentru transportul agentului termic. Varianta cu o eav (single) sau cu dou evi (twin) pentru tur i retur. Pentru transpotul apei calde i reci, la versiunea cu dou evi se folosete ap cald recirculat
Aplicaii 1) Ap cald i rece Agent termic Agent termic pentru rcire Uponor Thermo Uponor Aqua Uponor Quattro

PE-Xa cu EVOH PE reticulat PE-D PE-Xa PE reticulat PE-D PE-Xa i PE-Xa cu EVOH PE reticulat PE-D

Variante Opional cablu de nclzire (numai pentru evi single ) Material Material eav interioar Material izolaie Material manta exterioar de protecie
1)

pentru alte aplicaii i fluide (ex. chimicale, produse alimentare sau ap rezidual) contactai-ne !

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Flexibilitate - de la punctul termic i pn n cas Fr sudur, fr scule speciale Flexibilitatea i masa redus a evilor noastre preizolate, le face uor de manipulat i procesul de montaj se deruleaz rapid. Ele sunt compatibile de asemenea cu o gam larg de accesorii. De la o diversitate de treceri prin perei, seturi de izolare, la gama cunoscut de fitinguri. Cele mai importante avantaje ale montajului i racordrii Fr dificulti la montaj n jurul colurilor i obstacolelor Instalarea a pn la 200 metri de eav fr racord dintr-o singur bucat Structura evilor preizolate nu necesit montarea de compensatoare de dilatare Execuie rapid a construciei /timp scurt de montaj Metod uoar i sigur de racordare, inclusiv a izolaiei racordurilor i ramificaiilor Serviciul de tiere : lungimile colacilor, adaptate la cerinele dvs. Att lungimile standard ct i cele pariale sunt livrate n cel mai scurt timp. Suport complet oferit de tehnicienii notri cu experien n proiectare i montaj Suport pentru proiectare i instruire pe antier

Manipulare uoar datorit flexibilitii extraordinare: nu numai la derulare ntr-un an dar n mod special la cminul de racordare, unde clientul apreciaz aceste avantaje.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Flexibilitate i stabilitate datorit unei construcii unice a evii


Calitatea ridicat a evilor preizolate flexibile Uponor este consecina rezistenei elementelor individuale. Combinaia dintre mantaua exterioar de protecie, rezistent la mbtrnire, stratul izolator i robust din polietilen reticulat stabil dar flexibil, cu durata ndelungat de via i eava PE-Xa cu durat de via ndelungat, creaz sistemul de evi care poate fi uor i rapid instalat i care funcioneaz n siguran.

1 2 3 4

1 Mantaua exterioar de protecie din PE-D : rezistent la oc, cu durat lung de via dar flexibil, datorit geometriei unice 2 Izolaia din spum de polietilen reticulat, proprieti izolatoare ideale, rezistent la mbtrnire, rezistent la umiditate i flexibilitate foarte ridicat 3 Profilele de centrare colorate evit confuzia dintre evile de tur i retur

Cele mai importante caracteristici dintr-o privire Manipulare uoar i instalare rapid, datorate flexibilitii excepionale Izolaie rezistent la mbtrnire, permanent elastic, datorit spumei de polietilen reticulat cu celule nchise, absorbia de ap < 1% din volum Pierderile de cldur 1) monitorizate extern de ctre DIN Certco eava interioar PE-Xa rezistent la coroziune i cruste eava interioar realizat din polietilen reticulat (PEXa) ofer rezisten excepional la crpturile datorate oboselii, mediilor agresive, ngheului i micro-organismelor Rigiditate optim a inelului mantalei exterioare, rezisten la impact i presiune iar simultan ofer i flexibilitate ridicat la montaj i mas specific redus.
1)

4 eava PE-Xa: rezistent la temperatur i rezistent la formarea crustei pe interior i crpturilor datorit stresului termic

Uponor Thermo

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Tipuri de produse

Uponor Thermo

Practic, ideal i flexibil pentru furnizarea de agent termic Soluia ideal pentru distribuia agentului termic n reelele locale de nclzire, sau pentru racordarea complexelor de cldiri sau a caselor indiUponor Thermo Single Aplicaie primar Agent termic ap fierbinte Aplicaie secundar Ap rezidual Chimicale (sunai pentru confirmare) Material eav PE-Xa cu EVOH, SDR 11 (6 bar) Opiune Cablu de nclzire Material izolator Spum PE reticulat Material tub exterior PE-D (PE 80) Aplicaie primar Agent termic ap fierbinte Aplicaie secundar Ap rezidual Chimicale (sunai pentru confirmare) Material eav PE-Xa cu EVOH, SDR 11 (6 bar) Opiune Cablu de nclzire Material izolator Spum PE reticulat Material tub exterior PE-D (PE 80) Not: Soluiile standard verificate pentru distribuia agentului termic n reelele locale de nclzire sau pentru racordarea unei singure cldiri. viduale. Uponor Thermo n versiunea Twin combin circuitele de tur i retur ntr-un sistem de evi flexibile. Clasificarea sistemului cu eav Thermo este descris n EN 15632-T3 ca un sistem necompozit cu eav din mas plastic.

80C * max.95C

6 bar

25110 mm

Uponor Thermo Twin

80C * max.95C

6 bar

Not: Circuite combinate de tur retur n sistemele cu o singur eav, incluznd miezuri izolatoare cu dou culori pentru evitarea confuziei n timpul montajului

2563 mm

*V rugm s parcurgei explicaiile de la pagina 55 8 R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Uponor Aqua

"Specialistul" dvs. flexibil pentru ap cald i rece Imbatabil pentru instalarea rapid, sigur, i totui foarte economic n sistemele de furnizare a apei calde. Uponor Aqua Single n versiunea Twin , v oferim o soluie cu o eav de recirculare integrat. Clasificarea materialului evii PE-Xa pentru sistemul de evi Aqua este descris n EN ISO 15875.

70C * max. 95C

10 bar

25110 mm

Aplicaii primare Ap cald i rece Aplicaii secundare Alimentaie (sunai pentru confirmare) Chimicale (sunai pentru confirmare) Material eav PE-Xa, SDR 7,4 Opional Cablu nclzire Material izolator Spum PE reticulat Material tub exterior PE-D (PE 80) Aplicaii primare Ap cald cu recirculaie Aplicaii secundare Alimentaie sunai pentru confirmare) Chimicale(sunai pentru confirmare) Material eav PE-Xa, SDR 7,4 Material izolator Spum PE Reticulat Material tub exterior PE-D (PE 80)

Not: eav sigur, economic pentru instalaiile de ap cald.

Uponor Aqua Twin

70C * max. 95C

10 bar

Not: O eav pentru ap cald i una pentru recirculaie, combinate ntrun singur sistem. Profilul central izolator n dou culori simplific conectarea corect a evilor centrale.

2550mm

*V rugm parcurgei explicaiile de la pagina 55

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Uponor Quattro

Modul corect de a face un singur racord n cldire O eav pentru toate aplicaiile! Agentul termic tur i retur, mpre un cu apa cald, inclusiv cu recirculaia, n doar o singur eav. Uponor Quattro Aplicaii primare Agent termic Ap cald, ap cald cu recirculaie Material eav PE-Xa, SDR 7,4 (10 bar) i PE-Xa cu EVOH, SDR 11 (6 bar) Material izolator Spum PE reticulat Material manta exterioar protecie PE-D (PE 80) Not: eava Uponor Quattro este de asemenea practic i economic pentru racordarea cldirilor auxiliare. Profilul izolator cu dou culori simplific conectarea corect a evii centrale. Este cel mai convenabil, mai sigur i mai economic mod de a conecta o cldire individual sau un complex de cldiri.

70/80C * max.95C

6 bar + 10 bar

2532mm

* V rugm parcurgei explicaiile de la pagina 55

10

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Accesoriile sistemului

Sistemul de conectare

Tehnologia de conectare Uponor pentru produsele noastre Thermo, Aqua i Quattro Racordurile Uponor PE-Xa cu colier de strngere, sunt special proiectate pentru conectarea evilor de polietilen reticulat produse de Uponor, pentru ap cald i rece n instalaiile casnice i cele de nclzire centralizat. Racordurile sunt disponibile pentru dimensiunile evilor cuprinse ntre 25 -110 mm, n dou serii, marcate PN 6 (v.5.0) i PN 10 (v.3.2). Racordurile Uponor PE-Xa cu colier de strngere sunt proiectate pentru a oferi o excelent strngere a racordului pe eav. Fora de strngere este mai mare dect rezistena la rupere a evii, i performanele de etanare sunt neafectate de fluctuaiile de temperatur. Racordurile Uponor PE-Xa cu colier de strngere au un design simplu i robust, pot fi montate foarte rapid i uor, chiar i n locuri nguste i cu acces dificil. Cheile inelare folosite la fixarea racordurilor cnd fitingurile i racordurile sunt foarte mici, sunt comod de folosit comparativ cu mrimea racordului. Racordul Uponor PE-Xa cu colier de strngere este patentat, testat conform normelor DVGW (Germania),

NKB (Suedia), CSTB (Frana), KIWA (Olanda) i aprobate. Principalele componente ale fitingurilor sunt realizate din alam DR (rezistent la dezincare). Inelele O-ring sunt folosite pentru a etana racordul cu fitingurile evii. Nu este necesar teflon sau cnep pentru etaneizri suplimentare Racordurile Uponor permit o larg

gam de combinaii de conectare. Singurele scule necesare sunt dou chei fixe plus o pereche cleti.

Racord letat Cciul capt

Recomandare de proiectare : Cnd conectm racordurile Uponor PE-Xa cu colier de strngere cu componente de la alt productor, elementele terminale ale racordului Uponor trebuie s fie un fiting (cot sau muf) cu filet interior.

Racord letat

Niplu reducie cu O-ring

Racord

letat

Cot cu O-ring Flan letat cu O-ring

Rac ord let exterior cu O-ring

Teu cu O-ring

racord letat

Tehnica de racordare Uponor

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

11

Q&E - calea cea mai dreapt ctre instalaii profesioniste Sistemul este bazat pe proprieti le unice ale evilor Uponor PE-Xa (metoda Engel) i pe fitingul revoluionar Q&E. Permite montarea unui fiting fr alte scule dect un clete de expandare. Doar lrgii eava Uponor PE-Xa mpreun cu un inel Q&E i montai-o direct pe fitingul din alam sau din PPSU. eava va reveni la forma iniial iar montajul este complet. Tehnica a fost patentat de Uponor i este destinat exclusiv evilor Uponor PE-Xa cu dimensiunea de pn la 63 mm. Performanele fitingurilor au fost testate de cteva laboratoare independente acreditate, cum ar fi ATG(Belgia), Kiwa (Olanda), MPA (Germania), SP (Suedia), TGM (Austria), QAS ( Australia) ca i n laboratoarele proprii ale Uponor.

Montarea inelulului Q&E pe eav

Lrgii eava cu trusa de expandare Fitinguri Q&E PPSU

mpingei eava pe fiting i gata !

Beneficii: O soluie total i sigur pentru instalatorii profesioniti Design simplu i sigur fr garnituri, coliere cu presare sau tragere, ceea ce o face uor i simplu de folosit i rapid de executat Prin utilizarea tehnologiei Q&E, un profesionist realizeaz instalaia rapid i eficient. Odat ce racordul este fixat, el este nedemontabil

12

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Cciulile de capt
Pentru a proteja capetele evilor i pentru mprirea componentelor Cciulile de capt Uponor din cauciuc pentru eav, protejeaz izolaia evii i ofer o mprire ntre componente. Este important s oferii protecie la ptrunderea umiditii sau deteriorrii, astfel ca ntreg sistemul s poat realiza optim scopul pentru mai muli ani. O garnitur tip inel este de asemenea furnizat pentru a preveni intrarea Not: nainte de fixarea cciulii de capt, izolaia trebuie nlturat de pe eav pe o lungime potrivit. Trebuie inut cont de dimensiunile setului de izolaie. apei. Capacul poate fi montat uor i comod prin mpingere la captul evii, dup care este complet fixat cu un colier metalic. Not: Inelele clem nu trebuie montate cnd este folosit setul de izolaie Uponor !

Not: Capacele de cauciuc Uponor trebuie fixate la capetele mantalei exterioare de protecie nainte de a conecta eava PE-Xa !
Single Twin Quattro

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

13

Seturi de izolare Uponor Sunt disponibile seturi de izolare potrivite pentru izolarea i etanarea mantalei externe de protecie de 140,175 i 200 mm, att la racordul drept ct i la cel n T sau pentru coturi. Ele se potrivesc att la varianta cu o singur eav ct i la dou evi PE-Xa. Este disponibil de asemenea i un set de izolare H pentru conversia de la eava PE-Xa simpl la cea dubl. Setul izolator const n dou semicochilii care se asambleaz folosind nituri. Mantaua exterioar de diametru 68 i 90 mm poate fi adaptat la seturile izolatoare folosind inelele de reducie Uponor.

Set de izolare Uponor "T"

Set de izolare Uponor pentru cot

Set de izolare Uponor drept

Set de izolare Uponor "H"

Inel de reducie Uponor

Not: Folosii cminul Uponor pentru conexiunile Quattro

Not: Racordurile nu trebuie plasate sub drumuri, deoarece aceasta face dificil accesul ulterior i vehiculele grele pot deteriora racordul. Dac racordurile din apropierea drumurilor sunt inevitabile, trebuie turnat o plac de beton deasupra racordului pentru a distribui sarcina.

14

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Cminele Uponor
sau mai multe evi PE-Xa sau evi Uponor Quattro. Cminul este turnat i are perei din polietilen iar la interior este acoperit cu izolator din PE. Cminul de ramificare permite racordarea ulterioar a altor circuite. Cminul este etan i poate fi folosit pentru toate dimensiunile de eav (diametru exterior 140-200 mm).

Cminele de racordare Uponor sunt proietate pentru racordurile evilor care nu pot fi racordate cu un set de izolare Uponor. Acestea includ de exemplu, posibilitatea conectrii ntre evile Uponor simple i cele cu dou

Not: Racordurile nu trebuie plasate sub drumuri, deoarece aceasta face dificil accesul ulterior i vehiculele grele pot deteriora racordul. Dac racordurile din apropierea drumurilor sunt inevitabile, trebuie turnat o plac de beton deasupra racordului. pentru a distribui sarcina.

Thermo Twin casa Thermo Single

Thermo Twin casa

Thermo Twin casa

Thermo Twin casa

Thermo Single

Thermo Twin casa

Thermo Twin casa

Cminele turnate sunt executate din polietilen iar stratul izolator din interior reduce pierderile de cldur.

Alimentare de la circuitul principal al sursei de nclzire la 2 case


Aqua Twin casa 1 Aqua Twin Thermo Twin casa 2

Alimentare de la circuitul principal al sursei de nclzire la 4 case


Quattro casa Quattro casa Aqua Twin

Thermo Twin

Thermo Twin

nclzire i ap cald de la circuitele principale la cas

nclzire i ap cald de la circuitele principale la 2 case folosind eav Uponor Quattro

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

15

Accesorii pentru traversarea pereilor


instalat dup execuia unei guri n fundaie. Aceste manoane termocontractabile previn infiltrarea de ap prin picurare din fundaie n eav prin manonul de trecere.
manon termocontractibil

Tub Uponor de trecere (etan la ap fr presiune) Acest tub poate fi folosit pentru traversarea fundaiilor oriunde nu exista ap cu presiune. Tubul pentru traversare este montat pe locul unde fundaia este turnat sau este Kitul conine un tub de trecere cu lungimea de 400 mm i un manon termocontractabil.

tub de trecere

Garnitura de etanare Uponor (etan la ap fr presiune) Etaneaz eficient trecerea printr-o structur de beton, i previne ca umiditatea s intre n cldire. A fost testat etanarea cu Radon. Kitul conine tubul de trecere etan i clema inelar.

16

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Presetupa de etanare Uponor PWP pentru trecerea prin perei (rezistent la ap sub presiune) Presetupa de etanare Uponor PWP Presetupa de etanare Uponor PWP trebuie folosit oriunde se ateapt ap sub presiune. Ea poate fi folosit direct la aplicare pe peretele gurii practicate n betonul impermeabil sau pe peretele unei conducte din fibr de ciment care este betonat sau zidit.

Interior

Kitul Uponor suplimentar Dac nu este posibil s introducem mantaua exterioar de protecie perpendicular pe trecerea din perete , kitul suplimentar Uponor este folosit pentru a dispersa orice efort posibil.

Interior

Rina epoxy Uponor naintea de montarea unei treceri etane Uponor PWP, se practic o gaur n perete care poate fi acoperit cu rin Uponor !

EPOXY RESIN

HARDENER

Conducta din fibr de ciment Uponor Etanrile de perete Uponor PWP pot de asemenea s fie montate ntr-o conduct Uponor din fibr de ciment. Conducta Uponor din fibr de ciment, poate fi fixat n zidrie.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

17

Accesorii suplimentare

Mantaua deteriorat poate fi reparat uor i sigur cu manonul termocontractabil de reparaii Uponor . Banda de avertizare Uponor este aplicat peste eava flexibil preizolat pentru marcarea i identificarea ei.

Manonul Uponor termocontractabil

Banda de avertizare Uponor

Pentru fixarea i ghidarea evii exact pe poziie n pardoseal. Mai multe piese de ndoire n unghi pot fi mpreun, cap la cap. Conducta de ghidaj la coturi este folosit ca o carcas a evii preizolate, dirijnd elementele evii preizolate n cldire. Materialul este PVC plastic.
Piesele pentru fixare eav la coturi Conduct de ghidaj la coturi

18

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Proiectare

Bazele proiectrii
nica legrii. Tehnica este ndeosebi indicat n locurile unde casele sunt aliniate i dimensiunile produselor Quattro sunt cele adecvate. Suprafaa la sol necesar sistemului Quattro este foarte mic, permind ca racordurile de legare s fie fcute n interiorul apartamentelor. De exemplu, baza ridicat a unui hol poate fi folosit ca un spaiu de legtur. Linii speciale ale cldirii Cnd diferite proprietisunt alimentate termic, de la acelai punct, racordrile drepte de la cas la camera centralei sunt recomandate cnd camera centralei este plasat ntr-o poziie central. Montajul este foarte uor, fiind un traseu fr mbinri. anurile nu trebuie s fie meninute descoperite pentru testul de presiune. Bucile de eav folosite nu sunt mari i aceasta permite utilizarea elementelor multiple ale evii. Combinarea produselor Sistemele de radiatoare cu ap fierbinte pot fi folosite cu elementele de eav mari de circulaie ale produselor Quattro i Aqua Twin. Beneficiile oferite de elementele cu dou i patru evi pot fi luate n calcul n aceste locuri. Prin combinarea produselor, poate fi creat un sistem funcional i poate fi garantat funcionarea eficient a cminelor

Traseul elementelor Sistemul de eav flexibil preizolat v permite s proiectai anurile flexibil i s inei cont de mediu. Cnd eava este dirijat n cldire, la alegerea locului intrrii trebuie inut cont de cerinele de spaiu ale razei de ndoire ale elementului respectiv. Racordarea Implementarea celui mai profitabil sistem n termeni de costuri de operare i instalare, este cel mai bine realizat folosind elemente multiple de eav. Pierderea de cldur este cea mai mic la produsele Quattro care sunt recomandate n special pentru implementare la case terasate i mici cldiri de apartamente. Numrul racordurilor din sol poate fi redus pentru cldiri mici, folosind teh-

Central termic (nclzi re centralizat)

Quattro

Quattro Aqua Twi n Quattro Quattro Thermo Twi n

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

19

Proiectarea traseului evii


liber i aezat direct n an. Este esenial s evitm deteriorarea mantalei externe a evii. Este necesar un pat de nisip fr pietri. Granulaia nisipului poate fi ntre 0 i 2/3 mm. Niciodat s nu includei obiecte cu margini tioase sau ascuiete n an. ndoirea evii cu grij, (la cel puin 10 cm deasupra i dedesuptul mantalei externe, i pereilor anului) are un efect crucial asupra durabilitii mantalei externe de protecie. Cnd decidem o acoperire minim, trebuie avut n vedere posibilitatea deteriorrii de la lucrrile de construcie ulterioare, de pe parcursul ntregii durate de via a construciei. Materialul de umplere trebuie compactat n straturi, i trebuie folosit un utilaj pentru aceasta pentru un strat de acoperire de 500 mm grosime. Cnd acest lucru a fost fcut, aezai o band de avertizare i acoperii anul. Cnd acoperii cu un strat de grosime de la 0.5 metri pn la maxim 6 metri,

Flexibilitatea evilor Uponor permite adaptarea fr probleme la teren, fr nici o condiie de traseu. Este posibil s dirijm traseul deasupra sau pe sub evi existente n timp ce obstacolele pot fi simplu ocolite. Chiar i aezarea sistemului de evi sub o pnz de ap freatic de 3 metri (0.3 bar) este permis. Sistemul necesit doar excavarea unui an ngust de adncime mic. Amplasarea nu necesit n mod normal ca un operator s fie n an, cu execpia locurilor unde se fac racorduri sau ramificaii. La locul racordurilor i ramificaiilor, trebuie creat un spaiu de lucru potrivit pentru operaiile respective. Oriunde direcia evii se schimb, raza de curbur trebuie s nu fie mai mic dect minimul permis de diversele sisteme de evi. Este convenabil s executm toate excavaiile pe o parte a anului. eava este apoi derulat de la captul

mantaua extern de protecie Uponor poate suporta sarcina solului i a traficului. Certificarea bazat pe ATV DVWK-A127, demonstreaz c evile noastre, dac sunt amplasate conform condiiilor prescrise, pot suporta sarcini ale traficului greu (SWL60 = 60t) conform cu pagina de lucru ATV-A 127. Inelele de rigidizare ale mantalei externe de protecie sunt testate conform EN ISO 9969.

Acoperire an minim fr sarcina de trafic

Acoperire an cu sarcin de trafic conform SLW 60

Toate dimensiunile n mm

min. 0,5 m max 6,0 m

Atenie ! Nu s-a inut cont de limitele locale de nghe .

20

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Exemple de instalare
6

5 1

2 1 Conectare cu Thermo Twin

 lternativ: Tub perete , rezistent la ap A sub presiune (PWP) Numr necesar 1

 Alternativ: Tub perete, rezistent la ap B fr presiune (NPW) Produs Kit trecere Uponor NPW Uponor Thermo Twin Numr necesar 1

 lternativ: Tub perete , rezistent la ap A sub presiune (PWP) Numr necesar

Produs Uponor Thermo Twin

Produs eav Uponor fibr ciment *) Uponor Thermo Twin

1
1 1 1 2 2

Cciuli de capt Uponor Twin Racord cu Uponor 6 bar Racord Uponor filet interior Etanare trecere Uponor
1 1 1

Cciuli de capt Uponor Twin Racord adaptor Uponor 6 bar Racord Uponor filet interior

1 2 2

Garnitur perete Uponor PWP Kit suplimentar Uponor PWP *) Cciuli de capt Uponor Twin Racord adaptor Uponor 6 bar Racord Uponor filet interior *) optional, verificai necesitatea

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

21

Conectare cu Thermo Single

Circuit tur pentru nclzire la o cldire auxiliar cu Quattro

Tub pt. doi perei, nepresurizat la ap(NPW) Produs Uponor Thermo Single Cciuli de capt Uponor, Single Niplu Uponor de conversie 6 bar Racord Uponor filet interior Kit trecere Uponor 2 2 2 2 Numr necesar

Tub pt.doi perei, presurizat (PWP), nclzire (tur+retur), ap rece i cald sau ap cald i recirculat Produs Tub ciment Uponor PWP *) Uponor Quattro Tub perete Uponor PWP Cciuli de capt Uponor Quattro Kit suplimentar Uponor DWD *) Niplu Uponor de conversie 6 bar Niplu Uponor conversie10 bar Racord Uponor filet interior 2 2 2 4 4 8 2 Numr necesar

Ramificaie din Thermo Single cu evi Thermo Twin ramificaie cu set de izolare H
Numr necesar

Produs Uponor Thermo Single Uponor Thermo Twin Set izolator Uponor H Cciuli de capt Uponor, Single Cciuli de capt Uponor, Twin Niplu Uponor conversie 6 bar Racord T Uponor Reducie Uponor *)

1 4 1 6 2

Ramificaii Thermo Twin cu set de izolare T

Racorduri Thermo Twin cu set de izolare drept

Ramificaie din Thermo Single la Thermo Twin

Produs Uponor Thermo Twin Set izolator Uponor n T Cciuli de capt Uponor, Twin Niplu Uponor conversie 6 bar Racord T Uponor Reducie Uponor *)

Numr necesar

Produs Uponor Thermo Twin

Numr necesar

Produs Uponor Thermo Single

Numr necesar

1 3 6 2

Kit izolator Uponor drept Cciuli de capt Uponor , Twin Niplu Uponor conversie 6 bar Muf Uponor filet exterior

1 2 4 2

Uponor Thermo Twin Cmin Uponor Cciuli de capt Uponor, Single 4 Cciuli de capt Uponor, Twin Niplu Uponor conversie 6 bar Racord T Uponor Reducie Uponor *) Cot Uponor *) Conectai eava dac este necesar, eav sau niplu dublu (rspunderea clientului) 2 8 4 1

*) optional, verificai dac e necesar

22

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Dimensionarea evilor de nclzire


Tabel pentru pierderi de presiune
eav nclzire : Bazat pe 50 C temperatura apei*
Debit Volumetric
l/h 36 72 108 144 180 216 252 288 324 360 720 1080 1440 1800 2160 2520 2880 3240 3600 3960 4320 5040 5760 6480 7200 7920 8640 9360 10080 10800 12600 14400 16200 18000 19800 21600 23400 25200 27000

DIM: di [mm]:

25 x 2,3 20,4
kPa/m m/s

32 x 2,9 26,2
kPa/m m/s

40 x 3,7 32,6
kPa/m m/s

50 x 4,6 40,8
kPa/m m/s

63 x 5,8 51,4
kPa/m m/s

75 x 6,8 61,4
kPa/m m/s

90 x 8,2 73,6
kPa/m m/s

110 x 10 90,0
kPa/m m/s

l/s

0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 3,5 4 0,020 0,153 0,028 0,184 0,037 0,214 0,047 0,245 0,058 0,275 0,071 0,306 0,244 0,612 0,507 0,918 0,850 1,224 1,270 1,530 1,765 1,836 2,330 2,142 2,966 2,448 3,668 2,754 4,438 3,059 5,272 3,365 6,171 3,671 8,156 4,283 10,388 4,895 12,859 5,507 15,566 6,119 18,504 6,731 21,670 7,343 25,060 7,955 28,671 8,567 32,500 9,178 0,020 0,069 0,143 0,239 0,358 0,496 0,655 0,834 1,031 1,247 1,481 1,733 2,290 2,916 3,609 4,367 5,190 6,077 7,026 8,037 9,109 0,185 0,371 0,024 0,240 0,556 0,049 0,359 0,742 0,082 0,479 0,927 0,122 0,599 1,113 0,169 0,719 1,298 0,223 0,839 1,484 0,284 0,958 1,669 0,351 1,078 1,855 0,425 1,198 2,040 0,504 1,318 2,226 0,590 1,438 2,597 0,779 1,677 2,968 0,992 1,917 3,339 1,227 2,156 3,710 1,485 2,396 4,081 1,764 2,636 4,452 2,065 2,875 4,823 2,387 3,115 5,194 2,730 3,355 5,565 3,094 3,594 0,028 0,306 0,041 0,382 0,058 0,459 0,076 0,535 0,097 0,612 0,119 0,688 0,144 0,765 0,171 0,841 0,200 0,918 0,265 1,071 0,337 1,224 0,417 1,377 0,504 1,530 0,599 1,683 0,701 1,836 0,810 1,989 0,926 2,142 1,049 2,295 1,388 2,677 1,768 3,059 2,189 3,442 2,650 3,824 3,151 4,207 3,690 4,589 4,268 4,972 4,884 5,354 5,537 5,737 0,032 0,386 0,039 0,434 0,047 0,482 0,056 0,530 0,066 0,578 0,087 0,675 0,111 0,771 0,137 0,867 0,166 0,964 0,197 1,060 0,230 1,157 0,266 1,253 0,304 1,349 0,345 1,446 0,456 1,687 0,580 1,928 0,718 2,169 0,869 2,410 1,033 2,651 1,210 2,892 1,399 3,133 1,601 3,374 1,815 3,614 0,028 0,405 0,037 0,473 0,047 0,540 0,058 0,608 0,071 0,675 0,084 0,743 0,098 0,811 0,114 0,878 0,130 0,946 0,147 1,013 0,194 1,182 0,247 1,351 0,306 1,520 0,370 1,689 0,440 1,858 0,516 2,026 0,596 2,195 0,682 2,364 0,773 2,533 0,024 0,423 0,030 0,470 0,035 0,517 0,041 0,564 0,047 0,611 0,054 0,658 0,061 0,705 0,081 0,823 0,103 0,940 0,128 1,058 0,154 1,175 0,184 1,293 0,215 1,410 0,248 1,528 0,284 1,645 0,322 1,763 0,023 0,472 0,031 0,550 0,039 0,629 0,049 0,707 0,059 0,786 0,070 0,865 0,082 0,943 0,095 1,022 0,108 1,100 0,123 1,179

43,015 10,708 12,051 6,492 4,092 4,193 54,847 12,238 15,360 7,419 5,214 4,792 19,029 8,347 6,458 5,391 23,050 9,274 7,821 5,990 27,418 10,202 9,301 6,589 32,127 11,129 10,896 7,188 37,172 12,056 12,604 7,787 14,425 8,386 16,357 8,985

4,5 5 5,5 6 6,5

7 7,5

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

23

eav nclzire : Bazat pe 50 C temperatura apei*


Debit Volumetric
l/h 228800 30600 32400 34200 36000 37800 39600 43200 46800 50400 54000 57600 61200 64800 68400 72000 79200 86400 93600 100800 108000 115200 122400 129600 136800 144000 162000 180000 198000 216000 234000 252000 270000 288000

DIM: di [mm]

25 x 2,3 20,4
kPa/m m/s

32 x 2,9 26,2
kPa/m m/s

40 x 3,7 32,6
kPa/m m/s 18,398 9,584

50 x 4,6 40,8
kPa/m m/s 6,227 6,119 6,501 6,884 7,266 7,649

63 x 5,8 51,4
kPa/m m/s 2,041 3,855 2,279 4,096 2,528 4,337 2,790 4,578 3,062 4,819 3,347 5,060 3,643 5,301 4,268 5,783 4,939 6,265 5,653 6,747 6,412 7,229 7,213 7,711 8,057 8,193 8,944 8,675 9,872 9,157 10,842 9,639 12,906 10,602 15,132 11,566 17,520 12,530

75 x 6,8 61,4
kPa/m m/s 0,869 2,702 0,970 2,871 1,076 3,040 1,187 3,208 1,303 3,377 1,424 3,546 1,550 3,715 1,816 4,053 2,101 4,391 2,405 4,728 2,727 5,066 3,067 5,404 3,426 5,741 3,802 6,079 4,197 6,417 4,609 6,755 5,485 7,430 6,430 8,106 7,443 8,781 8,523 9,457 9,670 10,132 10,883 10,807 12,161 11,483 13,503 12,158

90 x 8,2 73,6
kPa/m m/s 0,362 1,880 0,404 1,998 0,448 2,115 0,495 2,233 0,543 2,350 0,593 2,468 0,646 2,586 0,756 2,821 0,875 3,056 1,001 3,291 1,135 3,526 1,277 3,761 1,426 3,996 1,582 4,231 1,746 4,466 1,917 4,701 2,281 5,171 2,674 5,641 3,095 6,111 3,544 6,581 4,020 7,051 4,523 7,522 5,054 7,992 5,611 8,462 6,195 8,932 6,805 9,402 8,444 10,577 10,243 11,752 12,200 12,928

110 x 10 90,0
kPa/m m/s 0,138 1,258 0,154 1,336 0,171 1,415 0,188 1,493 0,207 1,572 0,226 1,650 0,246 1,729 0,288 1,886 0,333 2,043 0,381 2,201 0,431 2,358 0,485 2,515 0,542 2,672 0,601 2,829 0,663 2,987 0,728 3,144 0,866 3,458 1,015 3,773 1,175 4,087 1,345 4,401 1,525 4,716 1,716 5,030 1,917 5,344 2,128 5,659 2,350 5,973 2,581 6,288 3,201 7,074 3,883 7,860 4,623 8,645 5,423 9,431 6,281 10,217 7,196 11,003 8,167 11,789 9,195 12,575

l/s

8 8,5 9 9,5 10

20,548 10,183 6,954 22,806 10,782 7,717 25,170 11,381 8,516 27,639 11,980 9,350

10,5 11 12 13 14 15 16

10,220 8,031 11,125 8,414 13,038 9,178 15,089 9,943 17,275 10,708 19,595 11,473 22,048 12,238

17 18 19 20 22 24 26

28 30 32 34 36

38 40 45 50 55

60 65 70 75 80

*Factori corecie pierdere presiune pentru alte temperaturi ale apei


C Factor 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95

1,217 1,183 1,150 1,117 1,100 1,067 1,050 1,017 1,000 0,983 0,967 0,952 0,938 0,933 0,918 0,904 0,890 0,873

24

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Diagram de pierderi de presiune


m/s 12,00 10,00

Nomograma este calculat la o temperatur a agentului termic de +70C *


kPa/m 10 7 6 5 4 3 2 5,00 4,00 7,00 6,00

1 0,7 0,6 0,5 0,4 3,00 2,50

,3

x2

0,3 0,2

2,00

25

x2

1,75

,9 ,7

x3

1,50

32

40

,6

x4

50

x6

63

0,1 0,07 0,06 0,05 0,04 0,03 0,02

x5

,8

1,25

,8

75

x8

.2

1,00

90

110
0,60 0,50 0,40 0,30 0,25 0,20 0,15 0,10 0,07 0,06 0,05 0,04 0,03 0,02 0,02 0,03 0,05 0,07 0,1 0,04 0,06 0,2 0,3 0,5 0,7 0,4 0,6 1 2 3 5

0,01 0,007 0,006 0,005 0,004 0,003 0,002

0,001 0,0007 0,0006 0,0005 0,0004 0,0003 0,0002

0,0001 0,01

x1

0,0
7

10

20

30

40

50 70 60

100 l/s

*Factori corecie pierdere presiune pentru alte temperaturi ale apei


Temperatur C Factor 90 0,95 80 0,98 70 1,00 60 1,02 50 1,05 40 1,10 30 1,14 20 1,20

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

25

Bazele dimensionrii instalaiilor de nclzire


exist limitri pentru viteza apei, deoarece evile din plastic nu se erodeaz. Domeniul de pierderi de presiune recomandate a fost nnegrit. Diagrama include valorile nominale 20, 45 i 30 pentru schimbri ale unde = debitul de mas kg/s m Q = puterea termic KW
temperatura +55C

Dac este necesar, folosirea unei pierderi de presiune pe metru considerabil mai mari, este mai degrab posibil cnd dimensionm evi din plastic pentru nclzire, dect atunci cnd dimensionm evi de oel. Nu = m Q cp

temperaturii. Mrimea poate fi de asemenea selectat funcie de debitul masic. Debitul masic necesar poate fi calculat cu formula:

= Diferena de temperatur C cp = cldura specific a apei 4,19 kJ/kgK

incl. 20% rezistena la frecare pentru ting .Coe cientul rugozitate eav PEX 0. .005 m

1,5 1,0 0,8 0,6 0,5 0,4 0,3 0,2


/1
v= 3,0

3, 0

Pierderea de presiune R [kPa/m]

18

m/ s

0, 4

25

32

/2

6, 0

2, 0

/2

2, 6

40

1, 5

/3

1, 2

63

0,1 0,08 0,06 0,05 0,04 0,03 0,02 0,02 1,0 3 1,5 2 2 0,03 3 0,05 0,1 0,2
0, 3

50

/4 /5 1, 4

0, 8

/6

75

/7

3, 6

1, 0

90

11
0, 5

0/

10

,0

0,3 0,4 0,5 20 30 40 50 100 100

1,0 100 200 300 200

2 200

4 5 6 7 8 10 12 300 500 1000 500 1500 1000

[kg/s] m Q [kW], = 20 K Q [kW], = 45 K Q [kW], = 30 K

4 5 6 7 8 10 20

4 5 6 7 8 10 3 4 5 6 7 8 10

30 40 50 20 30 40 50

500 300

Exemplu de dimensionare : Obiectivul este selectarea evilor de nclzire pentru nclzire i a spaiului pentru centrala termic. Suprafaa unei cldiri este de 300 m i nlimea camerelor este de 2.9 m. Cldirea are nclzire cu radiatoare normale cu temperatura apei pe tur de 1 = +70C i pe retur de 2= +40C.

Pasul 1. Determin necesarul puterii termice (volumul cldirii x necesarul specific de cldur). F = 300 m x 2.9 m x 25 W/m= 21 750 W 22 kW Pasul 2. Determin correct -axle sau debitul masic . = (1 2)=30 K

Pasul 3. Selecteaz dimensiunea corect a evii din zona pierderile de presiune recomandate conform diagramei = 30 K i Q = 22 kW= mrime eav 25/20.4 mm Necesar specific de cldur [W/m]
Casa Casa Cldire cu unifamilial cu teras apartamente 15 22 22 26 15 26 15 26 15 20 nou 20 28 veche

26

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Tabel de dimensionare rapid

eav de nclzire
Domeniu (ecart de temperatur) = 10 K = 15 K = 20 K = 25 K = 30 K = 35 K = 40 K Debit de mas
10 kW 15 kW 20 kW 25 kW 30 kW 35 kW 40 kW 860 kg/h 20 kW 30 kW 40 kW 50 kW 60 kW 70 kW 80 kW 1720 kg/h 30 kW 45 kW 60 kW 75 kW 90 kW 105 kW 120 kW 2580 kg/h 40 kW 60 kW 80 kW 100 kW 120 kW 140 kW 160 kW 3440 kg/h 50 kW 75 kW 100 kW 125 kW 150 kW 175 kW 200 kW 4300 kg/h 60 kW 90 kW 120 kW 150 kW 180 kW 210 kW 240 kW 5160 kg/h 70 kW 105 kW 140 kW 175 kW 210 kW 245 kW 280 kW 6020 kg/h 80 kW 120 kW 160 kW 200 kW 240 kW 280 kW 320 kW 6880 kg/h 90 kW 135 kW 180 kW 225 kW 270 kW 315 kW 360 kW 7740 kg/h 100 kW 150 kW 200 kW 250 kW 300 kW 350 kW 400 kW 8600 kg/h 110 kW 165 kW 220 kW 275 kW 330 kW 385 kW 440 kW 9460 kg/h 120 kW 180 kW 240 kW 300 kW 360 kW 420 kW 480 kW 10320 kg/h 130 kW 195 kW 260 kW 325 kW 390 kW 455 kW 520 kW 11180 kg/h 140 kW 210 kW 280 kW 350 kW 420 kW 490 kW 560 kW 12040 kg/h 150 kW 225 kW 300 kW 375 kW 450 kW 525 kW 600 kW 12900 kg/h 160 kW 240 kW 320 kW 400 kW 480 kW 560 kW 640 kW 13760 kg/h 170 kW 255 kW 340 kW 425 kW 510 kW 595 kW 680 kW 14620 kg/h 180 kW 270 kW 360 kW 450 kW 540 kW 630 kW 720 kW 15480 kg/h 190 kW 285 kW 380 kW 475 kW 570 kW 665 kW 760 kW 16340 kg/h

Tip eav p,v


25/20.4 0,30974 kPa/m 0,74962 m/s 32/26.2 0,32917 kPa/m 0,92296 m/s 32/26.2 0,66923 kPa/m 1,38445 m/s 40/32.6 0,37806 kPa/m 1,17416 m/s 50/40.8 0,19244 kPa/m 0,93702 m/s 50/40.8 0,26445 kPa/m 1,12443 m/s 50/40.8 0,34945 kPa/m 1,31183 m/s 63/51.4 0,14654 kPa/m 0,94464 m/s 63/51.4 0,18133 kPa/m 1,06272 m/s 63/51.4 0,21940 kPa/m 1,18080 m/s 63/51.4 0,26071 kPa/m 1,29888 m/s 75/61.2 0,13183 kPa/m 0,99949 m/s 75/61.2 0,15238 kPa/m 1,08278 m/s 75/61.2 0,17427 kPa/m 1,16608 m/s 75/61.2 0,19746 kPa/m 1,24937 m/s 75/61.2 0,22196 kPa/m 1,33266 m/s 90/73.6 0,10196 kPa/m 0,97903 m/s 90/73.6 0,11308 kPa/m 1,03662 m/s 90/73.6 0,12472 kPa/m 1,09421 m/s

Tip eav p, v
32/26.2 0,09786 kPa/m 0,46148 m/s 40/32.6 0,11240 kPa/m 0,58708 m/s 40/32.6 0,22851 kPa/m 0,88062 m/s 50/40.8 0,13023 kPa/m 0,74962 m/s 63/51.4 0,06425 kPa/m 0,59040 m/s 63/51.4 0,08839 kPa/m 0,70848 m/s 63/51.4 0,11513 kPa/m 0,82656 m/s 75/61.2 0,06334 kPa/m 0,66633 m/s 75/61.2 0,07836 kPa/m 0,74962 m/s 75/61.2 0,09480 kPa/m 0,83291 m/s 75/61.2 0,11263 kPa/m 0,91620 m/s 90/73.6 0,05429 kPa/m 0,69108 m/s 90/73.6 0,06274 kPa/m 0,74867 m/s 90/73.6 0,07174 kPa/m 0,80626 m/s 90/73.6 0,08129 kPa/m 0,86385 m/s 90/73.6 0,09136 kPa/m 0,92144 m/s 110/90.0 0,03874 kPa/m 0,65473 m/s 110/90.0 0,04296 kPa/m 0,69325 m/s 110/90.0 0,04738 kPa/m 0,73176 m/s

Tip eav p, v

50/40.8 0,03872 kPa/m 0,37481 m/s 50/40.8 0,07872 kPa/m 0,56221 m/s 63/51.4 0,04348 kPa/m 0,47232 m/s 75/61.2 0,02805 kPa/m 0,41646 m/s 75/61.2 0,03859 kPa/m 0,49975 m/s 75/61.2 0,05053 kPa/m 0,58304 m/s 90/73.6 0,02657 kPa/m 0,46072 m/s 90/73.6 0,03266 kPa/m 0,51831 m/s 90/73.6 0,03905 kPa/m 0,57590 m/s 90/73.6 0,04639 kPa/m 0,63349 m/s 110/90.0 0,02064 kPa/m 0,46217 m/s 110/90.0 0,02385 kPa/m 0,50068 m/s 110/90.0 0,02727 kPa/m 0,53919 m/s 110/90.0 0,03089 kPa/m 0,57771 m/s 110/90.0 0,03472 kPa/m 0,61622 m/s

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

27

eav de nclzire
Domeniu (ecart de temperatur) = 10 K = 15 K = 20 K = 25 K = 30 K = 35 K = 40 K Debit de mas Tip eav p,v Tip eav p, v Tip eav p, v

200 kW 300 kW 400 kW 500 kW 600 kW 700 kW 800 kW 17200 kg/h 210 kW 315 kW 420 kW 525 kW 630 kW 735 kW 840 kW 18060 kg/h 220 kW 330 kW 440 kW 550 kW 660 kW 770 kW 880 kW 18920 kg/h 230 kW 345 kW 460 kW 575 kW 690 kW 805 kW 920 kW 19780 kg/h 240 kW 360 kW 480 kW 600 kW 720 kW 840 kW 960 kW 20640 kg/h 250 kW 375 kW 500 kW 625 kW 750 kW 875 kW 1000 kW 21500 kg/h 260 kW 390 kW 520 kW 650 kW 780 kW 910 kW 1040 kW 22360 kg/h 270 kW 405 kW 540 kW 675 kW 810 kW 945 kW 1080 kW 23220 kg/h 280 kW 420 kW 560 kW 700 kW 840 kW 980 kW 1120 kW 24080 kg/h 290 kW 435 kW 580 kW 725 kW 870 kW 1015 kW 1160 kW 24940 kg/h 300 kW 450 kW 600 kW 750 kW 900 kW 1050 kW 1200 kW 25800 kg/h 310 kW 465 kW 620 kW 775 kW 930 kW 1085 kW 1240 kW 26660 kg/h 320 kW 480 kW 640 kW 800 kW 960 kW 1120 kW 1280 kW 27520 kg/h 330 kW 495 kW 660 kW 825 kW 990 kW 1155 kW 1320 kW 28380 kg/h 340 kW 510 kW 680 kW 850 kW 1020 kW 1190 kW 1360 kW 29240 kg/h 350 kW 525 kW 700 kW 875 kW 1050 kW 1225 kW 1400 kW 30100 kg/h

90/73.6 110/90.0 0,13687 kPa/m 0,05199 kPa/m 1,15180 m/s 0,77028 m/s 90/73.6 110/90.0 0,14953 kPa/m 0,05680 kPa/m 1,20939 m/s 0,80879 m/s 90/73.6 110/90.0 0,16269 kPa/m 0,06179 kPa/m 1,26698 m/s 0,84730 m/s 90/73.6 110/90.0 0,17635 kPa/m 0,06697 kPa/m 1,32457 m/s 0,88582 m/s 90/73.6 110/90.0 0,19051 kPa/m 0,07234 kPa/m 1,38216 m/s 0,92433 m/s 110/90.0 0,07790 kPa/m 0,96285 m/s 110/90.0 0,08364 kPa/m 1,00136 m/s 110/90.0 0,08956 kPa/m 1,03987 m/s 110/90.0 0,09567 kPa/m 1,07839 m/s 110/90.0 0,10196 kPa/m 1,111690 m/s 110/90.0 0,10843 kPa/m 1,15541 m/s 110/90.0 0,11507 kPa/m 1,19393 m/s 110/90.0 0,12190 kPa/m 1,23244 m/s 110/90.0 0,12890 kPa/m 1,27096 m/s 110/90.0 0,13608 kPa/m 1,30947 m/s 110/90.0 0,14344 kPa/m 1,34798 m/s

28

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Pierderea de cldur
Conductivitate termic a solului : Grosime strat acoperire a evii n an : 1,0 W/mK 0,8 m

Pierderi de cldur la eava Uponor Thermo Single

Not: Pierderile de cldur din diagram sunt calculate cu un factor de siguran de 1,05 conform cu cerinele normei germane "VDI-AG Gtesicherung". Ele depind de toleranele din producie.
50 45 40 35 90/200 30 25 20 15 10 5 0 75/200 63/175

110/200

Pierderi de cldur [W/m]

50/175 40/175 32/140 25/140

10

30

50

70

90

Diferena de temperatur [K ]

Exemplu pentru Uponor Thermo Single 50/175 M = Temperatur mediu E = Temperatur sol = Diferen de temperatur (K) = M E M = 75 C E = 5 C = 75 5 = 70 K Pierderi cldur: 15,75 W/m

6 V 047

Not Diagrama arat pierderea de cldur pe o eav. Pierderile de cldur pe tur i retur trebuie calculate separat. Pentru a obine pierderile totale, adunai pierderile pe tur i retur.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

29

Pierderile de cldur la eava Uponor Thermo Twin Conductivitate termic a solulului : Grosime strat acoperire a evii n an: 1,0 W/mK 0,8 m

Not Datele despre pierderile de cldur din diagram sunt calculate cu un coeficient de siguran de 1,05 conform cu norma german "VDI-AG Gtesicherung". Ele depind de toleranele de producie comunicate.
45

40 2 x 63/200 35

Pierdri cldur [W/m]

30

2 x 50/200 2 x 40/175

25 2 x 32/175 20 2 x 25/175

15

10

10

30

50

70

90

Diferen temperatur [K]

Exemplu pentru Uponor Thermo Twin 2 x 32/175 V = Temperatur tur R = Temperatur retur E = Temperatur sol = Diferena de temperatur (K) = (qV qR)/ 2 qE V = 70 C R = 30 C E = 5 C = (70 + 40)/2 5 = 50 K Pierderi de cldur : 12,50 W/m

6 V 047

30

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Dimensionarea evilor pentru ap cald


Tabelul pierderilor de presiune


DIM: ID [mm] 25 x 3,5 18
kPa/m m/s

eav pentru ap : Bazat pe temperatura apei de 50 C *


l/h

Debit de volum

32 x 4,4 23,2
kPa/m m/s

40 x 5,5 29
kPa/m m/s

50 x 6,9 36,2
kPa/m m/s

63 x 8,7 45,6
kPa/m m/s

l/s

6 72 108 144 180 216 252 288 324 360 720 1080 1440 1800 2160 2520 2880 3240 3600 3960 4320 5040 5760 6480 7200 7920 8640 9360 10080 10800 12600 14400 16200 18000 19800 21600 23400 25200 27000 28800 30600 32400 34200 36000 37800 39600 43200 46800 50400

0,01 0,02 0,03 0,04 0,05 0,036 0,196 0,06 0,050 0,236 0,07 0,065 0,275 0,08 0,083 0,314 0,09 0,103 0,354 0,1 0,124 0,393 0,037 0,237 0,2 0,429 0,786 0,127 0,473 0,043 0,303 0,3 0,890 1,179 0,263 0,710 0,089 0,454 0,031 0,291 0,4 1,494 1,572 0,442 0,946 0,150 0,606 0,051 0,389 0,5 2,233 1,965 0,660 1,183 0,224 0,757 0,076 0,486 0,6 3,103 2,358 0,917 1,419 0,311 0,908 0,106 0,583 0,034 0,7 4,098 2,751 1,210 1,656 0,410 1,060 0,140 0,680 0,045 0,8 5,215 3,144 1,540 1,892 0,522 1,211 0,178 0,777 0,058 0,9 6,452 3,537 1,905 2,129 0,645 1,363 0,220 0,874 0,071 1 7,806 3,930 2,304 2,366 0,780 1,514 0,266 0,972 0,086 1,1 9,275 4,323 2,737 2,602 0,927 1,665 0,316 1,069 0,102 1,2 10,857 4,716 3,203 2,839 1,084 1,817 0,370 1,166 0,120 1,4 4,233 3,312 1,433 2,120 0,489 1,360 0,158 1,6 5,390 3,785 1,824 2,422 0,622 1,555 0,201 1,8 6,672 4,258 2,257 2,725 0,769 1,749 0,248 2 8,075 4,731 2,731 3,028 0,931 1,943 0,301 2,2 9,598 5,204 3,245 3,331 1,106 2,138 0,357 2,4 11,239 5,677 3,799 3,634 1,294 2,332 0,418 2,6 4,392 3,936 1,496 2,526 0,483 2,8 5,024 4,239 1,711 2,721 0,552 3 5,694 4,542 1,939 2,915 0,626 3,5 7,532 5,299 2,564 3,401 0,827 4 9,599 6,056 3,266 3,886 1,053 4,5 11,890 6,813 4,045 4,372 1,304 5 4,898 4,858 1,579 5,5 5,824 5,344 1,877 6 6,823 5,830 2,198 6,5 7,892 6,315 2,542 7 9,032 6,801 2,908 7,5 10,240 7,287 3,297 8 3,708 8,5 4,140 9 4,594 9,5 5,069 10 5,566 10,5 6,083 11 6,621 12 7,759 13 8,979 14 10,279

0,367 0,429 0,490 0,551 0,612 0,674 0,735 0,857 0,980 1,102 1,225 1,347 1,470 1,592 1,715 1,837 2,143 2,449 2,755 3,062 3,368 3,674 3,980 4,286 4,592 4,899 5,205 5,511 5,817 6,123 6,429 6,736 7,348 7,960 8,573

*Factori corecie pierdere presiune pentru alte temperaturi ale apei


C Factor 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95

1,208 1,174 1,144 1,115 1,087 1,060 1,039 1,019 1,000 0,982 0,965 0,954 0,943 0,928 0,923 0,907 0,896 0,878

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

31

Diagram pierderi de presiune

Diagrama pierderilor de presiune prin evi de ap la 70 *


kPa/m 10 7 6 5 4 3 2 5,00 4,00 6,00 m/s

1 0,7 0,6 0,5 0,4 0,3 0,2

18

x2

3,00

,5

x4

,0 ,4

32

x5

2,00 1,75

28

x4

,5

40

x6

,9

1,50

50

x8

1,25

,7 63 x1 0,3

75

x1

2,4

0,1 0,07 0,06 0,05 0,04 0,03 0,02

1,00

0,40 0,01 0,007 0,006 0,005 0,004 0,003 0,002 0,10 0,001 0,0007 0,0006 0,0005 0,0004 0,0003 0,0002 0,07 0,06 0,05 0,04 0,03 0,02 0,01 0,02 0,03 0,05 0,07 0,1 0,04 0,06 0,2 0,3 0,5 0,7 0,4 0,6 1 2 3 4 5 6 7 10 20 30 40 50 70 60 100 l/s 0,30 0,25 0,20 0,15

0,0001

*Factori corecie pierdere presiune pentru alte temperaturi ale apei


Temperatur C Factor 90 0,95 80 0,98 70 1,00 60 1,02 50 1,05 40 1,10 30 1,14 20 1,20

32

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

110
0,60 0,50

x1

90

5,1

Instalare

Ghid de valori pentru procesul de instalare


Timpul necesar pentru instalarea acestor sisteme de evi depinde de condiiile locale. n tabelul urmtor, obstacolele, subtraversrile, condiiile meteo, timpii de montaj pentru fitinguri, i alte Timp instalare
Tip eav Single: 25 32 40 50 63 75 90 110 Twin: 25 32 40 50 63 Quattro: 25 Metri instalator/minute 2 / 15 2 / 15 2 / 20 2 / 20 3 / 20 3 / 25 3 / 30 3 / 30 2 / 20 2 / 20 2 / 30 3 / 25 3 / 30 2 / 30 50 Metri instalator/minute 2 / 30 2 / 30 2 / 40 2 / 40 3 / 40 3 / 50 4 / 60 4 / 60 2 / 40 2 / 40 3 / 40 3 / 50 4 / 60 3 / 40 100 Metri instalator/minute 3 / 40 3 / 40 3 / 60 3 / 60 4 / 60 4 / 75 5 / 90 5 / 90 3 / 60 3 / 60 4 / 60 5 / 90 5 / 90 4 / 60

aspecte nu au fost luate n considerare. Folosirea unor utilaje cum sunt excavatoare sau vinciuri de cabluri nu a fost inclus n calcul.

Ghid valori orientative pentru timpul mediu de montaj echipamentele de racord i accessorii:
Numr instalatori / grup minute per bucata (de ex. 2/15 = 2 instalatori necesita 15 minute per bucata) Cciul de capt Uponor Racord niplu reducie Uponor Pies racordare Uponor Pies racord n T Uponor (complet) Set izolator drept Uponor Set izolator n T Uponor Set izolator pentru col Uponor Set izolator n H Coloana Uponor incl. 6 x conexiuni la mantaua exterioar de protecie Kit trecere Uponor ap nepresurizat NPW Canal trecere Uponor ap sub presiune PWP 1/5 1 / 15 2 / 30 2 / 40 1 / 35 1 / 45 1 / 35 2 / 50 2 / 50 1 / 30 1 / 30

Dou exemple pentru timpul mediu de montaj pentru evile Uponor : Examplu 1: Instalare a 2 x 25 m Uponor Thermo Single 63 mm 3 instalatori fr ajutoare suplimentare Timp instalare: 3 x 20 minute Examplu 2: Instalarea a unui kit trecere izolator NPW 1 instalator fr ajutoare suplimentare Ghid valori pentru Cciuli de capt 1/5, niplu conversie 1/15, set manon trecere perete set NPW 1/30 Timp instalare : 1 x 50 minutes

Timpii de instalare menionai n continuare sunt minute de grup pentru numrul corespunztor de instalatori (neincluznd lucrri de excavare). Cifrele sunt doar orientative pentru calcule.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

33

Manipularea evilor

Stocare, ridicare i manipulare colac eav Au fost montate capace de protecie la capetele evii, pentru a proteja evile interioare din PE-Xa fa de lumina soarelui sau alte deteriorri, inclusiv la umplere cu pmnt. Protejai colacul de eav de obiecte ascuite pe timpul transportului i depozitrii. Nu tri colacul pe suprafee rugoase. Asigurai-v c tamburul cu eav preizolat nu este strivit i eava nu este deformat prin ndoire pe timpul depozitrii. Pstrai colacii n poziie orizontal. Colacii de eav i camerele de racordare pot fi depozitate n spaii deschise, alte componente ale sistemului trebuie depozitate n spaii acoperite.

Folosii numai curele de transport aprobate, cu limea minim 50 mm

V rugm s reinei ! Cnd ridicai colacii de eav, folosii un cablu de nylon sau textile cu o lime de cel puin 50 mm. Dac ridicai colaci cu un ncrctor frontal cu furci sau cu un utilaj similar, furcile trebuie rotunjite sau cptuite. Datorit flexibilitii i masei colacilor, diametrul colacului poate varia cu 30 cm.

Ridicai colacii numai pentru scurt timp. Colacii trebuie asigurai mpotriva deplasrii

V rugm s reinei ! Masele plastice, nu trebuie niciodat s fie puse n contact cu substane agresive ca ulei de motor, solveni, conservani pentru lemn sau similare.

34

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Instalarea evii din colac


Pstrai colacii cu eav livrat pe ct de mult e posibil n ambalajul de protecie pn la instalare ! Apoi derulai eava direct n an sau lng el. apariia forelor de forfecare; dac este necesar, montai puncte fixe n jurul capetelor evii de oel. Dac lucrai la temperaturi extrem de joase, (rigiditatea evii este crescut), evile trebuie depozitate ntr-un spaiu nclzit sau trebuie efectuat montajul ntr-un spaiu nclzit dup care instalaia trebuie mutat direct n an. Derularea evii din colac de la interior (recomandat pentru evi cu mantaua de protecie cu diametre ntre 140 mm i 175 mm sau lungimi ale colacului de pn la 100m):

Fig. 1

Fig. 2

Atenie : Capetele evii din colac se pot desprinde cnd benzile textile sunt desfcute (vezi Fig. 1). De aceea asigurai-v ca spirele evii din colaci s fie tot timpul fixate cu dou-trei benzi. (vezi Fig. 2).

conectat!). Fixai capetele evii (de Nu detaai ambalajul exterior! Tiai ex. ngropndu-le sau acoperindu-le benzile de fixare din nylon. Scoatei Niciodat nu tragei eava de-a lungul cu nisip). Derulai colacul spir cu captul interior al evii din colac (nu solului pentru c obiecte ascuite pot spir. scoatei capacul de protecie al evii cauza deteriorarea. Dac mantaua se pn cnd aceasta nu este deterioreaz, poate fi reparat folosind un manon termocontractiv. Toate prile traseului evii i accesoriile siste- Derularea evii de la exterior (recomandat pentru eav cu mantaua extern de mului trebuie inspectate vizual naintea diametru 200 mm sau lungimi ale colacului de peste 100 m): instalrii sau reparate defectele care influeneaz funcionarea. Prile care sunt lovite grav, trebuie nlturate ! Dac eava va fi instalat orizontal n deschideri, ea trebuie plasat pe puncte de sprijin (ce folosesc nisip de exemplu) ce previn alunecarea ulterioar. Dac solul este denivelat, aceste puncte de sprijin trebuie prevzute la fiecare 25 metri. Cnd ngropm seciuni de eav, capetele cu lungimea de 3 pn la 5 metri trebuie lsate libere pentru montarea sistemelor de racordare. La schimbarea materialului evii din oel n mas plastic, forele de dilatare trebuie tranferate de la eava de oel la cea de mas plastic pe timpul schimbrilor de temperatur. n acest caz, se evit nlturai folia de ambalare. Desfacei prima band de nylon de la captul exterior al evii, desfacei captul evii din colac i fixai colacul cu restul spirelor cu banda de nylon. Atenie cnd desfacei prima band de nylon, captul evii este pretensionat i poate s v rneasc ! Fixai captul desfcut al evii (de ex. ngropndu-l sau punnd nisip peste el) i derulai mai departe pn la urmtoarea band de nylon. Repetai procesul pn cnd colacul este complet derulat.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

35

Raza de ndoire Graie structurii i materialului folosit, sistemele de eav flexibil preizolat sunt extraordinar de flexibile. Razele de ndoire minime permise sunt listate n tabelul urmtor i trebuie respectate cnd eava este montat:

Atenie : eava de PE-Xa se poate strangula sau poate fi distrus dac raza de ndoire este mai mic dect cea minim specificat.

Raze minime de ndoire n mm


Produs Uponor Thermo Single Uponor Thermo Twin Uponor Aqua Single Uponor Aqua Twin Uponor Quattro 25 250 500 350 650 800 32 300 600 400 700 800 40 350 800 450 900 50 450 1000 550 1000 63 550 1200 650 75 800 90 1100 110 1200

Instalare la temperaturi joase Nu este recomandat montajul evii la temperaturi de sub -15C. Pe vreme rece, montajul este mai uor dac evile sunt deja nclzite, fiind depoMontajul pe perete sau pe plafon evile pot fi de asemenea montate pe perete sau pe plafon, folosind coliere sau plasndu-le ntr-un canal de cabluri.
Diametru manta Interval maxim ntre OD[mm] puncte sprijin [m] 68 90 140 175 200 0,6 0,9 1,2 1,8 2,2

zitate de exemplu n prealabil n spaii nclzite. Pe antier, evile pot fi nclzite cu o suflant cu aer cald. nclzirea evilor deasupra unui foc

deschis este interzis.

n scopul prevenirii ndoirii evii, instalai colierele conform tabelului alturat. Tabelul stabilete intervalul maxim dintre punctele de sprijin pentru montaj orizontal i vertical n

scopul prevenirii atrnrii evii. Dac este necesar, intervalul dintre coliere poate fi scurtat.

36

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Ancorarea Dilatarea materialului duce la mici schimbri n lungimea evii de PE-Xa, de aceea colierele sau punctele fixe de sprijin trebuie s permit deplasri ale evii.

evile de dimensiuni mici (cu diametrele OD 50 mm) pot fi ancorate n mod normal de piesele de la racorduri). evile de dimensiuni mai mari (diametrele OD 50 mm) trebuie ancorate folosind un punct fix.

Fixare cot eav PE-Xa cu colier (OD 50 mm)

Fixare conector fix cu colier (OD > 50 mm)

V rugm s reinei ! Ancorarea nu se face pe mantaua exterioar a evii preizolate.

Schimbare lungime [mm/m]

Dilatarea termic De exemplu: la instalarea unei evi de ap cald, temperatura pe antier este de 20C. Cu ct se va dilata eava dac prin ea va circula ap cu temperatura de 70C ? Graficul arat c diferena de temperatur dintre 20C i 70C produce o elongaie termic de 12,5 2,5 = 10 mm/m.

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 10 20 30 40 50 60 70 80

Temperatur [C]

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

37

Instruciuni de montaj
industriale. Racordurile Uponor cu colier de strngere sunt folosite pentru diametre exterioare de 25-110 mm i presiuni ntre 6 i 10 bar. Combinaiile dintre fitinguri se creeaz folosind piese racord. Racordurile sunt etanate folosind garnituri O-ring, furnizate cu fitingurile.

Racorduri Uponor cu colier strngere Racordurile Uponor cu colier de strngere sunt un set complet de fitinguri care racordeaz evile Uponor PEX folosite n instalaiile sanitare i de nclzire i n anumite aplicaii
Piesele racordului cu colier de strngere Verificai dac locul garniturii o-ring este curat. Folosii numai o-ring-uri furnizate cu conectorii. Plasai o-ring-ul n canelur. Strngei toate prile manual la maxim. Strngei prile folosind o cheie de piulie sau un clete cu flci mici la partea de jos (metal pe metal). Cnd se monteaz alte piese la conectorii Uponor cu colier, sau la evi, conectorii cu filet trebuie strni cu in sau cnep.

Tiai eava la unghi drept folosind un clete special pentru eava de . plastic Reinei! Nu folosii un ferstru pentru c acesta poate lsa resturi n eav. Aceste resturi pot bloca robineii ulterior

nlturai resturile din interiorul evii folosind o u nealt special sau un cuit .

Scoatei colierul exterior de pe conector Scoatei urubul i lrgii colierul exterior folosind un . clete special

Plasai urubul ntre flcile colier ului exterior i mpingei colierul exterior pe eav

mpingei colierul exterior spre eav Reinei ! Verificai dac colierul a fost rotit n poziia corect ! Urechile colierului trebuie s se strng deasupra . Instalarea evii este uoar i O-ringul rmne nedeteriorat dac el este lubrifiat (de exemplu spray cu silicon )

eava este mpins spre umrul colierului pn cnd eava se oprete. Instalai colierul exterior astfel nct s poat fi montat urubul prin urechile colierului.

MoS

0 mm

Strngei fitingul Uponor. Ungei filetul urubului i aiba nainte de strngere. Folosii un tip indicat de unsoare cum este vaselina siliconic. Strngei piulia cu atenie folosind o cheie. Meninei urubul fix folosind o alt cheie cnd strngei urubul.

Strngei urubul astfel ca urechile colierului s se ating . Dac ele nu se ating, ateptai cel puin 30 minute nainte de a strnge din nou piulia.

38

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Fitingurile Uponor Q&E Sistemul Uponor Quick & Easy (Q&E) este bazat pe memoria materialului evii PEX Uponor, care face s-i revin la forma iniial dup ce a dilatat. Tehnica a fost patentat de Uponor i este destinat exclusiv folosirii cu Uponor PEX. Din aceast cauz, trebuie folosite numai piese originale Uponor. evile nu vor fi despachetate 1 naintea instalrii pentru a opri orice deteriorare sau probleme care pot aprea de la radiaia UV. Verificai dac evile nu sunt pline cu impuriti (fr praf, mortar i uleiuri). Capacele la presiune trebuie puse la capetele evii pentru a stopa impuritile s intre nuntru. Capacele trebuie s rmn la capetele evii ct de mult posibil. 2 1 2
proiecie ca. 1 mm (Dim. 16 25 mm) ca. 3 mm (Dim. 32 mm)

Pentru ca sistemul Uponor Quick & Easy s funcioneze perfect, trebuie respectate urmtoarele instruciuni de montaj :

3a
rotire/dilatare pai ( ecare max. 45)

0 mm

Operaia de dilatare folosind expanderul Uponor Q&E cu baterie

3b

rotire/dilatare pai ( ecare max. 45)

0 mm

Trebuie montat capul de expadare Uponor potrivit cu dimensiunile evii i tipul ei. Introducei capul de expandare drept ct de mult posibil n captul evii i mpingei maina spre eav. Pornii maina (inei apsat ntreruptorul). Imediat ce expanderul Uponor este deschis la maxim (se recunoate din sunetul specific), maina comut automat pe cursa de revenire i capul este din nou nchis. Dai drumul la ntreruptor din nou, tragei puin afar capul sculei din

eav, astfel ca flcile conului s se desprind de pereii evii. Rotii maina radial cu puin (maximum 45) i mpingei capul expanderului ct de mult putei n captul evii. Pornii maina. Repetai operaia de dilatare de cte ori este nevoie pentru ca flcile expanderului s fie introduse la limita maxim n eav. Apoi dilatai pentru ultima dat. Imediat trecei la punctul 4.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

39

Montare mpingei rapid eava pn la limit pe fiting. Meninei n aceast poziie eava pentru cteva secunde, pn cnd eava se strnge pe fiting.
0 mm Reinei ! Nu trebuie s e distan ntre eav i captul tingului

max. 10 Sec.

Instruciuni de montaj pentru sistemul UPONOR Quick&Easy Pentru ca sistemul UPONOR Quick & Easy s funcioneze perfect , trebuie urmrite urmtoarele instruciuni de montaj:

Pasul 1. Tierea evii Tiai eava n unghi drept cu un cuit adecvat. Captul evii trebui s fie curat i fr zgrieturi

Pasul 2. P  lasarea inelului Q&E pe eav mpingei inelul potrivit cu dimensiunile evii ca s alunece pe suprafaa evii pn la limit. Inelul este prevzut cu opritor pentru un montaj sigur i uor.

Pasul 3. Montarea fitingului Deschidei complet mnerele cletelui, plasai capul expandor n interiorul evii i apoi strngei braele pn sunt complet nchise. Rotii expandorul ( cu maxim 1/8 rotaii). ntre operaiile de lrgire scoatei expandorul i rotii capul astfel nct s se mite liber fr s ating pereii evii.

Lrgirea final Cnd inelul atinge marginea capului de expandare lrgirea trebuie s se opreasc. Dac instalaia a fost excutat ntr-o zon n care accesul este dificil, va fi necesar s meninei pentru maxim 3 secunde la ultima lrgire pentru a avea timp suficient de montare a fitingului.

Instalarea trebuie oprit atunci cnd temperatura ambientului este sub -15 C.

40

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Cciulile de capt Uponor Cciulile de capt se vor folosi ntotdeauna pentru capetele evii. Ele protejeaz izolaia contra umezelii i separ elementele evii preizolate. Montarea capacelor de la capetele evilor Punei capacele la capete naintea racordrii. 1 2
1.

V rugm reinei ! Respectai de asemenea instruciunile pentru seturile de izolaie Uponor. 3

2.

nlturai mantaua evii i izolaia astfel ca eava s fie vizibil suficient pentru a racorda capetele. Fii sigur c nu deteriorai eava de PEX. Curai suprafeele cu atenie.

Instalai garnitura pe al doilea inel.

Tiai ieirile cciulior de capt conform cu dimensiunea evii de PEX.

Instalai cciula de capt folosind un lubrifiant special

OI L
Montai colierul deasupra cciulii de capt i garniturii. .

Not: Montarea setului izolator Uponor

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

41

Setul izolator Uponor Examplu: Ramificaie n T Setul pentru ramificaie n T este destinat pentru izolaie i impermeabilizare la elementele branamentelor simple sau duble. Toate ramificaiile din set sunt de aceeai mrime. evile de mrimi diferite sunt impermeabilizate folosind inele reductoare. evile sunt conectate conform instruciunilor de pe conectori (vezi conectarea evii PEX). Cciulile de Instalare 1 T-eu (ramificaie n T)
OD L1

capt sunt montate nainte ca evile s fie racordate i previn intrarea umezelii n interiorul elementelor evii pe timpul unei posibile scurgeri din racord. Citii instruciunile de montaj cu atenie nainte de instalare. Verificai dac setul conine toate componentele din list.

V rugm s reinei ! Testul de presiune se face naintea etanrii setului.

Inel reductor Uponor

Set cciuli capt Uponor


1.

2.

L1

L1

L1

OD [mm] 140 175 200

L1 [mm] 300 400 500


150 m m

OD

nlturarea mantalei de protecie i izolaiei din jurul evii PEX . Avei grij s nu deteriorai eava de PEX !

(Numai pentru diametrele OD 68 i 90 mm)

Montai inelul de reducie pe eav dac este necesar

Montai capacele de protecie. Reinei ! Nu se folosesc cleme inel la fitingurile de la captul evii

Facei testul de presiune nainte de nchiderea setului izolator

L2

Tiai eava de PEX la lungimea dorit astfel ca lungimea evii neizolate s fie ct mai mic

Racordai evile de PEX. Lsai vizibil ct mai puin eav neizolat.

42

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

200 mm 175 mm 68/90/140 m m

90 mm 68 mm

Inel reducie
ntindei adeziv la capetele setului izolator, Folosii mas de ad eziv de asemenea ntre inelul reduct or i mantaua evii, n funcie de dimensiunea mantalei exterioare

ntindei masa adeziv pe custurile orizontale ale setului izolator i pe capetele evii.

Montai eava n setul izolator

9a

8 x 30 m m SW 13

nchidei cu grij setul izolator

Strngei cele dou pri ale setului izolator cu uruburi.

9b

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11 ... i xai-l mprejur cu dibluri cu autoblocare

43

Cminul de branament Uponor


Cminul de branament Uponor poate fi folosit pentru toate dimensiunile de eav (140200 mm). Cminul este disponibil n dou modele, n T i n X. Cciulile de capt sunt ntotdeauna folosite n cmin.

Pregtirea anului

Nivelai fundul anului cu nisip i compactai-l. Dac este nevoie montai o plac de ancorare sub stratul de nivelare.

Adncimea normal a capacului camerei este la 50 cm. O adncime de 30 cm este permis dac nu sunt plasate ncrcri directe deasupra camerei.

Instalarea camerei de racord Uponor 1 2 3

Tiai mufele exterioare ale cutie de racord, n funcie de mrimea cerut de eava exterioar pentru a face racordarea, 10-20 cm, depinznd de mrimea evii.

Punei cciulie de capt pe evi. Montai conectorii la capetele evilor de PEX.

mpingei eava prin conectori i n interiorul camerei. Strngei cciuliele de capt pe mantaua evii folosind cleme inelare. Conectai evile i strngei cuplajul.

evii.

Frecai cu glaspapir suprafaa racordului cminului n jurul manonului termocontractabil. Curai zona de racordare.

Prenclzii zona de sub manonul termocontractabil folosind o lamp cu gaz. Punei manonul termocontractabil la loc i tragei fermoarul.

Umplerea anului 7 8
120 mm
50 cm (min. 30 cm )

nclzii manonul cu o flacr uoar, conform instruciunilor de pe manonul termocontractabil ncepnd de la petecul de acoperire al fermoarului. nti nclzii captul manonului dinspre cmin. Mutai apoi flacra pe ntregul manon.

nchidei capacul cminului dar strngei uruburile dup ce eava a fost testat la presiune. ncepei umplerea anului tasnd nisip n jurul racordurilor.

ncepei umplerea anului folosind pietri. Avei grij s nu deteriorai manoanele termoizolante. Meninei camera n poziie vertical. Compactai umplutura n straturi de aprox. 20-30 cm Compactarea mecanic direct asupra camerei de racord este interzis.

Cazuri speciale : ncrcare trafic: O plac de beton poate fi folosit deasupra camerei pentru distribuirea sarcinii. Fr o plac de protecie, o camer instalat la o adncime de 50 cm poate suporta o

ncrcare ocazional pe termen scurt de 3,000 kg (= 6,000 kg/m; de exemplu, un tractor mergnd pe deasupra). ncrcarea pe termen lung este permis pentru sarcini sub 500 kg (= 1,000 kg/m; de exemplu pentru un

autoturism parcat). Dac apa freatic poate urca pn la nivelul camerei, utilizarea unei plci de ancorare este _ recomandat.

44

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Seturile de trecere Uponor(rezistente la ap nepresurizat) Pachetul de trecere este utilizat pentru a etana o trecere subtera n printr-un perete de beton. Manonul de trecere este turnat n beton la locul de traversare, permind instalarea evii ulterior. Manonul autocontractabil previne infiltrarea apei n fundaie, printre eav i manonul de trecere. Garniturile de etanare etaneaz eficient traversrile printr-o structur de beton i previn infiltarea umiditii n cldire. Instalarea unui manon de trecere 1a 1b

Instalai manonul n elementul de structur prin care va trec e eava i ulterior xai-l cu beton. Notai c cel puin 10 cm de manon de eav trebuie lsat la exteriorul peretelui.

2-3

Instalai manonul termocontractabil deasupra segmentului de eav. mpingei segmentul de eav prin manonul de trecere.

4-5

Plasai manonul termocontractabil la mijlocul racordului ntre manonul de trecere i mantaua evii i nlocuii orice hrtie care poate rmas n interiorul manonului termocontractabil. nclzii manonul termocontractabil cu un arztor cu gaz, cu o acr galben. Cnd suprafaa manonului termocontractabil devine neted i adezivul iese prin capete, manonul , a primit destul cldur. Instalarea este gata cnd manonul termocontractabil s-a rcit la temperatura mediului.

Instalarea unei treceri etane


1. Instalai manonul de trecere etan n mijlocul peretelui 2. Strngei manonul de trecere pe eav cu o clem. 3. Instalai eava la locul corect i nalizai betonarea structurii

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

45

Etanrile la perei Uponor PWP (rezistente la ap sub presiune) Instalarea unei etanri Uponor PWP n centrul gurii sau a unui inel din fibr de ciment PWP 1

Introducei inelul de etanare PWP la limita peretelui (exterior) uruburile spre interiorul cldirii

3
M

Montai inelul de etanare PWP perpendicular pe eav

La asamblarea final, strngei pe rnd fiecare urub cu o cheie dinamometric n sens orar pn la cuplul maxim. Mmax este atins. Strngei uruburile de cteva ori. Repetei procedura dup dou ore.

Folosii un set suplimentar Uponor PWP pentru a reduce tensiunea.

46

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Manonul de reparaii termocontractabil Uponor 1 2 3

Curai poriunea deteriorat a evii.

Detaai folia protectoare din hrtie de pe interiorul manonului autocontractabil .

Plasai manonul termocontractabil pe seciunea deteriorat.

nchidei manonul termocontractabil cu clema metalic.

nclzii manonul n mod egal pe toate prile pn cnd el este strns xat de suprafaa evii.

Cotul de protecie Uponor i manonul autocontractabil 1 2 3

Instalai cotul de protecie la locul corect

Alunecai manonul termocontractabil e la captul cotului de protecie e pe eav.

Instalai eava n interiorul cotului de protecie ( o lungime potrivit a a evii trebuie lsat n cldire).

Rzuii suprafaa cotului de protecie. Plasai manonul constractabil peste cotul de protecie i peste zona de racord. .

nti nclzii manonul termocontractibil la captul cotului de protecie i lsai-l s se rceasc.

Apoi nclzii manonul termocontractabil la captul dinspre eav. Instalaia este gata cnd manonul s-a rcit la temperatura mediului.

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

47

Testul de etaneitate

Testul de etaneitate conform DIN 1988 Part 2


Testul principal Testul principal trebuie fcut imediat dup testul preliminar. Durata testului este de 2 ore. n acest test presiunea msurat la finalul testului preliminar nu tre-buie s scad cu peste 0.2 bar pe timpul urmtoarelor dou ore. Scurgerile nu trebuie s apar la nici un racord al instalaiei testate. evile de plastic Proprietile materialului din care evile de plastic sunt realizate fac ca eava s se dilate pe timpul testului de presiune i aceasta afecteaz rezultatul testului. Rezultatul testului poate fi de asemenea afectat de diferenele de temperatur dintre eav i mediul de test, datorit coeficientului ridicat de dilatare termic a maselor plastice. O schimbare de temperatur de 10 K aici, corespunde aproximativ unei schimbri de presiune ntre 0.5 i 1 bar. Pentru acest motiv, este necesar s meninem temperatura mediului de testare ct mai constant posibil cnd pri ale instalaiei incluznd evi de plastic sunt testate la presiune. Verificai toate racordurile vizual n acelai timp cu testarea presiunii. Experiena arat c scurgeri relativ mici nu pot fi detectate totdeauna doar prin urmrirea presiunii. Cnd testul de presiune este finalizat, golii complet instalaia.

Not Testul de presiune trebuie fcut nainte ca sistemul s intre n funciune. Pentru ca racordurile s nu picure, testul trebuie fcut i nainte ca racordurile s fie izolate i nchise. Desfurarea testului de presiune evile care au fost montate dar nu sunt nc acoperite trebuie umplute cu ap filtrat astfel nct s eliminm aerul. Testul de presiune include testul preliminar i pe cel principal. Testul preliminar Pentru testul preliminar, se aplic o presiune egal cu presiunea de operare plus 5 bar. Aceast procedur trebuie repetat de dou ori n termen de 30 minute i cu un interval de 10 minute ntre teste. Dup aceasta etap i dup o nc o perioad de teste de 30 minute, presiunea nu trebuie s scad cu mai mult de 0.6 bar (0.1 bar la fiecare 5 minute) i nu trebuie s apar scurgeri. Graficul testului de presiune
bar Re-presurizare

Presiunea de lucru + 5 ba r

P1 < 0,6 bar

P2 < 0,2 bar

Test preliminar
10 20 30 60 120

Test principal
180 min

48

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

MASTER

nregistrarea testului de presiune conform DIN 1988 Part 2


Denumire proiect Seciune Bene ciar Firm instalaii

Temperatur i

Temperatur ap

Temperatur mediu

evile umplute cu ap ltrat pentru evitarea aerisirii

Test preliminar

(considerat ca test princ cipal n anumite cazuri) Durata test : 60 minut e Presiune test : presiunea de lucru + 5 bar Presiunea de lucru ________ bar bar Presiunea dupa 30 minute (start test) Presiune dup 60 minut te (presiune nal ) bar (cdere maxim pres.0.6 bar)

Resultat test preliminar


S-au detectat scurgeri DA NU

Test principal

Durata test: 120 minute Presiune la startul testului

pierdere de presiune

: 0,2 bar bar (presiune nal la startul testului) bar (cdere maxim de presiune 0.2 bar)

Presiune dup 20 minute (presiune nal) Resultat test principal S-au detectat scurgeri
DA NU

Start test (ora)

Sfrit test (ora)

Loc

Data

Client (Reprezentant)

Firma de instalaii (Reprezentant)

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

49

Testele de presiune i de scurgere pentru evi de nclzire n conformitate cu DIN 18380


Not Testul de presiune trebuie s fie fcut nainte de punerea n funciune a sistemului. Pentru a vedea dac racordurile nu au scurgeri, testul trebuie fcut nainte ca seturile s fie izolate i nchise. Desfurarea testului de presiune evile care au fost asamblate dar nu i acoperite cu sol, trebuie umplute cu ap filtrat astfel nct s fie eliminat aerul. evile pentru nclzire vor fi testate folosind o presiune care este 1.3 ori presiunea total(presiunea static) a instalaiei, dar care este de cel puin 1 bar n fiecare parte a instalaiei. Numai manometrele care indic schimbri de presiune de 0.1 bar pot fi folosite. Manometrele trebuie plasate n cel mai de jos punct al instalaiei. Trebuie egalizate temperaturile mediului cu cea a apei cu care evile sunt umplute dup un timp de ateptare dup nceperea testului de presiune. Dup aceast perioad de ateptare, poate fi necesar s refacem presiunea de testare. Presiunea de test trebuie meninut pentru 2 ore, i nu trebuie s scad cu mai mult de 0.2 bar. Nu trebuie s apar scurgeri n acest interval de timp. Imediat ce este posibil dup testul cu ap rece, temperatura trebuie crescut la cea mai ridicat valoare a apei fierbini la care se fac calculele, pentru a verifica dac instalaia rmne fr scurgeri chiar i la temperatura maxim. Cnd instalaia s-a rcit la loc, circuitele de nclzire trebuie ve-rificate n final pentru a vedea daca nu au aprut scurgeri la racorduri.

50

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

MASTER

nregistrarea testului de presiune conform DIN 18380 pentru evi de nclzire


Denumire proiect Seciune Bene ciar Firma de instalaii

De veri cat presiunea maxim a componentelor instalaiei nlimea instalaiei Parametrii proiectului m Temperatur tur Temperatura retur C C

bar

Egalizarea temperaturii ntre cea a mediului ambie nt i cea a apei cu care sunt umplute evile trebuie realizat dup un timp acceptabil dup nceperea testului de presiune. Dup aceast perioad poate necesar restabilirea presiunii de testare. Orice recipient, ting, robinet, vas de expansiune care nu poate suporta testul de presiune, trebuie deconectat de la instalaie pe perioada testului de presiune. Instalaia trebuie umplut cu ap ltrat i aerisit complet. Pe durata testului se va face o inspecie vizual a racordurilor .

Star t Sfrit

Data

, ,

Ora

Test pr esiune Pierdere presiune

bar (durata 2 ore) bar (max. 0,2 bar!)

Data

Ora

n data de instalaia identi cat mai jos a fost nclzit la temperaturile din proiect i nu au fost gsite scurgeri. Dup rcire, nu au fost identi cate scurgeri. Trebuie luate msuri potrivite(utilizare antigel, control temperatur cldire) pentru a evita riscul de nghe. Dac antigelul nu mai este necesar pentru operarea in stalaiei conform cu speci caiile antinghe ale cldirii, antigelul trebuie nlocuiit prin golire i splarea instalaiei folosind cel puin 3 schimburi de ap.

Antigel adugat n ap Procedura ca mai sus

Da Da

Nu Nu

Start

test

Sfrit test

Loc

Dat

Client (Representant)

Firma instalaii(Reprezentant)

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

51

Specificaii tehnice

Proprietile evilor Uponor PE-Xa


evi ap cald evile PEX sunt indicate pentru transportul apei fierbini cu temperatura de pn la 95C i la o presiune maxim de 10 bar. eava Uponor PEXa este realizat n conformitate DIN EN 15875-2, cu un raport diametru/grosime perete SDR de 7.4.

evi nclzire evile pentru nclzire Uponor din PEXa sunt acoperite cu un strat de EVOH conform DIN 4726 pentru a preveni difuzia oxigenului. Ele sunt indicate n special pentru transportul agentului termic pn 95C i la o presiune maxim de 6 bar. Raportul diametru/grosime perete este conform SDR 11.

Proprieti mecanice Densitate Rezisten la ntindere (20 C) (100 C) 9-13 N/mm Modul E (20 C) (80 C) 300-350 Elongaie maxim (20 C) (100 C) 500-700 Rezisten la impact (20 C) (-140 C) No rupture Absorbia umiditii (22 C) Coeficient de frecare cu oelul 0.08-0.1 Energia de suprafa Permeabilitate oxigenului (20 C) (55 C) 3.0 x 10-9 Permeabilitate oxigen UponorevalPEX (80 C) Proprieti electrice

Valoare 0.938 19-26 800-900 N/mm 350-550 % No rupture kJ/mm 0.01 34 x 10-3 0.8 x 10-9 g m/m s bar 3,6 Valoare
15

Unitate g/cm N/mm


3

Metod DIN 53455 DIN 53457 DIN 53455 DIN 53453 DIN 53472

N/mm % kJ/mm mg/4d N/mm g m/m s bar mg/md Unitate

ISO 17455 Metod DIN 53483 DIN 53483 DIN 53481 VDE 0303 Metod DIN 53752 DIN 53460

Rezisten intern specific (20 C) 10 W/m Constant dielectric (20 C) 2.3 - Factor de pierderi dielectric (20 C/50 Hz) 1 x 10-3 - Tensiune de rupere (20 C) 100 kV/mm (0.5 mm folie) Proprieti termice Domeniu de temperatur Coeficient de dilatare liniar (20 C) (100 C) 2.05 x 10-4 Temperatura de nmuiere Cldur specific Coeficient de conducie termic 0.35 Valoare -100...+100 1.4 x 10-4 m/mC +133 2.3 W/mC Unitate C m/mC C kJ/kgC DIN 4725

52

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Proprieti de durat
realizate de institutele internaio nale de testare.Testele la oboseal arat c la o temperatur de 70 C i presiunea de 10 bar, n regim de operare continu, eava are o durata de via estimat de peste 50 de ani.

evile Uponor PE-Xa au fost certificate ca tip de produs prin DVGW din1977. Certificarea se bazeaz pe testele

Clasificare condiiilor de lucru conform EN ISO 15875 pentru evi preizolate Uponor
Sistemul de evi Uponor PE-Xa este proiectat conform cu EN ISO 15875 (Sisteme de evi din plastic pentru instalaii de ap cald i rece -- Polietilen reticulat
Clasa Temperatura plicaii a operare D [C]
a

Timp Tmax la TD [ani] [C]

Timp Tmal la Tmax [ani] [C]

Timp la Tmal [h]

Aplicaie tipic

1 60 49 80 1 95 a 2 70 49 80 1 95 20 2.5 Urmat de 40 20 4b Urmat de 70 2.5 100 60 25 Urmat de Urmat de (vezi coloana urmtoare) (vezi coloana urmtoare) 20 14 Urmat de 60 25 5b Urmat de 90 1 100 80 10 Urmat de Urmat de (vezi coloana urmtoare) (vezi coloana urmtoare)
a b

100 Distribuie ap cald (60C) 100 Distribuie ap cald(70C)

100

nclzire prin pardoseal i radiatoare cu temperatur joas

100

radiatoare de temperatur ridicat

Pentru a fi conforme cu regulile naionale, o ar trebuie s aplice fie clasa 1 fie 2. Unde mai mult de o temperatur de operare este artat pentru orice clas, timpii trebuie adunai, adic profilul temperaturii de operare pentru 50 ani pentru clasa 5 este: 20 C pentru 14 ani urmai de 60 C pentru 25 ani, 80 C pentru10 ani, 90 C pentru un an i 100 C pentru 100 ore NB! Pentru valori care depesc pe cele din tabel pentru TD , Tmax i Tmal, acest standard nu este aplicabil.

Clasificarea condiiilor de lucru conform EN 15632-3 pentru evi preizolate PE-Xa evile preizolate PE-Xa pentru nclzire i componentele sistemului Uponor legate de ele, sunt proiectate conform EN 15632-3 (evi pentru nclzirea centralizat Sisteme flexibile de evi preizolate Part 3: evi fr lipire; cerine i metode de test). pean, proiectate pentru o durat de via de cel puin 30 ani cnd lucreaz la urmtorul profil de temperatur/timp : 29 ani la 80 C + 1 an la 90 C + 100 ore la 95 C. Alte profile de temperatur/timp pot fi aplicate cu EN ISO 13760. Informaii suplimentare sunt date n prEN 156322:2008. Annexa A. Temperatura maxim de operare nu trebuie s depeasc 95 C.

Presiunea de operare

Temperaturi de operare i durata de via


Sistemele de evi preizolate PE-Xa sunt, conform cu acest standard euro-

Sistemele de evi preizolate Uponor PE-Xa sunt conform EN 15632-3, proiectate pentru operare continu la presiunea de 6 bar (SDR 11) i 10 bar (SDR 7,4).

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

53

Proprietile materialului mantalei de protecie


asigur o flexibilitate ridicat pe de o parte iar pe de alt parte o capacitate ridicat de a suporta sarcini statice.

Mantaua exterioar de protecie stabil, rezistent la impact din PE-D protejaz stratul izolator i eava PE-Xa de factorii externi din mediu. Proiectarea special a geometriei evii
Proprieti Material Stabilizat la UV Clasa protecie foc Densitate Modul de elasticitate Valoare PE-HD (PE 80) da B2 957 959 ~ 1000

Unitate - - - kg/m MPa

Metod DIN 4102 ISO 1183 ISO 527-2

Proprietile materialului izolator


apei. Designul multistrat combin flexibilitatea maxim i izolaia termic optim.
Unitate kg/m N/cm2
3

Izolaia rezistent la mbtrnire, este din polietilen reticulat i are, datorit structurii celulare nchise o absorbie minim a
Proprieti Densitate Rezistena la rupere Limite temperatura de operare- Minim - Maxim Absorbia apei Clasa protecie la foc Rezistena la compresie 50% deformaie Transmisie vapori de ap/ 10 mm grosime Valoare

Metod DIN 53420 DIN 53571

approx. 28 28 -40 +95 < 1,0 B2 73 1,55

C C volum-% - kPa g/m2 d

DIN 53428 DIN 4102 DIN 53577 DIN 53429

54

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

Anex

Tabele
evi nclzire (evalPEX) Mas [kg/m] 0.116 0.236 0.289 0.380 0.592 0.923 1.459 2.077 2.965 4.442 Volum [l/m] 0.13 24.5 0.31 0.42 0.66 1.03 1.63 2.31 3.26 4.85 Dimens.eav OD x s [mm] 25 x 2.3 32 x 2.9 40 x 3.7 50 x 4.6 63 x 5.8 75 x 6.8 90 x 8.2 110 x 10 ID [mm] 20.4 26.2 32.6 40.8 51.4 61.2 73.6 90.0 Mas [kg/m] 0.183 0.268 0.430 0.665 1.048 1.461 2.113 3.141 Volum [l/m] 0.31 0.50 0.85 1.32 2.08 2.96 4.25 6.29

evi Uponor PE-Xa - mas i volum


evi pentru ap Dimens. eav ID OD x s [mm] [mm] 18 x 2.5 25 x 3.5 28 x 4.0 32 x 4.4 40 x 5.5 50 x 6.9 63 x 8.7 75 x 10.3 90 x 12.4 110 x 15.4 13.0 18.0 20.0 23.3 29.0 36.2 45.6 54.4 65.2 79.8

Tabel comparative al evilor de ap Tabelul arat corespondena dimensiunilor evilor de PEX i cupru sau oel.

PEX OD OD/ID 18 28 32 40 50 63 75 90 110 18/13,0 28/20,0 32/23,2 40/28,6 50/36,2 63/45,7 75/54,4 90/65,2 110/79,8

evi cupru ND 15 22 28 35 42 54 63 76,1 88,9

OD/ID 15/13,0 22/20,0 28/25,6 48/32,0 42/39,0 54/51,0 63/59,0 76,1/72,1 88,9/84,9

Tabel comparativ al evilor de nclzire Tabelul arat corespondena dimensiunilor evilor de PEX i cupru sau oel.

EX P OD OD/ID 25 32 40 50 63 75 90 110 25/20,4 32/26,2 40/32,6 50/40,8 63/51,4 75/61,2 90/73,6 110/90,0

evi oel ND 20 25 32 40 50 65 80 100

OD/ID 26,9/22,9 33,7/28,1 42,4/37,2 48,3/43,1 60,3/54,5 76,1/70,3 88,9/82,5 114,3/101,7

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

55

Notie

56

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

R E E L E T E R M I C E U P O N O R - manual tehnic 0 5 / 2 0 11

57

Uponor- construim parteneriate cu specialitii Uponor este un lider n furnizarea soluiilor pentru instalaiile de alimentare cu ap i nclzire n cldirile de locuit sau publice din Europa i America de Nord i un proeminent productor de sisteme pentru infrastructur din Europa. Cele mai importante domenii de aplicaie ale Uponor sunt instalaiile de nclzire i rcire radiant, alimentrile cu ap i soluiile pentru infrastructur. Numrul angajailor la nivel de Grup depete 3500 persoane n 27 de ri. Grupul Uponor este listat la bursa de valori din Helsinki, Finlanda. Uponor. Simply more.

05/2011 - Ne rezervm dreptul de a face modificri

Uponor Reprezentan Str. Renvierii nr. 3-5 021121 Bucureti Romnia T +40-(0)31 80 533 92 F +40-(0)31 80 533 95 E info-ro@uponor.com W www.uponor.ro

S-ar putea să vă placă și