ver.3 2
Stimate beneficiar,
TERMOFARC
ver.3 3
CUPRINS
Atenţionare importantă…………………………………………….………………………………………………………5
De reţinut…………………………………………………………….…………………………………………………….6
Descrierea cazanului……………………………………………….………………………………………………………7
Gazeificarea………………………………………………………….…………………………………………………….7
Identificarea…………………………………………………………….………………………………………………….8
Elemente componente……………………………………………………………………………………………………..8
Date tehnice………………………………………………………………………………………………………………11
Accesorii………………………………………………………………………………………………………………….13
Capitolul 1................................................................................................................................................... 15
INSTRUCŢIUNI DE INSTALARE ............................................................................................................................ 15
1.1. Alegerea cazanului .............................................................................................................................................. 15
1.2. Amplasarea şi poziţionarea cazanului ................................................................................................................ 15
1.3. Montarea mantălei şi panoului de comandă....................................................................................................... 16
1.4. Racordarea hidraulică .......................................................................................................................................... 17
1.5. Elemente de siguranţă ......................................................................................................................................... 18
1.6. Racordarea elementelor de siguranţă ................................................................................................................. 18
1.7. Funcţionarea schimbătorului de siguranţă (serpentina de răcire). .................................................................... 19
1.8. Sisteme deschise şi sisteme închise .................................................................................................................... 19
1.9. Pompa pentru circuitul de încălzire .................................................................................................................... 21
1.10. Ventil termic de amestec ESBE........................................................................................................................ 21
1.11. Vana de amestec cu 4 căi .................................................................................................................................. 21
1.12. Aerisirea ............................................................................................................................................................. 21
1.13. Scheme de legături ale instalaţiei ..................................................................................................................... 22
1.14. Schema electrică a cazanului ............................................................................................................................ 27
1.15. Racordarea la coşul de fum ............................................................................................................................... 27
1.16. Umplerea sistemului .......................................................................................................................................... 28
Capitolul 2................................................................................................................................................... 29
PUNEREA ÎN FUNCŢIUNE ....................................................................................................................................... 29
2.1. Prima punere în funcţiune ................................................................................................................................... 29
2.1.1. Verificării la prima punere în funcţiune ............................................................................................................................. 29
2.1.2. Punerea în funcţiune............................................................................................................................................................. 29
2.1.3. Predarea la beneficiar ......................................................................................................................................................... 30
Capitolul 3................................................................................................................................................... 31
INSTRUCŢIUNI DE FOLOSIRE ŞI ÎNTREŢINERE ........................................................................................... 31
3.1. Funcţionarea cazanului ........................................................................................................................................ 31
3.2. Aprinderea ............................................................................................................................................................ 31
3.3. Panoul de comandă .............................................................................................................................................. 32
3.4. Aerului de ardere şi deblocarea clapetei unisens ............................................................................................... 33
3.5. Alimentarea şi realimentarea cu combustibil..................................................................................................... 34
3.6. Aerisirea magaziei de combustibil ..................................................................................................................... 34
3.7. Funcţionarea continuă ......................................................................................................................................... 35
3.8. Funcţionarea pe timp de vară .............................................................................................................................. 35
3.9. Întreruperea funcţionării de scurtă durată .......................................................................................................... 35
3.10. Întreruperea funcţionării pe o perioadă mai lungă. ......................................................................................... 35
3.11. Prevederi pentru combustibil ............................................................................................................................ 35
3.12. Exploatare .......................................................................................................................................................... 36
3.13. Curăţarea cazanului ........................................................................................................................................... 37
3.14. Întreţinerea cazanului şi a sistemului de încălzire. .......................................................................................... 37
3.15. Etanşeitatea cazanului. ...................................................................................................................................... 38
3.16. Schimbarea şnurului de etanşare a uşii ............................................................................................................ 39
3.17. Schimbarea duzei de ardere. ............................................................................................................................. 39
Capitolul 4................................................................................................................................................... 39
DEFECŢIUNI ŞI ÎNDEPĂRTAREA LOR ............................................................................................................... 39
Capitolul 5................................................................................................................................................... 41
PIESE DE SCHIMB ...................................................................................................................................................... 41
Capitolul 6................................................................................................................................................... 42
CONDIŢII DE CALITATE ŞI GARANŢIE ............................................................................................................. 42
Capitolul 7................................................................................................................................................... 44
NORME DE PROTECŢIE A MUNCII ŞI P.C.I. ..................................................................................................... 44
PROCES VERBAL DE PROBĂ DE CASĂ .............................................................................................................. 45
DECLARAŢIA DE CONFORMITATE .................................................................................................................... 46
ver.3 4
ATENŢIONARE IMPORTANTĂ
ver.3 5
DE REŢINUT
Este exclusă orice responsabilitate a constructorului pentru daunele cauzate de
erori de instalare sau folosire şi nerespectare a instrucţiunilor constructorului.
Combustibilul utilizat trebuie să fie lemne uscate (2 ani) cu umiditate maximă 20%.
În timpul procesului de ardere se pot forma funingine, gudron şi condens acid. Pentru a
evita formarea acestora, cazanul trebuie să funcţioneze la parametrii optimi (temperatura
agentului termic în cazan să fie 80-90 oC, iar temperatura agentului termic de întoarcere
minim 65oC). Se recomandă folosirea vanelor de ameste cu 4 cai, pompelor de recirculare
comandate de termostat sau a ventilelor termice TV(25, 32, 40), după modul de instalare.
Cazanul nu se va utiliza sub capacitatea nominală. În perioada de tranziţie sau vara (când
este necesară doar A.C.M.), cazanul va fi pornit (aprins) zilnic.
Cazanul poate fi amplasat la acelaşi nivel cu camerele de încălzit sau la subsol, şi poate
funcţiona cu circulaţie gravitaţională (naturală) sau forţată (cu pompă).
Amplasarea cazanului in camere de locuit şi pe holuri de acces este interzisă.
Pardoseala, tavanul şi pereţii trebuie să fie executaţi din materiale ignifuge conform
standardelor in vigoare.
Conductele de gaze arse trebuie să fie bine etansate şi izolate, să aibă secţiunea minimă
conform tabel “date tehnice”, iar coşul suficient de înalt pentru a asigura un tiraj corect
cazanului. Este interzisă racordarea a două sau mai multe cazane la un singur coş.
La amplasarea cazanului se vor respecta urmatoarele distanţe: 0,6 m în partea laterală a
cazanului; 0,8 m în partea posterioara ; 1,5 m în partea frontală şi 0,6 m până la tavan
Periodic se va efectua curăţarea căilor de fum prin intermediul uşilor din mijloc şi
inferioare. Curăţarea căilor de fum se va efectua numai când cazanul este oprit şi lăsat să
se răcească.
Cenuşa trebuie evacuată din cenuşar prin intermediul uşiţei de mijloc şi cea inferioară a
cazanului, periodic sau ori de câte ori este necesar acest lucru. Această operaţie se va
efectua numai când cazanul este oprit şi rece.
ver.3 6
DESCRIEREA CAZANULUI
Cazanele FI-GS sunt construite pentru arderea lemnelor, deşeurilor de lemn (în proporţie de 20%)
sau a brichetelor şi funcţionează pe principiul gazeificării, fiind dotat cu ventilator de aer, care asigură
alimentarea cu aer de combustie a camerelor de ardere. Aerul introdus de ventilator este dirijat pe
două canale de aer. Aerul primar (canalul superior) permite arderea de jos în sus (în masă) a lemnului
şi trecerea gazului de lemn prin duza refractară, iar aerul secundar (canalul inferior) ajută la arderea
gazului de lemn.
Sunt realizate în zece dimensiuni de fabricaţie, respectiv cu putere termică de 18; 25,6; 30,1; 40,6;
52,2; 60,3; 80; 104,4; 130 şi 150 Kw.
Din punct de vedere constructiv sunt cazane din tablă de oţel de grosime 5 respectiv 6 mm la
interior şi 4 mm la exterior, sudată, cu cameră de apă. Cazanele au două compartimente despărţite de
o placă de beton refractar prevăzut cu duze de ardere. Compartimentul superior are rol de magazie de
combustibil şi cameră de gazeificare, iar cel inferior cameră de ardere principală unde are loc arderea
propriu-zisă a gazului de lemn.
Sunt echipate cu două schimbătoare de căldură: serpentină pentru producerea de apă caldă
menajeră (gama 18 – 40 KW), şi serpentină de răcire – protecţie supraîncălzire (toată gama de puteri).
În partea frontală se află cele trei uşi, ventilatorul prevăzut cu clapetă de reglaj unisens, mânerul
de acţionare a clapetei de aprindere, a cărei tija este urmărită de un microîntrerupător (poziţia tijei în
punctele deschis-închis), respectiv panoul de comandă şi control.
Uşile cazanului, permit alimentarea cu lemne (cea superioară), evacuarea cenuşei si curăţirea
focarului şi a drumurilor convective (cea inferioară şi cea din mijloc). Ele sunt căptuşite cu beton
refractar iar etanşarea la închidere se face cu şnur ceramic.
Panoul de comandă conţine un termostat de comandă ce reglează temperature de lucru în cazan
(prin pornirea şi oprirea ventilatorului), un termostat de siguranţă cu rearmare manuală, un termostat
de minim (opreşte ventilatorul după scăderea temperaturii în cazan), un întrerupător general, o
siguranţă fuzibilă şi un termomanometru.
Sunt destinate pentru încălzirea clădirilor şi producerea apei calde menajere. Se poate monta
într-o instalaţie cu funcţionare gravitaţională sau cu circulaţie forţată cu pompă de circulaţie;
GAZEIFICAREA
Principiul gazeificării (sau distilării) lemnului, este un proces ce
asigură un randament maxim al combustiei lemnului, o emisie
minimă de fum şi substanţe nocive în atmosferă şi o reducere
substanţiala a costurilor energetice. Uscare
Lemnul (cu umiditate 15-20%) este încărcat în magazia de
combustibil , unde în contact cu jarul produs pe suprafaţa refractară Piroliză
dă naştere gazului de lemn prin fenomenul denumit ”distilare a
lemnului”, care combinându-se cu aerul primar (de combustie)
alcătuiesc un amestec de combustibil gazos. Acest combustibil este Ardere primară
insuflat prin duza refractară în camera de ardere unde are loc arderea
sub forma de “flacără răsturnată”. Ardere principală
Etapele procesului de gazeificare şi arderea gazului de lemn:
1. uscarea lemnului – se elimină vaporii de apă din lemn care în
Ardere totală
amestec cu produsele de ardere formează printre altele şi gudron.
2. carbonizarea (piroliza) –se formează gazul de lemn şi lemnul
uscat se tranformă în cărbune prin procesul denumit ”distilare”
3. arderea primară – arderea combustibilului format (combustia)
şi cedarea căldurii nivelului anterior şi următor.
4. arderea principală – amestecul de combustil este insuflat (transferat ) prin duza refractară unde se
autoaprinde la 560 oC în amestec cu aerul secundar.
5. arderea totală (finală) – are loc arderea gazului de lemn în camera de ardere principală în amestec
cu1 aerul secundar la temperaturi de 1200 oC.
Urmează transferul căldurii la agentul termic primar prin schimbătorul cazanului după care gazele de
ardere
ver.3 sunt evacuate pe canalul de fum. 7
IDENTIFICAREA
A Fiecare cazan este prevăzut cu o placă de identificare.
fig.1.
ELEMENTE COMPONENTE
Camerele de apă: sunt alcătuite din câte Magazia de combustibil: se găseşte in partea
doi pereţi plan-paralel din tablă de oţel de superioară a cazanului de forma paralelipipedică ,
grosime 5 – 6 mm respectiv 4 mm aşezaţi la aici are loc aprinderea lemnelor în faza iniţială şi
distanţă de 50 mm. Pereţii camerelor sunt producerea patului de jar după care sunt încărcate
întăriţi cu tiranţi din fier rotund Ø 12 mm trunchiurile de lemn.
sudaţi la ambele capete. Colectorul de fum: gazele de ardere după
Uşile cazanului: permit alimentarea cu cedarea energiei sunt adunate în colectorul de
lemne (cea superioară) fiind prevăzut cu o fum, aflat în partea posterioară a cazanului şi
placă tip perdea împotriva propagări fumului evacuate în coş. Acesta este prevăzut cu trei
în camera centralei, curăţare şi evacuarea capace de curăţire şi vizitare, două pe părţile
cenuşii din camera de ardere (cea din mijloc) laterale inferior (stânga-dreapta), iar una pe
şi curăţirea drumurilor convective (cea peretele superior al colectorului.
inferioară).
ver.3 8
ELEMENTE COMPONENTE
ver.3 9
ELEMENTE COMPONENTE
1. Cameră apă
2. Serpentină de preparare a apei calde
menajere (la gama 18 – 40,6 Kw)
6 3. Duză de ardere
4. Serpentină de răcire
5. Izolaţie de vată minerală
6. Racord tur
2 7. Conducte distributie aer ardere primara
8. Conducte distributie aer ardere secundara
1 9. Racord retur
7 – pentru puterile 18 - 105 Kw racordul
4 retur este de 1½” respectiv 2” filet exterior
şi se afla pe spatele cazanului stânga jos
3 (vedere spate)
10 - pentru puterile 130 - 150 Kw racordul
retur este de 2½” filet exterior aflat pe
partea stânga al cazanului
8 10.) Placă de beton refractar
11.) Ecran termic
12.) Sistem convectiv
13. Uşa curăţare inferioară
14. Uşa cameră de ardere
15. Ventilator centrifugal
9 16. Apărător ventilator
17. Uşa magazie combustibil
fig.2. 18. Mâner uşă termoizolant
19. Tijă mâner – acţionare clapetă aprindere
20. Conducta fum evacuare directa (by-pass)
15
11
14
13 12
fig. 3.
28
ver.3 10
DATE TEHNICE
Date referitoare la dimensiunile constructive al cazanelor FI-GS:
H
E
B
Lt
fig. 4.
ver.3 11
DATE TEHNICE
Cazan
FI-GS FI-GS FI-GS FI-GS FI-GS FI-GS FI-GS FI-GS FI-GS FI-GS
Denumire UM
18 25 30 40 50 60 80 105 130 150
Lăţime cazan (D) mm 605 605 605 605 710 710 820 820 930 930
Înălţime cazan (H) mm 1615 1615 1615 1615 1625 1625 1725 1725 1725 1725
Lungime cazan (L) mm 910 1030 1090 1200 1280 1450 1515 1755 1755 1900
Lungime totală cazan (Lt) mm 1035 1155 1215 1325 1400 1575 1640 1880 1880 2025
Înălţimea racord coş (E) mm 1360 1360 1360 1360 1430 1430 1530 1530 1520 1520
Racord coş () mm 170 170 170 170 200 200 220 220 240 240
Înălţimea racord tur mm 1460 1460 1460 1460 1645 1645 1750 1750 1750 1750
Greutate kg 475 535 570 605 745 810 995 1155 1265 1385
Supapă de siguranţă (SS) ţoli ½” ext. ½” ext. ½” ext. ½” ext. ¾” ext. ¾” ext. 1” ext. 1” ext. 1” ext. 1” ext.
Racord tur (RT) ţoli 1½”ext 1½”ext 1½” ext 1½” ext 1½” ext 1½” ext 2” ext. 2” ext. 2½”ext 2½” ext
Racord retur (RR) ţoli 1½”ext 1½”ext 1½” ext 1½” ext 1½” ext 1½” ext 2” ext. 2” int. 2½”ext 2½” ext
Racord golire cazan (RG) ţoli ½” int. ½” int. ½” int. ½” int. ½” int. ½” int. ½” int. ½” int. ½” int. ½” int.
Kcal/h 15.500 22.000 26.000 35.000 45.000 52.000 69.000 90.000 112000 130.000
Putere termică utilă (kW) (18) (25,6) (30,1) (40,6) (52,2) (60,3) (80) (104,4) (130) (150,8)
Randament % 87 – 89 87 – 89 87 – 89 87 – 89 87 – 89 87 – 89 87 – 89 87 - 89 87 - 89 87 - 89
Consum de combustibil
nominal (lemne cu umiditate Kg/h 5 7,06 8,35 11,23 14,45 16,7 22,15 28,9 36 42
18% şi Hi= 3500 kcal/kg)
Tiraj necesar la coş mBa 0,15 – 0,2 0,2 – 0,25
r
Înalţime minima coş ml 6 6 6 6 7 7 8 8 8 8
Conţinut de apă în cazan l 118 139 149 164 209 243 326 386 405 449
Temperatura gazelor de °C 130 - 140
ardere
Temperatura maximă de °C 95 95 95 95 95 95 95 95 95 95
lucru
Temperatura de lucru recomand. °C 80 - 85 80 – 85 80 – 85 80 – 85 80 – 85 80 – 85 80 - 85 80 – 85 80 – 85 80 - 85
Temperatura minimă pe retur °C 65 65 65 65 65 65 65 65 65 65
Putere electrică consumată W 80 80 80 80 135 135 240 240 400 400
Tensiune/frecvenţă de alimentare V/Hz
Presiunea maximă de lucru Bar 220 / 2 2 2 2 2 2 2 2 2
50
Presiunea maximă de probă Bar 2 4 4 4 4 4 4 4 4 4
Debit apă caldă menaj (∆t=35°C) l/min 4 12 12 12 - - - - - -
Volum magazie de combustibil l 120 135 150 175 230 280 400 510 570 655
175
Timp de ardere continuă la
ore 3 4
putere nominala
ver.3 12
DATE TEHNICE
Bloc racordare electrica FI 18 GS – FI 40 GS
RTM
A RT
AR
SS
ACM
S
ARR
RST
AR RG
fig.5 fig.6.1
RT RT
SS
SS
S
RST RST
ARR
ARR
RG RR
RR RG
fig.6.2 fig.6.3
ver.3 13
ACCESORII
Accesorii livrate cu cazanul
- Panou de comandă - Ventilator
(pachet de bază) (pachet de bază)
temperatura la cosul - Manual de utilizare
de iesire panou de comanda
(pachet de bază) (pachet de bază)
- Instrucţiuni de montaj,
exploatare şi întreţinere
(pachet de bază)
Accesorii recomandate ca şi obligatorii
deschis
sau închis
ver.3 14
INSTALAREA
Capitolul 1
INSTRUCŢIUNI DE INSTALARE
Capitolul se adresează atât persoanelor autorizate care procedează la instalarea cazanului, cât
şi beneficiarului care are interesul ca lucrările efectuate să corespundă normelor de siguranţă în
exploatare a tuturor elementelor care contribuie la bună funcţionare a instalaţiei.
Cazanul poate fi instalat de agenţi economici sau personal autorizat ISCIR. Instalarea,
montajul se va face după un proiect cu respectarea normativelor în vigoare şi în conformitate cu
cartea tehnică al cazanului.
Atenţie! În cazul neinstalării cazanului acesta trebuie depozitat într-un loc uscat.
Cazanul trebuie ales astfel încât puterea nominală să corespundă pierderilor de căldură şi
necesarului termic conform STAS 1907, condiţie esenţială pentru funcţionare corectă şi economică.
Alegerea unui cazan cu puterea nominală prea mare va avea ca rezultat depuneri de gudroane pe
peretele interioare a acestuia.
AMPLASAREA
1.2. Amplasarea şi poziţionarea cazanului
Cazanul se va monta numai în instalaţia de încălzire centrală executată pe baza unui proiect
întocmit de o instituţie specializată, în condiţiile respectării măsurilor de siguranţă prevăzute în STAS
7132-86; STAS 3417-85 ; Normativ I 13-94; Normativ I 13/1-96; PT C 9-2003; PT A2-2003;colecţia
ISCIR; GP 051-2000; P 118-99.
Cazanul va fi instalat într-o încăpere proprie amplasată în subsol, demisol sau la parterul
clădirilor civile sau industriale, cu excepţia clădirilor din categoria A şi B de pericol de inflamare sau
explozie. De asemenea este interzisă amplasarea cazanelor direct sub încăperi cu personal care nu se
poate evacua singur (de exemplu spitale), sub săli de spectacole, magazine, grădiniţe de copii sau sub
căile de acces ale acestora.
Sala cazanelor trebuie separată de
încăperile alăturate şi să fie suficient vitrată.
Încăperea în care se montează cazanul
trebuie să fie suficient de mare ca să permită
montarea cazanului pe o suprafaţă perfect
orizontală (eventual pe un postament metalic
sau din beton) respectănd distanţele conform
fig.8. Cazanul nu se amplasează pe suporturi
din materiale inflamabile. Încăperea trebuie
prevăzută cu un orificiu de acces al aerului
proaspăt, cu o deschidere de 400 cm2 – în
permanenţă deschis spre exterior. Se
recomandă ca pe pardoseală să fie amplasat
un sifon de scurgere şi conducte de apă
fig. 7. potabilă cu presiune suficientă pentru
umplerea instalaţiei de încălzire centrală.
Atenţie! Amplasarea cazanului în camere de locuit şi pe coridoare de acces este
interzisă !
ver.3 15
MONTAREA
12 14
5 4 10 6 11 9 13 1 2 3 20
15 16
18 17
7
9
19
8
Cazanul se va amplasa la locul lui destinat funcţionării. Se vor monta componentele conform fig.8.
desenului din fig. 9. după cum urmează:
- Asamblarea se începe cu însurubarea prezoanelor (poz.1.) ce susţin colectorul de fum.
- Se poziţionează canalul de fum (poz.2.) pe prezoane şi se fixează cu piuliţele M12 (poz3) în
nr. de 6 buc.
- Se monteajă microîntrerupătorul (poz.4) ce urmareşte tija de acţionare a clapetei de
aprindere peste care se poziţionează mantaua frontală poz.5 şi se vor fixa cu ajutorul
şuruburilor cu cap înecat M6, după care se însurubeză mânerul (poz.6) tijei de acţionare
clapetă aprindere.
- Se poziţioneaza mantalele laterale (poz.7 şi 8) şi se vor fixa cu ajutorul şuruburilor M6
(poz.9) căte două sus şi două jos.
- Se monteaza panoul de comanda (poz.10) si blocul de conexiuni electrice (poz.11) in cutia
acestuia (poz.12) si se fixeaza pe mantaua superioară (poz.13). Se monteaza sonda de
control temperatura la cosul de iesire (poz.14).
- Sonda aparaturi de comandă şi control se vor introduce în teaca ei((poz.15 ( şi în racordul
mufă ¼” (poz.16.) – dupa caz).
- Se fixează ventilatorul (poz.17), ( apărătorul ventilatorului (poz.18) între uşa superioară şi
de mijloc si manta fata inferioara (poz.19)
- Se pun mantalele posterioare (functie de tipul cazanului) şi se vor fixa cu ajutorul
şuruburilor M6 căte două sus şi două jos.
- Capacul superior (poz.13) se fixeaza cu element elastic -4 buc (vezi fig8.1)
- Se monteaza supapa siguranta 2,5 bari((poz.20) in racordul ei (stut filetat (1/2-1”’functie de
tipul cazanului) ((poz.15)
ver.3 16
MONTAREA
Cep sferic
Element elastic
fig.8.1.
RACORDAREA CAZANULUI
1.4. Racordarea hidraulică
Dacă sa efectuat poziţionarea şi montarea mantalelor se trece la racordarea hidraulică al
cazanului. Turul şi returul cazanului este prevăzut cu filete exterioare conform tabelului ”Date
tehnice”. Se va racorda la reţeaua de apă serpentina de producere a apei calde menajere (la gama 18 –
40 Kw). Se racordează serpentina de răcire conform fig. 10. Toate legăturile hidraulice de instalare a
cazanului se vor face cu respectarea ” schemelor de instalare”.
Pentru umplerea cazanului şi/sau al sistemului, instalatorul va racorda o conductă cu apă curentă
la conducta de întoarcere (returul instalaţiei). La această racordare se va intercala o clapetă de sens
(supapă de reţinere) şi un robinet de umplere.
Atenţie: La racordul de umplere al instalaţiei se va intercala o clapetă de sens!
Pentru o bună funcţionare şi pentru protecţia cazanului împotriva coroziuni se recomandă:
- pentru evitarea condensului acid şi gudronare, prin ridicarea temperaturi la returul cazanului, se
va alege una din următoarele variante de montaj:
- ventil termic de amestec TV 60ºC, care are rolul de a menţine apa de întoarcere la returul
cazanului la temperatura de peste 60ºC necesarul la retur fiind de minim 65ºC, sau pe
conducta de tur al instalaţiei se va monta un ventil termic de amestec TV 72ºC cu acelaşi rol
(pt. puterile de ≤ 70 Kw).
- pompă de recirculare între tur şi retur (by-pass) comandat de termostat.
- vană de amestec cu 4 căi cu sau fără servomotor reglat corect.
- pentru obţinerea apei calde manajere recomandăm instalarea a unui boiler cu acumulare,
- pentru mărirea autonomiei de funcţionare şi preluarea surplusului de căldură se recomandă
montarea cazanului cu vas de acumulare. Capacitatea vasului de acumulare (puffer) va fi minim
40 litri pe 1Kw instalat.
Notă: Pentru a obţine confortul termic dorit în locuinţă (temperatura de ambient), se
recomandă ca, corpurile de încălzire să fie echipate cu robineţi termostataţi.
Cazanul se monteaza în sisteme de încălzire prevăzute cu vase de expansiune deschise sau închise
dacă sunt îndeplinite condiţiile prevăzute la cap. ”Elemente de siguranţă”.
ver.3 17
RACORDAREA CAZANULUI
ELEMENTE DE SIGURANŢĂ
1.5. Elemente de siguranţă
INSTALAŢIEI
Vasul de expansiune deschis cu conducte de siguranţă tur-retur sau vas de expansiune închis
dupa caz;
Supapă de siguranţă reglată la presiunea de 2,5 bar (conform tabel date tehnice);
Serpentina de răcire conectat la reţeaua de apă rece şi la instalaţia de scurgere prin intermediul
unui robinet de golire termică “supapă termică ” STS 20 sau TS 130;
fig.10.
SISTEME DE INSTALARE
1.8. Sisteme deschise şi sisteme închise
Vasul de expansiune deschis se va monta în punctul cel mai înalt al instalaţiei, dar nu mai mult
de 20 m în înălţime, măsurat de la conducta de intrare a apei în cazan şi cât mai aproape de axa
verticală a cazanului. El va fi izolat termic şi protejat împotriva îngheţului.
Fundul vasului de expansiune trebuie să depăşeasca nivelul cel mai înalt al instalaţiei cu minim 1,5 m;
Echilibrarea hidraulică a instalaţiei este necesară pentru realizarea alimentării în condiţii optime a
tuturor corpurilor de încălzire. Aceasta se realizeaza prin:
- alegerea traseelor de conducte;
- dimensionarea conductelor;
ver.3 19
SISTEME DE INSTALARE
- utilizarea pompelor de circulaţie.
Vasul de expansiune deschis este absolut necesar în instalaţiile cu circulaţie gravitaţională.
SISTEME DE INSTALARE
1.8.2. Sisteme închise (cu vas de expansiune închis)
fig.
În cazul existenţei unei surse permanenete de11.apă şi montarea unui vas de expansiune este
dificilă / imposibilă, se poate alege varianta de montaj cu vas de expansiune cu membrană (închisă).
Folosirea lor are multe avantaje dintre care cel mai important este împiedicarea admisiei de aer în
sistem şi oxidări acesteia.
Vasul de expansiune închis trebuie dimensionat în funcţie de cantitatea de apă din instalaţie şi
cazan pentru a putea prelua dilatările apei şi sistemului.
Calcul de capacitate a vasului închis:
Q= v x (P1 + B) / B x 1,3 ; unde
Q – capacitatea vasului
P1 – presiunea hidrostatică [kPa]
B – diferenta de presiune (50 kPa)
v – volumul apei din sistem după încălzire v = G x Δv
G – masa apei [kg]; 1,3 –coeficient de siguranţă
Δv – cresterea volumului de apă la o anumită temperatură (ex. la Δt = 80ºC Δv =0,0355 [l/kg])
Presiunea de aer din vasul de expansiune închis trebuie reglată potrivit presiunii hidrostatice al
construcţiei, în funcţie de volumul total al apei din sistem.
Cel puţin anual se va verifica integritatea „ membranei” şi presiunea aerului din acesta.
ver.3 20
ELEMENTELE INSTALAŢIEI
ver.3 21
SCHEME DE INSTALARE
1.13. Scheme de legături ale instalaţiei
Atenţie! Schemele sunt orientative. Pentru o instalare corectă, respectaţi normativele în
vigoare.
1.13.1 Schema de legături hidraulice cu vas de expansiune deschis pentru cazanele FI-GS cu
serpentină de răcire, serpentină apă caldă menajeră şi ventil termic TV 60ºC
LEGENDĂ
VED – vas de expansiune deschis
RI – radiator
ACM – apă caldă menajeră
ARM – apă rece menajeră
Rt – robinet de trecere
SS – supapă de siguranţă
RC – racord coş
T – racord tur
R – racord retur
GC – golire cazan
ST – supapă termică
S – sondă supapă termică
ARR – apă rece reţea
RST – racord supapă termică
Cs– clapetă de sens
Pc – pompă de circulaţie
VT – ventil termic de amestec TV 60ºC
SC – scurgere canalizare
Fy – filtru impurităţi
TMM - termomanometru/manometru
fig.12.
1.13.2 Schema de legături hidraulice cu vas de expansiune deschis pentru cazanele FI-GS cu
serpentină de răcire, serpentină apă caldă menajeră şi pompă recirculare cu comandă
termostatată.
LEGENDĂ
VED – vas de expansiune deschis
RI – radiator
ACM – apă caldă menajeră
ARM – apă rece menajeră
Rt – robinet de trecere
SS – supapă de siguranţă
RC – racord coş
T – racord tur
R – racord retur
GC – golire cazan
ST – supapă termică
S – sondă supapă termică
ARR – apă rece reţea
RST – racord supapă termică
Cs– clapetă de sens
Pc – pompă de circulaţie
Prc- pompă recirculare
TS- termostat comandă pompe
SC – scurgere canalizare
fig.13. Fy – filtru impurităţi
TMM - termomanometru/manometru
ver.3 22
SCHEME DE INSTALARE
1.13.3 Schema de legături hidraulice cu vas de expansiune închis pentru cazanele FI-GS cu
serpentină de răcire, serpentină apă caldă menajeră şi ventil termic TV 60ºC .
LEGENDĂ
1.13.4 Schema de legături hidraulice cu vas de expansiune închis pentru cazanele FI-GS cu
serpentină de răcire, serpentină apă caldă menajeră şi pompă recirculare cu comandă
termostatată.
LEGENDĂ
fig.16.
LEGENDĂ
ver.3 24
SCHEME DE INSTALARE
1.13.6 Schema de legături hidraulice cu vas de expansiune deschis pentru cazanele FI-GS cu
boiler cu acumulare, vas de acumulare, serpentină de răcire şi pompă de recirculare cu
comandă termostatată.
fig.17.
LEGENDĂ
ver.3 25
SCHEME DE INSTALARE
1.13.7 Schema de legături hidraulice cu vas de expansiune închis pentru cazanele FI-GS cu
boiler cu acumulare, vas de acumulare, serpentină de răcire şi vană de amestec cu 4 căi.
fig.18.
17.
LEGENDĂ
ver.3 26
SCHEMA ELECTRICĂ
Pentru racordarea cazanului la reţeaua electrică de 220V, 50Hz se va folosi un cablu trifilar.
Camera centralei va fi prevăzut cu curent electric, bec pentru lumină şi două sau trei prize pentru
alimentare electrică a panoului de comandă şi a pompelor de circulaţie.
Racordarea cazanului se va face numai de persoane autorizate în acest sens, cu respectarea
normelor în vigoare.
Atenţie! Corpul cazanului trebuie legat la nul de protecţie pentru a avea împământare
şi a preveni pericolul de electrocutare.
COŞUL DE FUM
1.15. Racordarea la coşul de fum
Vor fi evitate coturile în unghi drept. Nu se va utiliza mai mult de un cot curbat pentru
racordarea cazanului la coş. Primul element de deviere sau cot se va monta la o distanţă minimă de 3
ori diametrul racordului de coş. Este interzisă montarea unor sisteme de obturare pe canalul de
legatură sau pe coş. Înălţimea minimă a coşului (izolat termic) este de 6 m (măsurat de la nivelul
camerei de ardere). El trebuie să asigure un tiraj bun, de minim 0,2 mbari.
ver.3 27
COŞUL DE FUM
O izolaţie corespunzătoare a coşului de fum este de asemenea, importantă, deoarece gazele de
ardere trebuie să aibă la ieşirea din coş o temperatură egal sau mai mare de 130 ºC, pentru a fi
eliminate problemele cauzate de condens.
Este interzisă racordarea altor aparate alimentate cu combustibil gazos la canale de fum care
deservesc şi focare cu combustibil lichid sau solid. La bază, coşul trebuie prevăzut cu o uşiţă de
vizitare, iar la terminal un capac de protecţie sau plasă..
Coşul de fum trebuie să fie construit în conformitate cu normativele în vigoare conform STAS
6793 şi STAS 3417 de către personal autorizat.
UMPLEREA SISTEMULUI
După ce s-au făcut toate legăturile hidraulice, puteţi trece la umplerea sistemului.
•Deschideţi toţi robineţii radiatoarelor, cazanului şi sistemului.
•Deschideţi încet robinetul de alimentare, asigurându-vă că eventualii robineţi de aerisire
automată funcţionează corect. Închideţi toţi robineţii de aerisire manuală când începe să iasă apa.
•Verificaţi presiunea sistemului pe termomanometru.
•Închideţi robinetul de alimentare şi aerisiţi cazanul.
•Dacă este necesar, reluaţi alimentare cu apă pentru a regla presiunea apei în instalaţie.
•Porniţi pompa de circulare a agentului termic şi verificaţi funcţionarea acesteia (se va aerisi).
Atenţie! Pe conducta de alimentare între robinetul de umplere şi cazan se recomandă
intercalarea unei clapete de sens, pentru prevenirea goliri accidentale al instalaţiei !
Periodic se va verifica presiunea apei din instalaţia de încălzire, realimentarea
acesteia făcându-se numai cu cazanul oprit şi rece.
Este interzisă utilizarea cazanului gol sau parţial umplut cu apă.
Utilizarea cazanului gol sau parţial umplut cu apă poate conduce la explozie.
ver.3 29
PUNEREA ÎN FUNCŢIUNE
La o ardere corecta flacăra degajată este de culoare gălbuie - roşiatică cu vârfurile tinzănd spre
albastru.
Cazanul FI –GS cu gazeificare funcţionează pe combustibil solid – lemn uscat (1-2 ani) cu
umiditate maximă 20%, deşeuri de lemn în proporţie de 20% şi brichete de rumeguş.
În regim normal de lucru funcţionarea cazanului este controlată de panoul de comandă şi
control .
Temperatura agentului termic este comandată si reglată prin termostatul de comandă maxim.
Temperatura de lucru a cazanului se poate regla până la 90 °C, dar valoarea recomandată este de 80-
90 °C, iar a temperaturii de întoarcere (retur) să fie peste 65°C, valoare necesară pentru limitarea
coroziunii la temperatură joasa a pereţilor cazanului.
Pentru a realiza temperatura pe retur, procedaţi după una din schemele descrise la cap.1 „Scheme
de instalare” .
La atingerea temperaturii setate automatizarea cazanului comandă oprirea ventilatorului.
La scăderea temperaturii sub valoarea setată termostatul de comandă maxim reporneşte ventilatorul.
Termostatul de siguranţă intervine la depăsirea temperaturii de 95 °C indicănd o stare de
supraîncălzire oprind total cazanul, repornirea necesitănd ca atare intervenţia utilizatorului.
Repornirea cazanului dupa intervenţia termostatului de siguranţă se poate face în modul următor:
- intervenţia utilizatorului şi înlăturarea cauzei care a produs supraîncălzirea
- răcirea cazanului sub 90°C;
Supapa termică corect instalată intervine la temperatura de 97°C permiţănd accesul apei în
serpentina de răcire imersată în cazan, răcind astfel cazanul; la coborârea temperaturii sub aceasta
valoare, supapa termică se închide automat.
Pentru o funcţionare normală trebuie asigurat în permanenţă accesul aerului proaspăt în
încăperea în care este amplasat cazanul.
APRINDEREA
3.2. Aprinderea
Deschideţi uşa superioară (uşa de alimentare), ridicaţi perdeaua de fum şi sprjiniţi în locaşul
prevăzut pentru acesta, ca alimentarea cu combustibil să fie uşoară, deasupra duzei de ardere
introduceţi o cantitate suficientă de combustibil (aschii) şi bucăţi de hârtie. Înaintea aprinderii focului
se deschide clapeta de aprindere prin împingerea manetei (18) în poziţia 1. fig.20.
Se aprinde combustibilul. şi se deschide uşa de mijloc pentru ardere naturală
Se închide uşa de alimentare şi se asteaptă căteva minute pentru arderea (ardere de jos în sus)
cantităţi de lemn introduse şi formarea patului de jar.
După formarea patului de jar se umple magazia de combustibil cu lemne, se eliberează perdeaua
de fum lăsănd să se sprjine pe lemnele din magazie, se închide uşa de alimentare, se lasă ca lemnul
alimentat să se aprindă să se formeze gazul de lemn, după care se închide uşa de mijloc şi se trage
clapeta de aprindere (18) în poziţia 2 (fig. 20. şi fig.20.1) şi se blochează cu surubul (30).
ver.3 31
APRINDEREA
31
30
1
2 fig.20. fig.20.1
Detaliu G
În poziţia 1: tija mâner împinsă – se deschide clapeta aprindere şi microîntrerupătorul (31)
opreşte funcţionarea ventilatorului;
În poziţia 2: tija mâner trasă – se închide clapeta aprindere, este acţionat microîntrerupătorul (31)
şi ventilatorul porneşte;
REGLAJE
3.3. Panoul de comandă
ver.3 32
REGLAJE
Funcţiile elementelor de comandă:
Vezi Manualul de utilizare al panoului de comanda.
Inainte de pornirea cazanului, cititi cu atentie Manualul de utilizare al panoului de comanda!
- microîntrerupător cu rolă – urmăreşte tija de acţionare a clapetei de aprindere şi are rolul de a
opri funcţionarea ventilatorului dacă clapeta de aprindere nu este inchisă (tija de acţionare a
clapetei de aprindere nu este trasă şi blocată cu şurubul 30). Opreşte ventilatorul şi în cazul
deschideri accidentale a clapetei de aprindere.
Aerul de ardere pentru cazanele FI-GS este furnizat de un ventilator centrifugal montat pe partea
frontala a cazanului. Admisia de aer este împărţită pe două circuite prin rampa de distribuţie a aerului.
Rampa de distribuţie a aerului se află în partea frontală a cazanului, între uşa superioara şi de mijloc
prevăzut cu clapetă gravitaţională unisens care se închide la oprirea ventilatorului. Aerul se împarte în
aer primar şi aer secundar. Aerul primar este distribuit la partea
superioară a magaziei de combustibil
prin intermediul a două conducte de
distribuţie. Aici se amestecă cu gazul de
lemn şi dă naştere la amestecul de
combustibil care trecănd prin duza de
ardere, arde. Aerul secundar este
distribuit prin duza de ardere prin
1 intermediul a două ţevi de secţiune
circulară prevăzute cu găuri (faţă în faţă,
2 decalat) furnizănd oxigen direct în zona
de formare a flăcării.
Reglajul aerului se face din şurubul aflat
pe conducta de refulare principală a
rampei de aer.
Prin rotirea surubului în sens orar –sens
de rotaţie 1. fig.21.- se reduce debitul de
aer de ardere.
Prin rotirea surubului sens antiorar – sens
de rotaţie 2. fig.21.- se măreste debitul de
aer de ardere.
Conducta de refulare principală a rampei
fig.21. de aer este demontabilă prin
17. dezşurubarea celor 4 piuliţe M6, astfel se
poate verifica şi debloca clapeta unisens.
ver.3 33
ALIMENTAREA
Alimentarea cu combustibil se face manual cu lemne uscate (1-2 ani) cu umiditate maximă 20%,
şi deşeuri de lemoase în proporţie de 20% sau brichete de rumeguş.
Pentru o bună utilizare se recomandă folosirea de butuci de lemn care se vor aranja suprapusi căt
mai compact, avănd lungimea descrisă la pct.3.11.
Cu cât lemnul este mai uscat cu atât gradul de mărunţire a lemnului trebuie să fie mai redus.
Nivelul maxim de umplere cu combustibil se va limita de regula la nivelul uşii depozitului de
combustibil.
La aprindere după formarea patului de jar se poate trece la alimentarea cu lemne a magaziei de
combustibil;
Înaintea oricărei deschideri a uşii magaziei de combustibil aerisirea cazanului este obligatorie şi
trebuie efectuată, pentru ca substanţele volatile degajate în procesul combustiei lemnului sunt
inflamabile şi în contact brusc cu aerul se pot autoaprinde producănd o explozie.
ver.3 34
CAZURI DE FUNCŢIONARE
3.7. Funcţionarea continuă
În perioada de iarnă este indicat funcţionarea continuă a cazanului, nefiind necesar reaprinderea
focului zilnic. Este posibilă menţinerea în funcţiune, deci o ardere continuă pe o perioadă mai
îndelungată de 12 ore (peste noapte) fără încărcări ulterioare folosind cazanul la sarcină scăzută. În
astfel de cazuri se are în vedere menţinerea temperaturi la returul cazanului.
COMBUSTIBILUL
3.11. Prevederi pentru combustibil
Combustibilul indicat pentru cazanele FI-GS cu funcţioneare pe principiul gazeificării sunt
bucăţi (butuci) de lemne uscate (1-2 ani) cu diametrul de 200 mm şi umiditate 15 – 20 %.
Lungimea lemnelor în funcţie de mărimea cazanului este dată în tabelul următor:
EXPLOATARE
A 3.12. Exploatare
Cazanul poate fi deservit numai de persoane adulte care cunosc instrucţiunile de utilizare şi
modul de funcţionare a aparatului, nefiind permisă lăsarea nesupravegheată a copiilor în preajma
acestuia.
Cazanul funcţionează cu supraveghere periodică. Noţiunea de “funcţionare cu supraveghere
periodică” implică controlul periodic al existenţei apei în instalaţie, alimentării cu combustibil.
La punerea în funcţiune, personalul de P.I.F. este obligat să instruiască beneficiarul cu privire la
exploatarea şi întreţinerea corectă a cazanului.
În timpul exploatării este necesară completarea combustibilului din cazan. O încărcătură de
combustibil arde în perioade de timp variabile, în funcţie de natura şi umiditatea combustibilului
folosit, încărcarea termică a instalaţiei, temperatura externă şi tirajul coşului
La o funcţionare a cazanului la o temperatură mai mică la retur de 65 ºC, pe corpul cazanului
poate sa apară condens, ceea ce produce coroziunea elementelor metalice, gudronarea pereţilor
interioare şi reduce durata de viaţă a cazanului.
Nu se recomandă funcţionarea cazanului la sarcină termică redusă timp îndelungat.
În timpul exploatării cazanului se interzice supraîncălzirea acestuia.
Este interzisă utilizarea unor lichide inflamabile pentru aprinderea focului.
La efectuarea curăţirii cazanului se va inspecta şi starea părţilor componente, a etanşărilor, etc.
În cazul constatării unor nereguli, acestea vor fi remediate de către unităţile de service.
Pe cazan şi la distanţe mai mici decăt cele admise nu se admit a fi depozitate obiecte sau
materiale inflamabile.
În cazul scoaterii cenuşei din cazan se interzice a se depozita la o distanţă mai mică de 1,5 m de
materiale inflamabile. Cenuşa va fi depozitată în containere neinflamabile cu capac.
Autonomia de funcţionare este între 6 şi 12 ore în funcţie de esenţa şi umiditatea lemnului utilizat
şi încărcarea termică.
ver.3 36
ÎNTREŢINEREA
3.13. Curăţarea cazanului
Atenţie!Înainte de orice operaţie de curăţire sau întreţinere este obligatoriu scoaterea
cazanului sub tensiune şi lăsarea lui să se răcească.
Curăţirea cazanului trebuie efectuată în mod regulat, de câte ori este nevoie. Intervalul de
curăţire depinde de calitatea lemnului utilizat, intensitatea arderii, tirajul coşului şi de alte condiţii.
Se recomandă curăţirea la intervale de 3-5 zile. Produsele de ardere acumulate (cenuşa) împreună cu
condensul şi gudroanele înrăutăţesc schimbul de căldură, scad randamentul cazanului.
Deasemenea o cantitate mare de cenuşă va micşora spaţiul de ardere, va putea înfunda drumurile
de gaze sau aer .
Magazia de combustibil se va curăţa înainte de fiecare aprindere de resturile de ardere.
În timpul procesului de gazeificare se produce gudron care se depune pe pereţi cazanului.
Cantitatea de gudron depinde de esenţa şi umiditatea lemnelor şi de temperaturile de la turul şi returul
cazanului. Acest gudron trebuie curăţat cel puţin odată pe lună, cu instrumentele de curăţare livrate
odată cu cazanul.
Modul de curăţire al cenuşei
Se deschide uşa de alimentare şi se va mătura cenuşa prin orificiul duzelor de ardere – curăţind şi
pe aceştia - în camera inferioară de unde se va evacua ulterior.
Se deschide uşa focarului (uşa de mijloc) de unde cu vătraiul se trage cenuşa fără a deteriora
placa din material refractar.
Pe usa inferioară se vor curăţa căile convective (de fum)
Capace pt curatarea de
funingine a colectorului de fum
fig.22
.
Etanşarea cazanului este foarte importantă, mai ales uşile, clapeta de aprindere şi colectorul de
fum. Dacă la una dintre acestea se înregistrează scăpări, fumul poate pătrunde în camera centralei, dar
înainte poate provoca o ardere necontrolată în magazia de combustibil care duce la supraîncălzirea
cazanului. Din acest motiv şnurul de etanşare trebuie uns din două în două săptămâni cu ulei sau
vaselină grafitată.
fig.23
fig.24
.
ver.3 38
ÎNTREŢINEREA
3.16. Schimbarea şnurului de etanşare al uşii
Se înlătură şnurul de etansare cu ajutorul unei surubelniţe şi se curăţă canalul acestuia. În canalul
şnurului se introduce pastă de silicon rezistent la temperatură. Se ia şnurul nou şi se taseză în canalul
practicat în uşă, unde se va lipi în siliconul introdus anterior. Se prinde uşa de măner şi se închide pe
rama uşi pentru ca şnurul să se aşeze. Dacă este necesar se vor regla balamalele şi dispozitivul de
închidere a uşi.
3.17. Schimbarea duzei de ardere.
Duza de ardere este fomată din una sau mai multe duze de ardere (cărămizi) identice poziţionate
în corpul cazanului pe suportul duzei .(în cazul deteriorări duzei de ardere se va schimba doar acea
parte care sa deteriorat) Modul de schimbare a acestor duze:
- se scoate sau sparge piesa de samotă veche.
- se curăţă locasul ei de gudroane şi resturi de şamotă
- se instalează duza cea nouă în locaşul ei poziţionand astfel ca găurăle din rampa de aer
secundar să comunice cu găurile din duză.
- se etansează cu praf de samotă.
Numărul de piese ceramice ce compun duza de ardere;
REMEDIEREA DEFECŢIUNILOR
Capitolul 4
DEFECŢIUNI ŞI ÎNDEPĂRTAREA LOR
În tabelul de mai jos sunt prezentate principalele defecţiuni ce pot apărea în funcţionarea
cazanului, precum şi măsurile de remediere ale acestora:
Defecţiune Cauza Remediere
Ledul de control al - lipsă tensiune alimentare - se verifică
întrerupătorului general - ştecherul nu este introdus - se verifică
nu luminează corespunzător în priză
- întrerupător defect -se înlocuieşte
- cablu de alimentare defect -se înlocuieşte
- microintrerupătorul nu este acţ. -se trage tija clapetei de aprind.
Cazanul nu atinge - apă insuficientă în sistem; - se reumple;
temperatura reglată - debit pompă prea mare; - se reglează turaţia pompei;
(putere utilă scăzută) - cazan subdimensionat; - problemă de proiectare;
- calitate necorespunzătoare a - se schimbă combustibilul;
combustibilului;
- clapeta de aprindere deschisă; - se închide;
- tiraj insuficient; - coş nou sau curăţat;
ver.3 39
REMEDIEREA DEFECŢIUNILOR
ver.3 40
PIESE DE SCHIMB
Capitolul 5
PIESE DE SCHIMB
Cazanul este conceput pentru folosire îndelungată, fără piese de uzură rapidă. Înlocuirea de
piese devine necesară pentru remedierea defecţiunilor ce apar după funcţionare îndelungată sau
datorită nerespectării instrucţiunilor de folosire. Toate operaţiile de remediere sau înlocuire se vor
face numai de serviciul de întreţinere autorizat de producător.
Lista pieselor de schimb: - piesă ceramică refractară – duză ardere
- ventilator
- panou de comanda
- senzor INC
- senzor ACM
- senzor gaze
- senzor termic
- siguranta fuzibila
- microintrerupător de la clapeta de aprindere
- şnur etanşare uşă
- condensator ventilator
ver.3 41
CONDIŢII DE GARANŢIE
Capitolul 6
CONDIŢII DE CALITATE ŞI GARANŢIE
ver.3 43
CONDIŢII DE GARANŢIE
Capitolul 7
NORME DE PROTECŢIE A MUNCII ŞI P.S.I.
La montarea, punerea în funcţiune, exploatarea şi întreţinerea cazanului se va ţine seama de:
Normele republicane de protecţia muncii; Normele R.E.T. (regulament de exploatarea tehnică a
centralelor); Prescripţii P.S.I.; Prescripţiile tehnice ISCIR C9-2003; P 118; Normativ I13-94;
Procurarea acestor norme şi prescripţii, ediţia la zi, este în sarcina beneficiarului care exploatează
şi întreţine instalaţia;
ver.3 44
PROCES VERBAL DE PROBĂ DE CASĂ
_________________ _________________
L.S.
ver.3 45
DECLARAŢIE DE CONFORMITATE
DECLARAŢIA DE CONFORMITATE
(aici se ataşează)
ver.3 46
Carte tehnică elaborată de: Dir. Teh. Ing. KÖPE JÁNOS-CSABA
si proiectant ing GAL EMERIC
ver.3 47
SC TERMOFARC SRL; B-dul. Braşovului, nr.118, SĂCELE, Jud. BRAŞOV;
Tel: 0268/274945, Fax: 0268/276193
www.termofarc.ro
ver.3 48
VASI DI ESPANSIONE PER RISCALDAMENTO
EXPANSION TANKS FOR HEATING SYSTEMS
ERCE
- 10° ÷ + 99°C ERCE 35 A102L31 35 1,5 10 +99°C 400 390 - 3/4” 410 x 410 x 410
ERCE 35/P A122L31 35 1,5 10 +99°C 400 415 390 (lungh.) 3/4” 410 x 410 x 410
ERCE 50 A102L34 50 1,5 10 +99°C 400 500 - 3/4” 410 x 410 x 535
ERCE 50/P A122L34 50 1,5 10 +99°C 400 415 500 (lungh.) 3/4” 410 x 410 x 535
ERCE 80 A112L37 80 1,5 10 +99°C 400 820 - 3/4” 410 x 410 x 860
ERCE 100 A112L38 100 1,5 10 +99°C 500 775 - 3/4” 510 x 510 x 830
ERCE 150 A112L43 150 1,5 10 +99°C 500 1005 - 3/4” 510 x 510 x 1040
ERCE 200 A112L47 200 1,5 10 +99°C 600 1065 - 1” 610 x 610 x 1110
ERCE 250 A112L49 250 1,5 10 +99°C 650 1160 - 1” 660 x 660 x 1210
ERCE 300 A112L51 300 1,5 10 +99°C 650 1240 - 1” 660 x 660 x 1290
ERCE 500 A112L55 500 1,5 10 +99°C 775 1400 - 1” 1/4 785 x 785 x 1440
Ø Ø
Ø
DN1
H
H
H
DN1 DN1
CALOR SRL
Str. Progresului nr. 30-40, sector 5, Bucuresti
tel: 021.411.44.44, fax: 021.411.36.14
www.calorserv.ro - www.calor.ro
FISA TEHNICA
1/3
STATIE DEDURIZARE SIMPLEX AUTOTROL LGX255 R16T- DATE TEHNICE SI DIMENSIUNI
2/3
atunci cand va montati o statie de dedurizare apa utilizati cu 30% mai putine produse pentru igiena corporala si 30%
detergent pentru spalat rufe ;
factura de energie se poate reduce cu pana la 15%-20% ;
aparatura electrocasnica are durata mai mare de viata si costuri mai reduse de intretinere.
3/3
MODEL: 125, 150, 200, 300,
BOILERE MIXTE ELDOM INVEST
400, 500 litri
BOILERE MIXTE
STIMATE CLIENT,
ELDOM INVEST LTd. va ofera o noua gama de boilere mixte cu acumulare cu capacitati de la 125 pana la 500 litri.
Acestea sunt concepute pentru a furniza un volum mare de apa calda pentru consumatori casnici, hoteluri mici, vile, ferme,
intreprinderi.
Boilerele sunt fabricate in mai multe versiuni: cu sau fara serpentina (una sau doua, una mai mare si una mai mica) si
termometru. Rezervorul si schimbatoarele de caldura sunt emailate si protejate de anozii de magneziu impotriva coroziunii,
sau sunt fabricate dintr-un aliaj superior din otel (inox).
Apa din boiler poate fi incalzita:
- electric cu ajutorul unor rezistente;
- prin surse alternative prin serpentine de la sistemul de incalzire locala sau centrala sau de la colectoarele solare.
- combinarea surselor (electrica si prin intermediul serpentinelor)
Combinarea corespunzatoare a surselor de caldura poate duce la o economie semnificativa de energie electrica in fiecare
anotimp al anului (colectoarele solare pot fi folosite ca sursa exterioara de caldura pe perioada verii iar in timpul iernii se vor
folosii sistemele de incalzire locala sau centrala).
Toate boilerele sunt prevazute cu schimbatoare de caldura electrice (rezistente) si accesorii de protectie pentru reglajul
temperaturii, izolatie din spuma de poliuretan si dupa caz o manta exterioara din otel acoperita cu o vopsea din polimeri-
epoxidici. Pentru facilitarea transportului, boilerele de 300, 400 si 500 litri sunt fixate pe paleti.
INSTALAREA BOILERULUI
Boilerele sunt de tip verticale si trebuie instalate pe pardoseala in conditiile indicate. Camera in care se instaleaza boilerul
trebuie prevazuta cu un sistem de golire in pardoseala pentru evacuarea apei din boiler in timpul reparatiilor.
Indepartati paletul (prevazut la boilerele de 300, 400 si 500 litri) folosind un dispozitiv de ridicare corespunzator. Indepartati
dopul de cauciuc prevazut la partea superioara la mijlocul capacului – vezi figura 3.
Un inel cu capat filetat corepunzator greutatii boilerului este prevazut pentru insurubare in racordul M10 de sub dopul de
cauciuc. Dupa ridicarea boilerului desurubati cele trei bolturi cu picioruse pentru transport de la partea inferioara, indepartati
paletul si reinsurubati bolturile cu picioruse in aceleasi gauri. Pozitionati boilerul in locul destinat acestuia. Dupa instalarea
acestuia desurubati inelul cu capat filetat si montati la loc dopul cu garnitura.
Pozitia verticala a boilerului se obtine prin reglarea bolturilor cu picioruse.
Boilerele cu capacitati de 125, 150 si 200 litri sunt alimentate electric monofazat
la retea conform fig. 5. Schema de legaturi electrice pentru boilerele de 125
pana la 200 litri (cu sau fara serpentina) este prezentata in fig. 6 si 7.
Boilerele cu capacitati de 300, 400 si 500 litri se vor racorda la o retea electrica
trifazata conform schemei din fig. 8. Sectiunea conductorilor pentru faze, neutru
2
si protectie al cablului de alimentare trebuie sa fie de minim 2,5 mm . Conductorul
de protectie trebuie sa fie racordat la terminalul de protectie sau la pin-ul marcat
cu simbolul de impamantare. Fiecare circuit de curent trebuie prevazut cu o
siguranta fuzibila de 16 A pe fiecare faza. Pentru a conecta cablul de alimentare
la boiler, trebuie indepartat capacul de plastic de protectie a bornelor. Dupa
conexiunea conductorilor la borne, capacul trebuie fixat la loc. In exteriorul
boilerului trebuie montat un dispozitiv (intrerupator) pentru pornirea si oprirea
acestuia.
Distanta dintre contactele acestui dispozitiv in pozitia oprit trebuie sa fie cel putin
3 mm pentru fiecare pol.
Racordarea boilerului la reteaua electrica de alimentare trebuie efectuata numai
de catre personalul autorizat si calificat.
UTILIZAREA BOILERULUI
Inainte de pornirea boilerului asigurati-va ca acesta este umplut cu apa
(VERIFICATI!). Pornirea boilerului se realizeaza prin actionarea dispozitivului
(intrerupator) exterior. Dupa acesta operatie se va aprinde lampa de pe
capacul protector, intra in functiune rezistentele electrice si incepe sa se
incalzeasca apa. Dupa atingerea temperaturii setate din termostat, lampa se
stinge. Aceasta se va aprinde din nou atunci cand temperatura va scadea sub
temperatura setata. Termometrul (daca boilerul este prevazut cu un astfel de
dispozitiv) arata aproximativ temperatura apei din boiler. Functionarea boilerului
este oprita cu ajutorul dispozitivului exterior. La boilerele de 125 pana la 200 litri
temperatura apei se poate regla din butonul termostatului. La boilerele in varianta
modificata cu reglajul temperaturii prin intermediul serpentinelor (reglaj optional)
este prevazut un al doilea termostat (la partea superioara) destinat reglarii
procesului de incalzire cu serpentine. Lampa de la partea superioara indica
functionarea serpentinelor. Acest circuit de reglare trebuie conectat numai de catre
personalul autorizat si calificat care a dimensionat conexiunile boilerului la sursele
de caldura alternative. Curgerea apei prin vana de siguranta T&P (puteti verifica
acest lucru la palnia racordata la aceasta) indica faptul ca boilerul functioneaza
intr-un regim critic. Opriti imediat functionarea boilerulu! Intrerupeti alimentarea
electrica, intrerupeti alimentarea cu apa rece a boilerului si opriti recirculatia apei in
boiler(e). Orice interventie asupra boilerului este interzisa inainte ca un tehnician
autorizat sa fi eliminat cauza deschiderii vanei (supapei de siguranta). Utilizarea
boilerelor si a racordurilor acestora trebuie efectuata strict urmand instructiunile
producatorului.
INTRETINERE
Anozii montati in rezervorul emailat al boilerului au o durata de viata aproximativa de 5 ani. Apelati la unitatea de service
autorizata dupa expirarea duratei de viata a anozilor pentru testarea si inlocuirea acestora.
In recipientele de otel inox nu se monteaza niciun model de anod.
In zonele in care apa are duritatea foarte mare, depunerile din recipient si de pe schimbatoarele de caldura trebuie
indepartate in fiecare an sau la doi ani. Indepartarea depunerilor nu constituie obiectul garantiei boilerului.
REGULI IMPORTANTE
1. Boilerele trebuie instalate si utilzate in conformitate cu cerintele din acest manual in premiza unei protectii normale
impotriva incendiilor, in care apa din boiler poate fi golita si evacuata in conditii de siguranta.
2. Este interzisa actionarea boilerului de catre copii.
3. Racordarea hidraulica si electrica a boilerului la retea trebuie efectuate numai de catre personalul calificat si autorizat.
Sectiunile respective din certificatul de garantie trebuie completate corespunzator.
4. Boilerul trebuie conectat corespunzator la punctul neutru si circuitul de siguranta de la reteaua de alimentare electrica.
5. Boilerul, instalat si conectat hidraulic si electric, trebuie pus in functiune de o persoana calificata si autorizata numai dupa
ce au fost efectuate testele functionale in locul unde este montat. Certificatul de garantie trebuie completat corespunzator.
Testele functionale nu reprezinta o obligatie de garantie.
6. Boilerul trebuie racordat la sursele alternative de caldura de catre personalul autorizat si calificat de furnizor.
o
7. Prevenirea inghetului apei in interiorul boilerului – daca exista riscul atingerii unor temperaturi reduse (sub 0 C), atunci
boilerul trebuie golit (vezi sectiunea “RACORDAREA TEVILOR LA INSTALATIA DE ALIMENTARE CU APA SI INSTALATIA
DE INCALZIRE”.
8. Pentru a mentine functionarea in siguranta a boilerului, actionati cu regularitate supapa de siguranta (vana combinata)
ridicand manerul acesteia pentru evacuarea unui jet puternic de apa. Aceasta operatie este necesara cel putin la fiecare 14
zile de la punerea in functiune a boilerului precum si dupa fiecare oprire a alimentarii cu apa a boilerului.
9. Atunci cand este actionata supapa de siguranta pentru elminarea unui jet de apa si golirea apei din boiler trebuie luate
toate masurile necesare pentru evitarea defectiunilor rezultate din evacuarea apei din boiler.
10. Daca boilerul este prevazut cu supapa de siguranta (vana combinata T&P), verificati regulat cu atentie eventuala
deschidere a supapei. In cazul in care apa incepe sa curga prin racordul de evacuare al supapei prin palnie opriti imediat
functionarea aparatului, intrerupeti alimentarea electrica si hidraulica si apelati la unitatea de service autorizata pentru
verificare si reparare.
11. Anodul de protectie trebuie inlocuit periodic inclusiv dupa expirarea perioadei de garantie.
AC-2
ER-CE
- 10° ÷ + 99°C ER 5 * A102L11 5 1,5 8 +99°C 205 225 3/4” 210 x 210 x 250
ER 8 CE A102L16 8 1,5 8 +99°C 205 300 3/4” 210 x 210 x 320
ER 12 CE A102L20 12 1,5 8 +99°C 270 300 3/4” 280 x 280 x 310
ER 18 CE A102L24 18 1,5 8 +99°C 270 410 3/4” 280 x 280 x 450
ER 24 CE A102L27 24 1,5 8 +99°C 320 355 3/4” 330 x 330 x 375
Ř
* Esente da marcatura CE
H
DN1
ER 5 ÷ 24
CALOR SRL
Str. Progresului nr. 30-40, sector 5, Bucuresti
tel: 021.411.44.44, fax: 021.411.36.14
www.calorserv.ro - www.calor.ro
CALOR SRL
Str. Progresului nr. 30-40,
sector 5, Bucuresti
tel: 021.411.44.44, fax: 021.411.36.14
www.calorserv.ro - www.calor.ro
Aplications FOR
All heating systems, air condition systems, closed loop cooling systems and industrial circulatory systems.
The implementation bronze casing SAN for the usage in drinking water circulation systems.
OPERATION
∆p-Proportional pressure control
After selecting level pump recognizes the lowest resistance of the system and automatically adjusts its own strain.
∆p-Constant speed
After selection pump works in three different speeds
PRODUCT DESCRIPTION
• High efficiency ECM technology
• Energy savings
• Proportional pressure control
• Constant speed
• Easy handling and installation
• Robust and compact construction for long life
• Automatic venting
• Low noise operation
• Single body, which allows a variety of mounting positions
• Possibility of housing with cataphoretic
• Twin pump option
• The possibility of an analog input signal 0-10 V
Dimensions L DN D2 b1 b2 I a
NMT 40 130/180 15/20/25/32 1"/5/4"/6/4"/2" 80 48 108 27/29/32
TECHNICAL DATA
Flow Q up to 2,6 m³/h
Pressure H up to 4 m
Power 5 - 25 Watt
Nominal pressure 10 bar
Permissible mediums
• Water, mixed with glycol, parameters must be checked in the mixture of water with over 20% of glycol
• Pure non-explosive liquid media free from mineral oils and without solid particles
Permissible temperature range
• Medium temperature from +5 ⁰C to +95 ⁰C with max. surroundings temperature up to +40 ⁰C
Minimum inlet pressure
0,05 bar < 75 ⁰C Temperature of medium
0,28 bar < 90 ⁰C Temperature of medium
Electrical connection
Voltage 1 ~ 230 V, 50/60 Hz
Motor/Electronics
Aplications FOR
All heating systems, air condition systems, closed loop cooling systems and industrial circulatory systems.
The implementation bronze casing SAN for the usage in drinking water circulation systems.
OPERATION
∆p-Proportional pressure control
After selecting level pump recognizes the lowest resistance of the system and automatically adjusts its own strain.
∆p-Constant speed
After selection pump works in three different speeds
PRODUCT DESCRIPTION
• High efficiency ECM technology
• Energy savings
• Proportional pressure control
• Constant speed
• Easy handling and installation
• Robust and compact construction for long life
• Automatic venting
• Low noise operation
• Single body, which allows a variety of mounting positions
• Possibility of housing with cataphoretic
• Twin pump option
• The possibility of an analog input signal 0-10 V
Dimensions L DN D2 b1 b2 I a
NMT 40 130/180 15/20/25/32 1"/5/4"/6/4"/2" 80 48 108 27/29/32
TECHNICAL DATA
Flow Q up to 2,6 m³/h
Pressure H up to 4 m
Power 5 - 25 Watt
Nominal pressure 10 bar
Permissible mediums
• Water, mixed with glycol, parameters must be checked in the mixture of water with over 20% of glycol
• Pure non-explosive liquid media free from mineral oils and without solid particles
Permissible temperature range
• Medium temperature from +5 ⁰C to +95 ⁰C with max. surroundings temperature up to +40 ⁰C
Minimum inlet pressure
0,05 bar < 75 ⁰C Temperature of medium
0,28 bar < 90 ⁰C Temperature of medium
Electrical connection
Voltage 1 ~ 230 V, 50/60 Hz
Motor/Electronics
Aplications FOR
All heating systems, air condition systems, closed loop cooling systems and industrial circulatory systems.
The implementation bronze casing SAN for the usage in drinking water circulation systems.
OPERATION
∆p-Proportional pressure control
After selecting level pump recognizes the lowest resistance of the system and automatically adjusts its own strain.
∆p-Constant speed
After selection pump works in three different speeds
PRODUCT DESCRIPTION
• High efficiency ECM technology
• Energy savings
• Proportional pressure control
• Constant speed
• Easy handling and installation
• Robust and compact construction for long life
• Automatic venting
• Low noise operation
• Single body, which allows a variety of mounting positions
• Possibility of housing with cataphoretic
• Twin pump option
• The possibility of an analog input signal 0-10 V
Dimensions L DN D2 b1 b2 I a
NMT 40 130/180 15/20/25/32 1"/5/4"/6/4"/2" 80 48 108 27/29/32
TECHNICAL DATA
Flow Q up to 2,6 m³/h
Pressure H up to 4 m
Power 5 - 25 Watt
Nominal pressure 10 bar
Permissible mediums
• Water, mixed with glycol, parameters must be checked in the mixture of water with over 20% of glycol
• Pure non-explosive liquid media free from mineral oils and without solid particles
Permissible temperature range
• Medium temperature from +5 ⁰C to +95 ⁰C with max. surroundings temperature up to +40 ⁰C
Minimum inlet pressure
0,05 bar < 75 ⁰C Temperature of medium
0,28 bar < 90 ⁰C Temperature of medium
Electrical connection
Voltage 1 ~ 230 V, 50/60 Hz
Motor/Electronics
Specificatii tehnice :
FEATURES
The dry stainless steel pressure gauges and the
glycerine filled pressure gauges are designed for
measuring pressure on non-crystallising, non-viscous and
non-aggressive gaseous fluids and liquids. They are
designed following the EN 837-1 standard. The pressure
scale is graduated in bars.
AVAILABLE MODELS
LIMITS OF USE
PRECISION CLASS
At 20°C, in % of scale:
ø 63 1.6 class
ø 100 1 class
Design EN 837-1
MEASUREMENT SCALES
Range (bar) Graduation (bar) Range (bar) Graduation (bar) Range (bar) Graduation (bar)
No.
1616 - F1616 1617 1618
1 -1 / +1 0.05 -1 / +1 0.05 -1 / +1 0.05
2 0 / 1.6 0.02 0 / 1.6 0.02 0 / 1.6 0.02
3 0 / 2.5 0.05 0 / 2.5 0.05 0 / 2.5 0.05
4 0/4 0.1 0/4 0.1 0/4 0.1
5 0/6 0.1 0/6 0.1 0/6 0.1
6 0 / 10 0.2 0 / 10 0.2 0 / 10 0.2
7 0 / 16 0.2 0 / 16 0.2 0 / 16 0.2
8 0 / 25 0.5 0 / 25 0.5 0 / 25 0.5
9 0 / 40 1 0 / 40 1 0 / 40 1
10 0 / 60 1 0 / 60 1 0 / 60 1
CONSTRUCTION
Name Material
Case AISI 304 SS
Fitting AISI 316 SS
Mechanism AISI 316 SS
Dial Aluminium
Glass Toughened glass
Ø63 Pointer Aluminium
Ø100 Pointer Aluminium
DIMENSIONS (mm)
1616-F1616 / 1617-1618
ACCESSORIES
The following accessories can be used with the 1616 - F1616-1617 and 1618 pressure gauges.
siphon damper front flange bracket needle valve ball valve
SY D1 RPM MIGNON
ASSEMBLY INSTRUCTIONS
1. Plan the measuring outlet in a part of the pipe installation or of the tank where the flow is uniform and
undisturbed.
2. If the fluid is dirty, viscous or crystallising, use a diaphragm seal.
3. Check that the measuring range for the pressure to be measured is in accordance with the scale of the
pressure gauge.
4. Check that the fluid temperature is compatible with that of the pressure gauge operation. If necessary, mount a
siphon.
5. Mount an isolation valve between the pressure gauge and the pressure outlet to be able to perform its
maintenance.
6. A glycerine filling and a damper are necessary, when vibrations are present on the installation.
7. Use a flat gasket suitable for the fluid, to avoid leak-tightness for the pressure gauge fitting.
8. When screwing on the pressure gauge, do not hold it by the dial, but use a flat wrench on the fitting as shown in
the diagram below.
9. If the pressure gauge is filled with glycerine, bring it to atmospheric pressure by cutting the pressure release plug
nipple.
10. If a hydrostatic test is carried out on the installation, do not exceed the pressure intended for the pressure
gauge. Otherwise, close the isolation valve or remove the pressure gauge.
11. During start-up, slowly open the isolation valve to prevent water hammer which can damage the pressure gauge.
12. Gently tap the pressure gauge case.
13. Read the displayed value.
Interiorul unui cos de fum din inox se va executa din inox austenitic W430i (AISI 304)
cu grosimea de 0.4 mm.
Izolatia unui cos de fum din inox se va executa cu vata minerala, de inalta densitate,
tip NOBASIL, (import SLOVENIA) cu grosimea de 40 mm. Vata este pe suport din folie
de aluminiu.
Exteriorul unui cos de fum din inox se va executa din inox feritic lucios W 416 (AISI
430) cu grosimea de 0.5 mm.
COSURI DE FUM INOX - CALOR SRL ofera intreaga gama de cosuri de fum din
INOX cu diametre cuprinse intre 150 mm si 600 mm. La cerere se pot realiza
cosuri cu constructie speciala
Fisa tehnica
Bazin vidanjabil 20 mc
ROI - Rezervor orizontal subteran / Bazin a) 1 buc manloc de vizitare DN600 mm, H=400 mm, capac PAFS
vidanjabil b) 1 buc teava PVC DN 160
c) 1 buc aerisitor DN 110
d) grosime 10 mm,
e) aproximativ 950 Kg,
f) pe baza de comanda
g) dimensiuni: Diam.= 2500 mm, L=4550 mm
h) volum: 20 mc
FIŞĂ TEHNICĂ
PREVECTRON 2 tip TS 3.40 Millenium (cod 1213)
1. Raza de protecţie:
2. Caracteristici:
1. STAND-BY
Dispozitivul de amorsare se încarcă cu ajutorul electrozilor inferiori,
obţinând energia necesară din câmpul electric atmosferic (câţiva zeci
kV/m în timpul furtunilor). Acesta înseamnă că Prevectron este total
autonom, nu necesită alimentare exterioară cu energie electrică.
2. CONTROL
Prevectron reacţionează automat şi instantaneu la orice creştere
bruscă al câmpului electric – echivalentă cu apariţia liderului
Legendă:
descendent.
Dispozitivul de amorsare electronic controlează precis funcţionarea
Rp - raza de protecţie
Prevectron, pentru ca acesta să lanseze un lider ascendent numai în h – înălţimea
momentul cel mai critic, mai bine zis în momentul imediat premergător D – raza sferei fictive
descărcării principale. ∆L – avansul de amorsare
3. AMORSARE ∆L(m)=106 ∗ ∆T(µs)
Când lovitura de trăsnet este iminentă, descărcând energia acumulată
în faza stand-by, Prevectron va amorsa anticipat un lider ascendent la Pentru alte înălţimi necuprinse în
vârful său, înaintea tuturor vârfurilor vecine. Astfel Prevectron va fi tabel se foloseşte relaţia (h>2m):
punctul de impact preferenţial al loviturii de trăsnet din zona protejată.
RP = h(2 D − h) + ∆L(2 D + ∆L)
3. Alte informații:
- producătorul este certificat conform ISO 9001:2000 (certificat Bureau Veritas nr.1912713)
- furnizorul este certificat conform ISO 9001:2008 (certificat DNV nr. 59324-2009)
- termen de garanţie: 24 luni de la livrare
FISA TEHNICA
1/2
PANOU SOLAR TUBURI VIDATE WARMMAN sunEVO 20 - SCHEMA
sunEVO
1.3 0.77 10 2020*995*155 39.9 100
10-1.3 mp
sunEVO15-
1.9 1.15 15 2020*1410*155 58.3 150
1.9 mp
sunEVO
2.6 1.54 20 2020*1825*155 77.1 200
20-2.6 mp
2/2
AQUAJET
GRUPURI DE PRESURIZARE CU AUTOAMORSARE AUTOMATA
DATE GENERALE
Aplicatii
Grupurile automate de ridicare a presiunii apei sunt foarte potrivite pentru uz
casnic, instalatii mici pentru uz civil, agricol, industrial, instalatii de spalare si alte
aplicatii de tip hobby.
Ele sunt caracterizate prin utilizarea unor electropompe cu autoamorsare JET
care pot functiona chiar si in prezenta bulelor de aer, gaz si chiar a unor mici
cantitati de nisip in apa.
Grupul este alcatuit dintr-un rezervor cu membrana cu capacitatea de 20 lt., un
presostat pentru functionarea automata, manometru, electropompa JET
prevazuta cu cablu de alimentare cu stecker, kit de racordare intre pompa si
rezervor, toate fiind deja asamblat si gata de instalare.
DATE TEHNICE
CARTE TEHNICA
POMPE AUTOAMORSANTE
JA-JR-JGR-JG-JX
• Sunt destinate pomparii apei curate si a fluidelor care sunt neagresive d.p.d.v. chimic si mecanic fata de materialele din
care sunt realizate pompele, non-explozive si avand o temperatura maxima de 90°C daca rotorul este metalic (fonta,
alama, otel) sau 50°C daca rotorul este din plastic (noryl) sau daca exista garnituri;
• Trebuie instalate in locuri bine ventilate, protejate impotriva intemperiilor si in conditii de temperatura ambientala de max.
40°C;
• Rotorul este orizontal (cu exceptia pompelor din gama MV), pompele fiind prevazute la baza cu cadru de fixare: din
considerente de siguranta, se recomanda fixarea pompei cu ajutorul orificiilor prevazute in cadrul de baza; trebuie evitata
montarea pompei cu motorul aflat sub corpul pompei;
• Nu trebuie pornite de mai mult de 5-30 ori pe parcursul unei ore, la intervale egale; cu cat puterea pompei este mai mare,
cu atat numarul pornirilor trebuie sa fie mai mic;
• Presiunea maxima de lucru este: in cazul pompelor PE50-PL50/JR/JA60÷120/JGR-JR/JX/PA/SE/SD/SC/RA/KB100 – 6
bar, in cazul pompelor PC/JA150÷300/KM/KBJ – 8 bar, in cazul pompelor PE80-100/PL80-100/MN/MO-MV – 10 bar, in
cazul pompelor KB150÷1500 – 11 bar.
Conductele
Conductele trebuie fixate si ancorate astfel incat sa nu transmita tensiuni sau vibratii catre pompa. Diametrul interior al
conductelor depinde nu numai de lungimea acestora ci si de debitul necesar: diametrul trebuie ales astfel incat viteza fluidului
sa nu depaseasca 1,4-1,5 m/s pe aspiratie si 2,4-2,5 m/s pe refulare; in nici un caz diametrul conductei nu trebuie sa fie mai
mic decat diametrul racordului pompei.
Inainte de instalare trebuie verificat ca interiorul conductelor sa fie curat.
Conducta de aspiratie
- trebuie sa fie cat mai scurta posibil, fara blocaje sau schimbari bruste de directie;
- trebuie sa fie perfect etansa si sa reziste depresiunilor create in timpul aspiratiei pompei;
- trebuie montata cu o panta ascendenta catre pompa astfel incat sa se evite aparitia pungilor de aer care ar impiedica
amorsarea pompei sau ar provoca dezmorsarea acesteia.
Pentru ca pompa sa functioneze, trebuie montata pe aspiratie o vana de capat cu sorb; in cazul pompelor autoamorsante,
vana de capat cu sorb poate fi inlocuita cu o clapeta de retinere montata direct pe aspiratie. Pentru functionarea corecta a
pompei, capatul conductei de aspiratie trebuie imersat in apa pe o adancime egala cu minim dublul diametrului conductei.
Conducta de refulare trebuie prevazuta cu o clapeta de retinere si cu o vana de reglaj. Clapeta, montata in amonte fata de
vana, protejeaza pompa de fenomenul de lovitura de berbec si previne circulatia inversa a apei prin rotor in cazul opririi bruste
a pompei. Vana de reglare se foloseste pentru reglajul debitului de fluid, inaltimii de pompare si puterii absorbite.
Pe conducta de refulare se monteaza un manometru. In cazul pompelor autoamorsante, pentru inaltimi de amorsare si
aspiratie ridicate (mai mari de 5 m, dar mai mici de 9 m), conducta de refulare trebuie sa aiba un tronson drept vertical de
minim 1 m.
Conexiunile electrice
Se aleg dimensiuni corespunzatoare pentru cablul electric de alimentare in functie de lungimea acestuia si de curentul electric
de alimentare indicat pe placuta pompei: pregatiti capetele conductoarelor de alimentare si de legare la pamant astfel incat in
momentul conectarii acestea sa nu scape atunci cand sunt fixate la placa de borne si la borna de impamantare.
Bransamentul electric trebuie realizat intotdeauna de catre personal autorizat, respectand normele in vigoare.
Conexiunile trebuie realizate conform cu diagrama de pe prima pagina si/sau din interiorul carcasei placii de borne. Realizati
legatura pompei la pamant cu terminalul corespunzator. Asigurati-va ca reteaua de alimentare are un sistem de impamantare
eficient si ca legarea la pamant a pompei este sigura.
In cazul unora dintre pompele monofazate, motorul dispune de un sistem incorporat de protectie termica automata.
Inainte de inceperea oricaror operatiuni de intretinere si/sau reparatii ale pompei, aceasta trebuie deconectata de la sursa de
alimentare cu energie electrica pt. ca este posibil ca aceasta sa porneasca brusc in cazul in care motorul s-a oprit prin
actiunea sistemului automat de protectie.
In orice caz, atat pentru pompele trifazate cat si pentru cele monofazate, trebuie prevazuta o protectie electrica
corespunzatoare (intrerupator magnetotermic si intrerupator diferential de curent de actionare nominal care nu depaseste 30
mA) in masura sa asigure o debransare omnipolara a retelei cu o distanta de declansare a contactelor de cel putin 3 mm.
Ecartul maxim admis intre tensiunea de alimentare si valoarea nominala indicata pe placuta pompei este de +5%.
Pornirea
Inainte de pornirea pompei, verificati ca axul rotorului se roteste liber. Pt. aceasta, pompele mici sunt prevazute cu o scobitura
pt. surubelnita, la capatul axului; daca acesta este blocat, introduceti surubelnita in aceasta scobitura si ciocaniti usor pt. a-l
debloca.
Pompa se porneste numai dupa ce corpul acesteia precum si conducta de aspiratie sunt complet umplute cu lichid, prin
orificiul prevazut pt. aceasta. Innici uncazpompanutrebuiesa functionezeinsec.
In cazul pompelor trifazate, verificati ca rotorul se roteste in sensul corespunzator indicat de sageata de pe corpul pompei (in
sens orar cand pompa este privita dinspre rotor); daca pompa se roteste in sens gresit, inversati cele doua faze de alimentare.
Verificati ca pompa functioneaza la parametrii indicati pe placuta; in caz contrar, reglati din vana de pe conducta de refulare
si/sau reglati presiunea de interventie a eventualelor presosatate.
Intretinere
Pompele nu necesita o intretinere speciala. Daca exista pericolul aparitiei inghetului in cazul opririi prelungite a pompei, corpul
acesteia precum si conductele trebuie golite complet. Inainte de repornire, asigurati-va ca rotorul pompei nu este blocat din
cauza depunerilor sau din alte cauze si umpleti complet cu lichid corpul pompei si conducta de aspiratie.
DATE TEHNICE
Putere 3
Debit (m /h-l/min) A R
Putere absorbita
MODEL I (A)
nominala 0,6 1,2 1,8 2,4 3 3,6 4,2 4,8 6
kW
10 20 30 40 50 60 70 80 100
JA 200 JA 200 T 1,65 2,2 2,22 2,22 10,3 4,1 61 59,5 58 56 54 514 49 46 40 1”1/2 1”
Putere 3
Debit (m /h-l/min)
Putere absorbita
MODEL I (A) A R
nominala 0,6 1,2 1,8 2,1 2,4 3
kW
10 20 30 35 40 50
Monofazat Trifazat kW HP 1~ 3~ 1x230V 3x400V Coloana apa (m)
JGR 80 JGR 80 T 0,59 0,8 0,78 0,79 3,6 1,3 35 27 20,5 11,5 - - 1” 1”
JG 80 JG 80 T 0,59 0,8 0,79 0,79 3,7 1,4 39,5 32 25 20,5 12,5 - 1” 1”
JG 100 JG 100 T 0,74 1 0,98 1 4,6 2,2 44,5 37,5 32 29 27 15,5 1” 1”
JGR 85 JGR 85 T 0,59 0,8 0,78 0,79 3,6 1,3 35 27 20,5 11,5 - - 1” 1”
JG 85 JG 85 T 0,59 0,8 0,79 0,79 3,7 1,4 39,5 32 25 20,5 12,5 - 1” 1”
JG 105 JG 105 T 0,74 1 0,98 1 4,6 2,2 44,5 37,5 32 29 27 15,5 1” 1”
JX 85 JX 85 T 0,6 0,8 0,82 0,78 3,9 1,4 39 33,5 29 - 25 - 1” 1”
JX 105 JX 105 T 0,75 1 1,1 1,1 4,7 2,2 42 36 31,5 - 27,5 24 1” 1”
JX 125 JX 125 T 0,9 1,2 1,15 1,15 5,4 2,4 47 42 37 - 33 23 1” 1”
DIMENSIUNI
DOMENIU DE UTILIZARE
CARACTERISTICI NOMINALE
CARACTERISTICI DE FUNCTIONARE
CARACTERISTICI NOMINALE
EN 60 335-1
IEC 335-1
CEI 61-150
EN 60034-1
IEC 34-1
CEI 2-3
1/2
DOMENIILE DE UTILIZARE ŞI INSTALAŢIE
SUNT RECOMANDATE PENTRU POMPAREA APEI CURATE CU
CONTINUT DE NISIP IN LICHIDUL POMPAT NU MAI MARE DE 150G/
M3. DATORITA RANDAMENTULUI RIDICAT SI A FIABILITATII SUNT
ADECVATE PENTRU APLICATII DE UZ DOMESTIC, CIVIL SI
INDUSTRIAL, PENTRU DISTRIBUTIA AUTOMATICA A APEI FIIND
ECHIPATE CU VASE DE EXPANSIUNE, PENTRU IRIGARI, PENTRU
RIDICAREA PRESIUNII, LA INSTALATII ANTIINCENDIU, ETC.
GARANŢIE 2 ANI conform condiţiilor noastre generale de vânzare.
CARACTERISTICI TEHNICE DE CONSTRUCŢIE
EXECUŢII LA CERERE
2/2
4SR8
CURBE DE FUNCTIONARE 50 Hz n= 2900 1/min
0 10 20 30 40 50 US g.p.m.
0 10 20 30 40 Imp g.p.m.
300 feet
d =65%
4SR8/42
275 900
250
800
225
50
700
4SR8/31
200
600
Inaltimea H (metri)
175
4SR8/23
35 500
150
125 400
4SR8/17
100
4SR8/13 300
75
4SR8/9 200
50 4SR8/7
4SR8/4 100
25
0 0
0 20 40 60 80 100 120 140 160 180 200 l/min
0 1 2 3 4 5 6 7 8 9 10 11 12 m³/h
Debitul Q
TIP PUTERE m³/h 0 2.4 3.6 4.8 6.0 7.2 8.4 9.6 10.8 12.0
Q
Monofazic Trifazic kW HP l/min 0 40 60 80 100 120 140 160 180 200
4SR8m/4 4SR8/4 0.75 1 27 26 25 24 23 22 20 17 13 10
4SR8m/7 4SR8/7 1.1 1.5 47 46 45 43 41 38 34 29 23 16
4SR8m/9 4SR8/9 1.5 2 60 58 57 55 52 48 43 37 30 21
4SR8m/13 4SR8/13 2.2 3 87 85 83 80 76 70 63 54 43 30
H metri
– 4SR8/17 3 4 112 110 108 104 99 92 82 70 56 40
– 4SR8/23 4 5.5 153 150 146 141 134 124 111 95 76 53
– 4SR8/31 5.5 7.5 205 200 196 190 181 167 149 128 103 72
– 4SR8/42 7.5 10 280 272 266 257 244 225 202 175 140 98
Q = Debit H = Inaltimea de pompare manometrica totala Toleranta curbelor de functionare conform EN ISO 9906 App A.
209
Sistem de stocare a lichidelor
Water storage tanks
Система хранения жидкостейa
Fișă tehnică
Stock
___________________________________________________________________________________________
Rezervor cilindric vertical
Vertical cylindrical tank
Резервуар цилиндриЧеский вертикальный
1
Se fabrică cu un racord de 1” la partea 1
With a connection of 1”at the bottom 1
Изготовляется с соединением 1” в
inferioară 2
With connections : нижней части
2
Se fabrică cu racorduri: -1 x 1 1/2”and1 x 1” at the bottom and 2
Изготовляется с соединениями:
-1x 1 1/2” şi 1 x 1” la partea inferioară; -1 x 1 1/2”at the top - 1x 1 1/2” и 1 x 1” в нижней части
-1 x 1 1/2” la partea superioară 3
Htot: total height, including cap - 1 x 1 1/2” в верхней части
3
Htot: înălţimea totală, inclusiv capac 3
Общая высота: общая высота, включая
крышку
SIMPO
(S.W. 2.2)
Attention:
This manual contains information on limitations regarding product use and
function and information on the limitations as to liability of the manufacturer.
The entire manual should be carefully read.
Table of Contents
1. INTRODUCTION ............................................................................................................................................................................. 5
1.1. General Description ........................................................................................................................................................ 5
1.2. General Specifications .................................................................................................................................................... 5
1.2.1 General Technical Specifications .................................................................................................................... 5
1.2.2 Possible Hardware Configurations .................................................................................................................. 6
1.2.3 Environment .................................................................................................................................................... 6
1.2.4 Electrical Characteristics ................................................................................................................................. 6
2. INSTALLATION ............................................................................................................................................................................... 8
2.1. Wall Mounting ................................................................................................................................................................. 8
2.2. System Components ....................................................................................................................................................... 9
2.2.1 Front panel ...................................................................................................................................................... 9
2.2.2 Configuration of the basic modules ............................................................................................................... 11
2.2.3 Description of the main PCB (control panel).................................................................................................. 11
2.3. Connection of Signaling Devices................................................................................................................................... 13
2.3.1 Connecting of Sounders ................................................................................................................................ 13
2.3.2 Connecting of Signaling Devices ................................................................................................................... 13
2.3.3 Connecting to the Specialized Inputs ............................................................................................................ 13
2.3.4 Loop Controller .............................................................................................................................................. 14
2.3.5 Maximum Permissible Cable Length ............................................................................................................. 15
2.4. Connecting to the Main Power Source .......................................................................................................................... 16
2.5. Connecting the Accumulator Battery ............................................................................................................................. 17
2.6. Connecting a Heat Printer ............................................................................................................................................. 17
2.7. Connecting an AJAX LAN/ GPRS Communication Module .......................................................................................... 17
2.8. Connecting a Network Module ...................................................................................................................................... 17
3. PROGRAMMING TYPES .............................................................................................................................................................. 18
3.1. Programming via ProsTE Software ............................................................................................................................... 18
3.2. Programming via Panel’s Keyboard .............................................................................................................................. 18
3.3. Firmware Update........................................................................................................................................................... 18
3.3.1 Firmware Update from Computer .................................................................................................................. 18
3.3.2 Firmware Update from USB Drive ................................................................................................................. 19
3.3.3 Coping Image File from the Panel to USB Drive ........................................................................................... 19
4. FULL HARDWARE RESET ........................................................................................................................................................... 19
5. PROGRAMMING OF SIMPO FIRE ALARM PANEL ..................................................................................................................... 20
5.1. General Information for Programming and Operation ................................................................................................... 20
5.2. Codes and Access Levels ............................................................................................................................................. 20
6. DESCRIPTION OF THE OPERATION MODES ............................................................................................................................ 22
6.1. Review of Alarm Events ................................................................................................................................................ 22
6.2. Review of Fault Events ................................................................................................................................................. 22
6.3. Review of Disablements ................................................................................................................................................ 23
6.4. Review of Running Tests .............................................................................................................................................. 23
6.5. Review of Warning Messages ....................................................................................................................................... 24
6.6. Silencing the Internal Buzzer......................................................................................................................................... 25
6.7. Silencing the Sounders ................................................................................................................................................. 25
6.8. Activate Evacuation....................................................................................................................................................... 25
6.9. Resetting the Panel ....................................................................................................................................................... 25
6.10. General Test ............................................................................................................................................................... 25
2
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
APPENDIX А ..................................................................................................................................................................................... 46
APPENDIX B ..................................................................................................................................................................................... 48
APPENDIX C ..................................................................................................................................................................................... 48
APPENDIX D ..................................................................................................................................................................................... 49
APPENDIX E ..................................................................................................................................................................................... 50
3
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
GUARANTEE
The guarantee terms are determined by the serial number (barcode) of the electronic device!
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective product when it is returned to the factory. All
parts replaced and/or repaired shall be covered for the remainder of the original guarantee, or 6 months, whichever period is longer. The original
purchaser shall immediately send manufacturer a written notice of the defective parts or workmanship.
INTERNATIONAL GUARANTEE
Foreign customers shall possess the same guarantee rights as those any customer in Bulgaria, except that manufacturer shall not be liable for any
related customs duties, taxes or VAT, which may be payable.
GUARANTEE PROCEDURE
The guarantee will be granted when the appliance in question is returned. The guarantee period and the period for repair are determined in advance.
The manufacturer shall not accept any product, of which no prior notice has been received via the RAN form at: http://www.teletek-
electronics.com/en/support/Service
The setup and programming included in the technical documentation shall not be regarded as defects. Teletek Electronics bears no responsibility for
the loss of programming information in the device being serviced.
WAIVER
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other guarantees, explicit or implicit (including any implicit
guarantees on behalf of the dealer, or adaptability to specific purposes), and over any other responsibilities or liabilities on behalf of the
manufacturer. The manufacturer does neither agree, nor empower, any person, acting on his own behalf, to modify, service or alter this Guarantee,
nor to replace it with another guarantee, or another liability with regard to this product.
UNWARRANTED SERVICES
The manufacturer shall repair or replace unwarranted products, which have been returned to its factory, at its sole discretion under the conditions
below. The manufacturer shall accept no products for which no prior notice has been received via the RAN form at: http://www.teletek-
electronics.com/en/support/Service .
The products, which the manufacturer deems repairable, will be repaired and returned. The manufacturer has prepared a price list and those
products, which can be repaired, shall be paid for by the Customer. The devices with unwarranted services carry 6 month guarantee for the replaced
parts.
The closest equivalent product, available at the time, shall replace the products, the manufacturer deems un-repairable. The current market price
shall be charged for every replaced product.
4
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
1. INTRODUCTION
1.1. General Description
SIMPO is an addressable fire panel with maximum coverage of 16 zones and connecting 1 to 2 loops. The panel
supports communication protocol Teletek Electronics (SIMPO TTE Loop) and operation with SensoIRIS addressable
device series.
Every SIMPO TTE Loop provides up to 250 devices (detectors and modules, regardless of the type).
An arbitrary number of devices can be added to each zone thus ensuring the easy adaptation of the system to any type
of configuration.
To avoid or significantly diminish problems when mounting the system it must be carefully planned prior to installation.
This includes: establishing an address for every device and planning a name of maximum 40 digits (including the
spaces) for each address, thereby ensuring easy access to the device.
According to the acting standards for establishing fire systems and the plan of the building, the devices must
be grouped in zones.
5
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Maximal Configuration
o Control panel (main PCB with one built-in loop controller)
o Indication (indicator PCB with mounted LCD module)
o Power supply source and 220V terminal
o SIMPO TTE Loop controller (for the second loop)
o LAN/ GPRS Communication module (for version 2.3 and higher)
o Network controller (for version 2.3 and higher)
1.2.3 Environment
Degree of protection: IP30
Operation temperature: -10ºС up to +50ºC
Relative humidity: до 95% (without condense)
Storage temperature: -10ºС up to +60ºC
Weight (without the battery): ~ 4.2 kg.
ATTENTION: Do not instal the fire panel near power electromagnetic fields (radio equipment,
electric motors, etc.)!
6
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Loading capacity
Max. loading capacity of one loop: 500 mA DC
Max. loading capacity of AUX output: 500 mA DC
Max. loading capacity of outputs SND1 and SND2: 500 mA DC
Max. loading capacity of outputs FIRE, FAULT and EXT: 300 mA DC
Max. total loading capacity (sum of the four mentioned above): 2.0 A DC
Programmable relay outputs: 15A@24VDC, 15A@120VAC, 10A@250VAC
Consumption
From the main power supply in standby mode:
o For a minimum configuration: 60 mA AC
o With mounted second loop controller: 75 mA AC
From the backup power supply in FAULT mode and generated message ‘AC loss’:
o For a minimum configuration: 125 mA DC
o With mounted second loop controller: 213 mA DC
ATTENTION!
Qualified specialists only should install the panel.
The electronic components of the panel are vulnerable to electrostatic discharge.
Never add or turn off components which are being power supplied!
7
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
2. INSTALLATION
2.1. Wall Mounting
• The panel must be installed in a clean dry place and must not be subjected to impact or vibrations (Figure 1). It must
be situated far from heating appliances. The temperature must be within -5ºС and + 50ºC. The fire panel is not
waterproof!
• Unpack the panel and observe for visible damages due to bad transport or incorrect storing.
• Open the front cover and disconnect the flat indication cable and the earthling point (Figure 2).
Figure 1 Figure 2
• Remove the front cover as dismount the side hinges (Figure 3).
Figure 3
• Choose inlets for the main power supply cable, loops, sounders, control devices, etc. Remove the metal cap element
just from those holes for cable running (Figure 4).
8
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
• Use the template in the set to fix the mounting holes of the metal box on the wall.
• Drill holes (suitable for anchors Ø6mm) on the wall and fix the metal box.
• Route the external cables onto the back box, make off connection glands etc., BUT DO NOT make any connections
at this stage. ENTER THE MAINS CABLE THROUGH ITS OWN CABLE ENTRY POINT AND KEEP MAINS WIRING
AWAY FROM SYSTEM AND OTHER LOW VOLTAGE WIRING.
• Connect the mains supply and earth to the power supply terminal (see Figure 16), BUT DO NOT apply the main
electrical supply at this stage.
• Place the battery in an upright position.
• Mount the front cover back to the bottom as mount the hinges in the reverse order of that described on Figure 3.
• Connect back the flat cable for the indication and the earthling point (Figure 2).
• Proceed with initial power up of the system and testing.
• When you finish with power up and testing steps and the panel is normal operation mode you must fix the front cover
to the bottom with the two screws for the spare parts kit.
Фигура 5
9
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The button is active at access levels 2 and 3. Use the arrows to scroll over the
Navigation
menus; in the programming menus the buttons has a specific function for changing
buttons
values and switching between the editable fields.
10
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
11
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
FAULT – Potential, monitored output for connection of auxiliary devices, 24 VDC/ 0.3А. This output is activated
in case of system trouble or fault.
EXT - Potential, monitored output for fire extinguishing, 24 VDC/ 0.3А. This output is activated in case of a fire
alarm condition.
FIRE – Potential, monitored output for connection of auxiliary devices (signaling devices for exampple), 24
VDC/ 0.3А. This output is activated in case of fire in the premisses.
AUX – Potential output for power supply of auxiliary devices, 24 VDC/ 0.5А.
SND 1, SND 2 – Potential, monitored outputs for connecting sounders, 24 VDC/ 0.5А.
IN PC (Input Protection Alarm Confirmation) – Input for monitoring of signal „Confirmation for extinguishing
started in the site“ sent by extinguishing control panel.
IN FP (Input Fault Protection Panel) – Input for monitoring of signal „Fault“ sent by extinguishing control panel.
IN AmC (Input Alarm Confirmation) – Input for monitoring of signal „Alarm confirmation“ sent by extinguishing
control panel.
LOOP 1 (-LOOP+ / +ERT / -LOOP+) – Terminal row for connecting Loop 1 in the system.
LOOP 2 – Interface connector for adding SIMPO TTE loop (for Loop 2) in the system configuration.
INDICATION – Interface connection for the indication module.
POWER – Interface connection for the main power supply unit.
JP7 – Jumper for enable/ disable the built-in battery for supporting the real time clock in case of main and
backup power supply failure.
PRINTER - RS232 interface connector for heat-printer.
USB UTG – Micro USB A/B connector for firmware update of the main microprocessor via PC or USB flash
drive; suitable also for programming via ProsTE software.
BATT – Connector with wires (red and black) for connection to the accumulator battery. The type of connection
is according the battery terminals – to every cable shoe is added a separate cable lug connector Ø5mm (M5).
Restore Defaults – Jumper for full hardware reset of the panel and restoring the factory default settings.
Earth Fault – Jumper for enable/disable indication for earth fault.
Example: If you want to enable the earth fault indication set a jumper on Earth Fault terminals.
Fuses:
AUX – 0.5А, PTC type, resettable
FAULT, EXT, FIRE – 0.3A, PTC type, resettable
BATT – 7A, PTC type, resettable
LED indication:
LED 1 (red) – Indication for scanning the devices connected to Loop1. In normal operation mode the LED
lights on continuously in 10 seconds intervals.
LED 2 (green) – Indication for data transfer between the main microprocessor of the panel and the controller
for Loop 1.In normal operation mode is constantly blinking.
12
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The monitored outputs SND, at activation, provide 24VDC@0,5A to the load connected between
them and GND*.
The monitored outputs FAULT, EXT and FIRE, at activation, provide 24VDC@0,3A to the load
connected between them and GND*.
It is necessary to connect in parallel to the last device in the loop a 10k terminate resistor,
so to ensure that the panel is able to detect any break or short circuit in the loop – see Figures 10
and 11!
Figure 11 – Example for connecting of end device (an illuminated exit sign) to the Monitored FIRE Output.
13
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Up to 250 SensoIRIS devices can be connected to SIMPO ТТЕ loop controller (up to 180 of them with isolator).
The general connection diagram of devices to the loop controller is shown on Figure 13.
The maximum current consumption of the devices in the communication line is Imax = 500mA. If the consumption
exceeds this value an over-load protection would be turned on.
Detector 1 Detector 2 Detector N
In the configuration of addressable fire alarm panel SIMPO could be mounted a second loop controller as a separate
module – see Figure 14.
ATTENTION! Do not add or remove loop expanders to the fire panel configuration when
the main and backup power supplies are on!
- Connect the connectors: LOOP 2 of the main control panel and LOOP of the second loop controller.
- Fix the second loop expander to the metal box of the fire panel using the supplied bolts in the spare parts
kit.
LED 1/ LED 2 – LED indication for the loop controller status, analogical to that for the main control panel – see
the description on page 12.
14
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
ATTENTION! SIMPO ТТЕ Loop controller supports up to 250 devices, regardless of the type, as up
to 180 of them can be with connected isolator!
To ensure the correct operation of the system is necessary to make some calculations in advance:
1. To ensure the ability of the fire 2. To ensure the ability of the fire 3. To ensure the ability of the devices
panel to receive the signals from the panel to recognize the double in the loop to receive command
devices in the loop, calculate: addresses in the system, calculate: signals from the panel, calculate:
where:
LC1max, LC2max, LC3max - are maximum permissible length of the used cable, [km];
RC - is total ohm resistance of the two wires of the used able; its value shows the magnitude of the cable resistance at
length 1km [Ω/km];
Ri - is the total resistance of the isolator modules in the loop;
Imax - is the maximum current consumption in the loop - total amount of the current consumption of all devices in the
loop *.
ATTENTION! Always calculate the maximal cable length according the mentioned above formulas!
If LC > LC1max or LC > LC3max - the fire panel would not be able to communicate with the devices.
15
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The connection diagram shown on Figure 15, gives the possibility to protect devices against opening and short circuit.
For example, short-circuit in section 2 will not influence the operation of sections 1 and 3. The isolator modules at the
both ends of section 2 will isolate it, and section 1 and 3 will continue working properly, as section 1 will operate by
supply from the channel “A” and section 3 - by supply from channel “B”. Since the fire panel will not be able to
communicate with the devices from section 2, it will generate an alarm signal for lost devices and open circuit.
Section 2
Section 1 Section 3
Channel А Channel В
Figure 15 – Example for connecting of detectors and call points to a loop expander
(the built-in in the main control panel or SIMPO TTE Loop)
The maximum number of devices between two isolator modules (module isolator device or using
the built-in module isolator in a device) is 30!
Fuse 4А
Type: glass time-delay
Main
Power
Source
Figure 16. Connecting the main power supply cable to the 220V terminal
16
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The battery cannot power up the panel before the mains supply has been switched on! The
charging of the accumulator battery is done at maximum current I = 2A and charging voltage U ≤
13.65V.
17
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
3. PROGRAMMING TYPES
3.1. Programming via ProsTE Software
The specialized ProsTE software is designed for programming of intruder and fire alarm panels produced by Teletek
Electronics JSC. To program the fire alarm panel SIMPO you should first to install the ProsTE software on your
computer – the program can be downloaded free of charge after registration on the website of the producer:
http://www.teletek-electronics.com/en/products/software/Programming/ProSTE.htm
To program the SIMPO panel you have to use specialized “cable ProsTE”. If the computer you are using for the
programming is not equipped with RS232 interface, you should use also a cable converter RS232-USB – Figure 18.
The detailed description of all buttons on the front panel is presented in item 2.2.1 – 5, page. 9
The detailed description of Maintenance and Installer programming access levels is presented in item 5.
ATTENTION!
The firmware update of the main microprocessor of fire alarm panel SIMPO should be performed by
qualified personnel only and after held training program by the producer Teletek Electronics JSC!
18
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Use the Windows Explorer file manager to copy the new image update file (with *.bin extension) in Removable
Disk directory.
When the coping of the image file completes, remove the Removable Disk, as select Eject option from its
dialogue box (right click with the mouse over it).
If the data in the image file are correct, the panel starts the firmware update procedure of the main
microprocessor accompanied with short beeps.
Disconnect the USB cable.
The panel will reset itself automatically after a successful firmware update.
Wait until the polling procedure is complete - USB drive will be displayed with its name and manufacturer. On
the last row of the screen will start blinking the notice Press 'Enter' to continue.
Press Enter button and wait for a message for the USB drive capacity. On the last row of the screen will be
active two buttons (2) To Panel and (3) From Panel.
Press (2) To Panel button. A list with the present image files (with *.bin extension) copied to USB drive is
displayed on the screen, as the software revision is displayed on the right side, for example:
0:/SIMPO/SIMPO2_0.BIN v 2.00
Scroll through the listed files using the buttons with up and down arrows – the currently selected file is blinking.
Select the file and press Enter button.
The panel starts uploading the file from the USB drive to the external Flash memory of the panel. The running
process is displayed with a progress bar.
If the data in the image file are correct, the panel starts the firmware update procedure of the main
microprocessor accompanied with short beeps.
Disconnect the USB cable.
The panel will reset itself automatically after a successful firmware update.
19
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
When turned on, the panel always conducts a procedure of loading the parameters, which usually takes about 5-6 sec.
There is no access to the menus of the panel during that procedure.
Upon the initial startup, the panel does not hold any configurations. Initialization may take several minutes. The
initialization time needed depends on the number of periphery and loop devices – for Loop 1 and Loop 2. After the
panel has been turned on, it performs a procedure for detecting newly installed loop devices – see also APPENDIX C,
page 48.
Right after the initial startup of the mains power supply and initialization completed the panel turns to normal operation
mode. If there are any active alarm and fault messages they are displayed on the screen, as the indication follows the
priority:
The name of the current active indication group is blinking together with the number of the first message. Press the
ENTER button to review some additional information for the respective message as data and time of occurring, device
address, zone number or other, according the trouble type.
The indication for the active ALARMS in the system is viewed with highest priority.
The addressable fire alarm panel SIMPO supports different languages for the programming menus.
The factory default setting of the language is in English. You can change the language after the initial power-
up as enter in sequence:
Press CANCEL – enter code 3333 – select menu 6) GENERAL SETTINGS – menu 6.4) PANEL SETTINGS –
Button 1 – Button ENTER
Use the ENTER button to enter in programming menus and confirmation of entered values and parameters; the
functional digit buttons are used for entering of access codes and changing the current status; the navigation buttons
(up/ down and left/ right arrows) are used for scrolling through the menus and for changing the editing field.
Code
Level Description Access
Combination
Only Silence buzzer and Evacuation* buttons are active. It is not allowed to
1 User - enter Maintenance and Programming access levels.
* Just for that cases, when the fire alarm signal is received from a device
Silence buzzer, Silence sounders, Reset and Evacuation buttons are active.
2 Maintenance 2222 Maintenance access level entry, which allows partial programming and menu
settings.
Silence buzzer, Silence sounders, Reset and Evacuation buttons are active.
3 Installer 3333
Installer access level entry, which allows full programming and settings.
The introduced code combinations are visualized with “*“ symbol. The entry is automatic.
20
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The access codes could be changed only from level Installer - menu 6) General Settings - submenu 6.1) Access
codes.
There are different restrictions on the panel functions in the relative access levels, which are shown in the following
table:
Access Level
Mode/ Menu Description
1 2 3
ALARMS Viewing the Alarms Messages in the system.
FAULTS Viewing the Faults Messages in the system.
DISABLEMENTS Viewing the active disablements in the system.
TESTS Viewing the running tests in the system.
Operation modes
* Just for that cases, when the fire alarm signal is received from a device
- The operation modes and the menus are not supported for that access level
- The operation modes and the menus can be reviewed or are allowed for partial programming for that access level
21
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Example:
The User can review also some additional information for every of the alarm events. For this, select the number of the
alarm message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER button.
On the screen is displayed information for the loop number and the address of the device sensed the alarm event. At
the bottom of the screen is displayed the day and time of occurring of the respective event. Note that the additional
information is different according the type of the alarm event. To exit the review alarm events mode, press CANCEL
button.
Example:
The User can review also some additional information for every of the faults events. For this, select the number of the
fault message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER button.
In case, there are active alarms in the system, but you want to review the fault messages, press button (2) – FAULTS
mode. The present faults in the system are displayed with serial numbers. The reviewing is the same as described in
item 6.1. The total number of active faults is displayed at the bottom right corner of the screen. Use button (1) to go
back to ALARMS mode and reviewing the alarm messages.
22
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Example:
The User can review also some additional information for every of the disablements. For this, select the number of the
disablement message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER
button.
In case, there are active alarms and/ or faults in the system, but you want to review the disablements, press button (3)
– DISABLEMENTS mode. The disablements in the system are displayed with serial numbers. The reviewing is the
same as described in item 6.1. The total number of the introduced disablements is displayed at the bottom right corner
of the screen. Use button (1) to go back to ALARMS mode and reviewing the alarm messages.
Example:
The User can review the number of the zone in test mode. For this, select the number of the zone using up/ down
arrow buttons (the number of the selected event is blinking) and press ENTER button.
In case, there are active alarms and/ or faults in the system, but you want to review the running tests, press button (4)
MORE>> – TESTS mode is blinking. The running at the moment tests in the system are displayed with serial numbers.
The reviewing is the same as described in item 6.1. The total number of the running tests is displayed at the bottom
right corner of the screen. Use button (1) to go back to ALARMS mode and reviewing the alarm messages.
To review the running TESTS at active alarms and/ or faults in the system:
23
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Example:
The User can review also some additional information for every warning message. For this, select the number of the
message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER button. On the
screen is displayed information for the loop number and the address of the device. At the bottom of the screen is
displayed the day and time of occurring of the warning. Note that the additional information is different according the
type of the warning event.
In case, there are active alarms and/ or faults in the system, but you want to review the warnings, press button (4)
MORE>> – (3) WARNING mode. The warning messages in the system are displayed with serial numbers. The
reviewing is the same as described in item 6.1. The total number of the warnings is displayed at the bottom right corner
of the screen. Use button (1) to go back to ALARMS mode and reviewing the alarm messages.
24
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Level 1: Just for that cases, when the fire alarm signal is received from a detector in a zone.
To start the sounders for evacuation alert, the user has to press the button.
Levels 2 and 3: In case there is no fire alarm signal from a detector in a zone.
To start the sounders for evacuation alert, the user has to enter in sequence:
Maintenance Code – 2222
Installer Code – 3333
After resetting are cleared also all introduced earlier test in zones and disablements. The introduced delays are not
cleared. The panel returns to normal operation mode.
To start the general test press button – all LEDs must light on and the internal buzzer starts sounding. On the
LCD module every one position is displayed with 5x8 dots. The panel will automatically exit the general test mode after
5 seconds. The general test can be stopped also with next pressing of the same button.
25
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Cancelation of entered parameters and settings; Step back in the menu structure.
Total Entries - Shows the total number of the recorded events in the
memory log file.
Total Alarms Count - Shows the total number of the registered
alarm events.
Use the functional digit buttons to enter the respective submenu.
Exit to the main screen of VIEW LOG menu is realized with CANCEL button.
26
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
In “From date” field enter the new date using the buttons:
- UP arrow for increasing the number
- DOWN arrow for decreasing the number
- LEFT/ RIGHT arrows for changing the editing field
Then press the ENTER button – at the screen is displayed the first event for the entered date with time.
Exit to the main screen of VIEW LOG menu is realized with CANCEL button.
Exit to the main screen of VIEW LOG menu is realized with CANCEL
or (3) NO button.
Note: The ‘CLEAR’ submenu is not available in the Maintenance access level (2).
From the main screen of VIEW LOG menu press (4) PRINT button. The screen displays two fields for setting a time
interval for the extract. Two additional submenus for printer settings are available also.
In the fields “From date” and “To date” enter the time interval for
printing. You can use also the functional digit button to select:
1 – PRINT SETTINGS. Press to enter in submenu for printer settings.
2 – PRINT ALL. Press for direct printing of all recorded events in the
system LOG file.
Press the ENTER button to start printing. The system will ask for confirmation before starting the printing.
4 – Press the button to change the size of the used paper. The
possible size formats are: 37/ 57/ 80 mm.
27
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Submenu (1) GO TO. Enter the zone number you want to go. After pressing the button the screen displays:
Submenu (2) DEV. COUNT. The submenu shows information about the total number of the devices in the
respective zone. From the main screen of ZONES menu select a zone number and press button (2). The
screen displays information about the total number of the devices in the selected zone regardless of their
current state.
Example:
Exit to the main screen of ZONES menu is pressing button ENTER
or CANCEL.
During the test mode the installer activates detectors in the zone (applies heat or smoke) to check their proper
operation. The panel confirms the receiving of fire alarm messages with short sound signals and the number of the
tested zone is blinking.
To stop the zone test, press the (3) ‘STOP TEST’ functional button. The zone returns to normal operation mode.
After completing the zone testing, reset the panel, as described in item 6.9.
28
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
From the main screen of ZONES menu the User can set additional parameters for every zone in the system. To set
zone parameters, select its number using the up/ down arrow buttons and press ENTER button.
In the new sub screen first you can enter a 40-symbol long name for the zone. Use the functional button to set the
operation mode, delays T2 and a group number.
In NORMAL mode any detector activation within the system generates an alarm event to the respective zone.
In DOUBLE mode any detector activation within the system generates a PREALARM event to the respective
zone,but also awaits the activation of another detector from the same zone to generate a FIRE signal. The
RESET command shall disable the FIRE and PREALARM events. If during 5 minutes there is no other fire
alarm signal from the same or other detector in the zone the FIRE alarm will be ignored. The operation of a
zone in DOUBLE action mode is shown in the examples below.
29
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
EXAMPLE 1 EXAMPLE 2
5 min 5 min
Time Time
EXAMPLE 1: In this case the fire panel will not activate the sounders and the signalization on the front panel because
during time interval 2 no second alarm signal is generated.
EXAMPLE 2: In this case the fire panel will activate the sounders and the signalization on the front panel because
during time interval 2, two alarm signals are generated.
After RESETTING of the panel, the events FIRE and PRE ALARM are cleared, and LED ‘General Fire’ light off.
To enter in the submenu for DELAY Т2 setting, press button (3) DELAY T2 from the zone parameters programming
screen.
In the SOUNDERS field set the time delay for sounders (SND1 and SND2) outputs activation. The time delay
can be in range from 0 up to 540 seconds.
In the FIRE BRIGADE field set the time delay for FIRE output activation. The time delay can be in range from
0 up to 540 seconds.
In case of activation of more than one zone, the delays to the outputs are caused by the zone with shorter delays.
The editing value is blinking. Set the time delays using the navigation buttons: up (increasing) and down (decreasing)
arrows to change the value, and left and right arrows to move over the fields.
The set time delays T2 are confirmed with the ENTER button.
30
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
To enter in the submenu for group setting, press button (4) GROUP from the zone parameters programming screen.
In the field CHOOSE GROUP set the number of the group from 1 to 16. To increase the value press ‘up arrow’ button
and to decrease it – the ‘down arrow’ button. The set group number is confirmed with ENTER button.
Exit to the main screen of ZONES menu is realized with CANCEL button.
From the main screen of DEVICES SETUP menu, the User can review detailed information for all connected devices in
the system configuration.
The address number of the currently editing device is blinking. Additional submenus are available through the
functional digit buttons.
Submenu (1) GO TO allows quick access to a device address in the respective loop number. The currently editable
value is blinking. Use up and down arrows to select device address. Use the left and right arrows to switch over the
editable fields. Confirm with ‘ENTER’.
Submenu (2) DEV. COUNT allows the User to check the total number of the devices connected to the system
configuration. The exit to the main screen of DEVICE SETUP menu is with pressing ENTER or CANCEL button.
31
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The new found devices in the system are presented with a fault type message on the main screen and a pulsed sound
signal. You can silence the buzzer with pressing the ‘SILENCE BUZZER’ button. Then enter the installation menu and
select ‘3. Devices Setup’ Menu. Press ‘ENTER’ button and follow the structure below.
To save the new found devices press the (3) SAVE button. The panel will ask if you want to save the selected device
only or all new found devices in the configuration. Choose button (2) THIS to save only the selected device and button
(3) ALL to save all new devices. The exit is automatic to the main screen DEVICE SETUP, as the saved devices are in
normal operation mode.
Note: The panel automatically saves the new devices on the serial address. The other types of addressing or changing
the current set address are described in item 7.4.
The panel will ask if you want to remove the selected device only or all present devices in the configuration. Choose
button (2) THIS to remove only the selected device and button (3) ALL to remove all devices (regardless of their
current status). The exit is automatic to the main screen DEVICE SETUP.
Note: If after deleting, the removed devices are still connected physically to the system, the panel will find then and will
alert with “New Loop Devices Found” fault messages. To avoid this, it is recommended first to disconnect the device from
the system and after that to remove it from DEVICE SETUP menu.
The panel will not follow the operation of the disabled device and will not respond to fire or fault messages from it. To
enable the device again, select its address and press the active button (4) ENABLE.
Note: If at the moment of enabling the device, it is in fire alarm mode (the fire signal was generated earlier, when the
device was still disabled) the panel will alert for the fire alarm situation immediately!
32
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Attention: Programming device type parameters is available only from access level 3!
The SIMPO fire alarm addressable panel operates with full range of SensoIRIS addressable detectors, call points,
sounders and modules via Teletek Electronics communication protocol. According the type of the device the setting
parameters are different. Use the descriptions below to set the devices in your system configuration.
To set parameters of a device go to its address number in the DEVICES SETUP menu (the editable address number is
blinking) and press ‘ENTER’.
Note: You can make the device settings also for NEW and DISABLED devices.
Association to a zone number. The first editable parameter is setting the zone number for this device. Use the up
and down arrows to set the zone number according your specific system configuration. By default all devices are
associated to Zone 1.
Entering of a specific name. The installer can enter a specific name for every device. The name can be up to 40
digits long and it is entered on the second row. Use the left and right arrows to move the cursor. The symbols (small
and capital letters and characters) are set with the up and down arrows. Confirm the entered name with ‘ENTER”. See
also the APPENDIX B.
Use the functional digit buttons to enter the respective submenus according the type of the selected device.
After pressing button (1) SENSITIVITY you are entering the submenu
for setting the sensitivity level of the smoke chamber for DAY and
NIGHT alarm mode.
Use the functional buttons (2) and (3) to select the sensitivity level:
Normal/ Middle/ Low/ High.
After pressing button (1) CLASS you are entering the submenu for
setting the class for DAY and NIGHT alarm mode. Use the functional
buttons (2) and (3) to select the class: A1R/ A2S/ BS.
33
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The class for SensoIRIS M140 is fixed to A1R and could not be changed.
All set parameters are confirmed wit ENTER button.
(4) SOUND TYPE – Choose the sound type. In the submenu enter number from 1 to 32 – see Table 1 for the different
sounder types.
34
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
35
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
The activation of the SensoIRIS MINP input can be programmed according the application. To program the generated
event at the input, press button (1) INPUT – in the submenu are active two fields for setting:
GENERATES – Use the up/ down arrow buttons to select generated event at the input: FIRE/ EVACUATE/
НУЛИРАНЕ/ MESSAGE ALARM/ MESSAGE FAULT/ MESSAGE WARNING/ SILENCE BUZZER/ SILENCE
SOUNDERS
DELAY – The field is common for all events. Enter time delay 0-600 sec for activation event.
Use the left and right arrows to switch over the GENERATES and DELAY fields.
Press the functional button (2) GROUP to enter in submenu for group selection. In the editing field enter the group
number using the up/ down arrow buttons.
All set parameters are confirmed wit ENTER button. The exit to the main screen of DEVICE SETUP menu is with
pressing CANCEL button.
36
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Use the functional buttons to set parameters for inputs and outputs.
The programming is same for all of the outputs/ inputs.
For the settings of the ‘INPUTS 1/2’ refer to the submenu of
SensoIRIS MINP.
For the settings of the ‘OUTPUTS 1/2’ refer to the submenus of
SensoIRIS MIO-04.
Relay module with interface for 240 VAC. The module is available in
two versions with 1 and 2 relay outputs. Use the functional buttons to
set the following parameters:
(1)/ (2) OUTPUT – Set the parameters for the output – see the
description of module SensoIRIS MIO-04.
(4) ON/ OFF LED BLINK – Alternatively changes the status of the
device LED indication.
All set parameters are confirmed wit ENTER button. The exit to the main screen of DEVICE SETUP menu is with
pressing CANCEL button.
37
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Parameter Settings
Activation type Loop Group Zone Device Input
Logic Behavior
No No No No No*
DEVICE 1/2 - - 1 - 250 1-4 - Latched/ Unlatched
INPUT GROUP - 1 - 16 - - - AND/ Latched/ Unlatched
OR
FIRE ZONE - - 1 - 16 - - - Latched
FIRE ZONE GROUP - 1 - 16 - - - AND/ Latched
OR
FIRE (common) - - - - - - Latched
FAULT ZONE - - 1 - 16 - - - Latched/ Unlatched
FAULT ZONE GROUP - 1 - 16 - - - AND/ Latched/ Unlatched
OR
FAULT (common) - - - - - - Latched/ Unlatched
FAULT SYSTEM - - - - - - Latched/ Unlatched
PRE ALARM ZONE - - 1 - 16 - - - Latched/ Unlatched
DISABLE (common) - - - - - - Latched/ Unlatched
SOUNDER ON - - - - - - Latched/ Unlatched
RESET - - - - - - Unlatched
EVACUATE - - - - - - Latched
SILENCE BUZZER - - - - - - Latched/ Unlatched
SILENCE ALARM - - - - - - Latched/ Unlatched
TEST - - - - - - Latched/ Unlatched
38
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
This menu allows the installer to set or change the device address or to perform self-addressing procedure. The type of
addressing depends on the installer’s preferences and the system capacity and configuration.
The installer can use two addressing procedures for adding new devices to the system configuration.
- AUTO ADDRESSING. The new devices are directly connected to the panel Loop 1 and/ or Loop 2. The panel
will recognize them and gives automatically addresses according the order of the devices in the line. The panel will
start with the first free address in the system configuration. The installer can SAVE the new devices one-by-one or all
at the time from the Menu 3. Devices Setup.
- SELF ADDRESSING. The new devices are prepared for connection to the system configuration - the loop
line is ready but the devices are not installed (the detectors and sounders are not mounted to the bases, the call points
and modules are not connected to the loop). The installer enters 4. Addressing - 4.3. Self addressing menu. The panel
shows the first free address for every of the loops. Now the installer can start mounting detectors and modules one by-
one. The panel will set the displayed address number to the mounted device and automatically proceeds with next free
address in the system.
To set address to a device, enter in the installer’s menu - 4. ADDRESSING - 4.1. SET ADDRESS. The device must be
prepared for connection to the panel (loop 1 or loop 2).
The system automatically shows the first address in the system. You can check the device assigned at this address
with pressing the ‘LED ON’ button - the LED(s) of the device will lighting on permanently. Next pressing of the same
button will off the LED. Use the button ‘CHANGE’ to switch to loop 2 if present in the system. The address is free if
‘SAVE’ button is active.
To find a free address use the up and down arrows to scroll over the address numbers.
The free address in the system configuration is recognized with active ‘SAVE’ functional button (2) in the last row of the
screen. Take the new device and connect it to the system - mount the detector or siren to the base or connect the
module to the loop. Press the ‘SAVE’ button and wait for a couple of seconds. If the addressing is successful the
message ‘SUCCESSFUL’ starts blinking on the screen. If the message is ‘ERROR’ then there is a problem - the device
is not properly connected; there is no communication with the panel. You can proceed with setting the next address or
escape with ‘CANCEL’ button.
The system automatically shows the first address in the system. Use the up and down arrows to select the address of
the device you want to change.
39
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Use again the up and down arrows to find a free address in the system configuration - the active ‘SAVE’ functional
button (2) in the last row of the screen will appear. Press the ‘SAVE’ button and wait for a couple of seconds. If the
address changing is successful the message ‘SUCCESSFUL’ starts blinking on the screen. You can proceed with
changing other address or escape with ‘CANCEL’ button.
7.4.3 Self-Addressing
In this submenu the installer can perform self addressing procedure of devices to the system configuration. The self
addressing procedure is suitable when there are great amount of devices to be connected to the panel.
The new devices are prepared for connection to the system configuration - the loop line is ready but the devices are
not installed (the detectors and sounders are not mounted to the bases; the call points and modules are not connected
to the loop).
To perform self addressing, enter in the installer’s menu - 4. ADDRESSING - 4.3. SELF ADDRESSING. The panel
shows the first free address for every of the loops. Now the installer can start mounting detectors and modules one by-
one. The panel will set the displayed address number to the mounted device and automatically proceeds with next free
address in the system.
IMPORTANT NOTES!
1. During the self addressing procedure leave minimum 10 sec time interval between connecting the
next device to the loop.
2. NEVER connect devices to both loops at the same time. Connect all devices to loop 1 first and
after that proceed with loop 2.
3. Write the address number of the device on the provided sticker - for detectors and sounders on
the base, and for modules and call points - on the PCB.
4. After completing the self addressing procedure test the devices with LED indication on.
40
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
To set outputs parameters, enter in the installer’s menu - 5. PANEL OUTPUTS. The submenus are allocated in two
screens.
Attention: In access level 2 you can only review the set delay status (ON/ OFF), with no rights to change it!
41
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Attention: In access level 2 you can only review the set delay status (ON/ OFF), with no rights to change it!
Attention: The relay outputs are available for setting parameters only from access level 3!
In this submenu the installer can the set parameters of the relay outputs on the control panel PCB.
To access the RELAY OUTS submenu, enter in the installer’s menu - 5. PANEL OUTPUTS - MORE>> - RELAY OUTS
(2).
Attention! The order of the relay numbers follows that on the control panel PCB!
For the settings of the relay outputs refer to the description of the menus for SensoIRIS MIO-04.
The exit to the main screen of PANEL OUTPUTS is with pressing the CANCEL button.
42
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
A list with submenus is displayed after entering the installer’s menu - 6. GENERAL SETTING. The currently selected
submenu is blinking. To enter into a submenu press ‘ENTER’.
Default codes:
INSTALLER: 3333; MAINTENANCE: 2222
If the installer’s access code is changed and obscured you have to perform a hardware reset of the
panel settings!
The editable field is blinking. Use the up and down arrows to set the date and time. Use the left and right arrows to
switch over the editable fields.
43
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
IMPORTANT NOTES!
The SIMPO panel is equipped with built-in battery for saving the set time and date in case of main or
back-up power supply lost.
Put a jumper on JP7 terminals on the control panel PCB to enable the built-in battery and saving the
set time and date.
Press the functional button ‘2’ to select the preferred alarm mode:
NIGHT - Select to set nighttime alarm mode. The devices will operate
only in night alarm mode.
DAY - Select to set daytime alarm level. The devices will operate
only in day alarm mode.
SCHEDULE - Select to set operation on a schedule. The devices will
operate on the programmed schedule.
44
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
Use the functional buttons to set: Use the functional buttons to set:
(1) LANGUAGE - Press to set the language. Every (1) Earth Fault - Press to enable/ disable the Earth
pressing of the button changes the currently used Fault indication. When the Earth Fault indication is
language for the menus. enabled you have to set a jumper to Earth Fault
(2) + Brightness - Press to increase the brightness terminals on the control panel PCB.
of the screen back light. The maximum value is 20. (2) BATTERY - Press to enable/ disable the
(3) - Brightness - Press to decrease the brightness Accumulator Battery Fault Indication. When the
of the screen back light. The minimum value is 0. Accumulator Battery Fault Indication is enabled the
(4) MORE>> - Press to switch to other panel panel will monitor the internal battery resistance Ri. In
settings. normal operation Ri<0.3Ω. If Ri>0.3Ω, the panel will alert
for Battery fault with message in Faults menu ‘Battery
Confirm all settings with pressing ENTER button. High Resistance’. The installer has to change the
accumulator battery with new.
(4) << BACK - Press to switch back to previous settings.
7.6.5 Delay Т1
In this submenu the installer sets the time to Delay T1. T1 is the time delay needed for reaction of the security
personnel on the protected site. T1 provides a time delay for the personnel to go to the zone in fire alarm and to check
the situation. The operation of time delays T1 and T2 are described with the algorithm below.
To access the DELAY T1 submenu, enter in the installer’s menu - 6. GENERAL SETTING - 6.5) DELAY T1. The
screen displays:
Use the up and down arrows to set the delay T1. The time interval is
in range 0 - 60 sec.
Confirm the settings with ‘ENTER’ button.
45
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
APPENDIX А
Table: Event Messages.
Message Description
Flash Error FLASH Memory error is detected.
Ram Error RAM Memory error is detected.
New Periphery Devices Found New periphery devices are found in the system configuration.
Periphery Device Fault The device is not responding (the device is lost or failed).
Periphery Device Type Error A periphery device with different type is found on the address.
AC Loss The charging device is failed.
Battery Low The accumulator battery is discharged.
Battery Loss The accumulator battery is missing.
Battery High Resistance High value (Ri>0.3Ω) of the battery internal resistance. Replace the battery immediately!
Earth Fault Resistive connection between some signals and earth < 10k.
Charger Fault The charging unit is failed.
Sounder1 Short Short circuit detected at Sounder 1 output.
Sounder2 Short Short circuit detected at Sounder 2 output.
Sounder1 Open Circuit broken at Sounder 1 output.
Sounder2 Open Circuit broken at Sounder 2 output.
Fire Output Short Short circuit detected at Fire output.
Fire Output Open Circuit broken at Fire output.
EXT Output Short Short circuit detected at Extinguishing output.
46
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
47
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
APPENDIX B
Table: Text and symbols for introducing device and zone names.
In device or zone name entering mode every pressing of up/ down arrow button changes the entered letter or symbol.
When moving to the next new position the entering starts from the begging of the table.
! ” # $ % & ‘ ( ) * + , - . / 0 1 2 3 4 5
[
6 7 8 9 : ; < = > ? @ A B C D E F G H I J K
L M N O P Q R S T U V W X Y Z [ ] ^ _ ` a
b c d e f g h i j k l m n o p q r s t u v w
x y z
APPENDIX C
Initial power up of the system.
48
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
APPENDIX D
Two steps of alarming Algorithm.
49
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
APPENDIX E
Tree structure of the programming menus.
The presented tree structure describes the full access to the programming menus from level 3 – Installer. From access
level 2 – Maintenance, some of the programming menus are not displayed or the operation with them is partially limited
– see also the Table on page 21.
50
SIMPO Addressable Fire Alarm Panel – Installation and Programming Manual
51
www.teletek-electronics.com
9^cdQ\\QdY_^Q^TEcUb]Q^eQ\
2 B-TEL2
! !!
'"($
)
"($
)
"($
)!
)
)
* )
)
+
)
)
I
,
"($
)
%
"($)
*
/
)
"($
)!
)
)
"-.$ "-.$ "-01.$ G
2
*
)
*
!
"
$
"
$
3"
$
E
,
2
%
)
/
)
3
)
45'465
45'415"
)
$
"
2$ 45'415"
$
,
2 /
)
$ 8
7
6
2
"
"',65$ ,
5$
"2
)65$
*
2
)
)
)
!
'
8
9
)
2*)-*)&/
&,0:
%&'()*+,)**)-.)&/01 %&'(),,,02*)-2)3/6
2
0/')%&)*)-)"
2
2
;,<#$
2%&)*)-0)/'"
2
2
;,<#$
4 2
05'0!&)*)-"
2
2
;,<#$
2
0/')/0*)-)"=2
2
$
2/0*)-0)/'"2
2
$
4 2
05'0/0*)-"=2
2
$
2
8
7
9
)
%&60(7%%'8:
7')
0/*.)&/0: ')
0/*2)3/:
";,<#$
$
)
*
)>
#$
4 B-TEL2
INDEX
5 B-TEL2
INTRODUCTION
GENERAL FEATURES
FEATURES
Vocal and digital dialer
4 independent alarm channels with priority management. G
Option to control Stop Alarm and Listen-in features remotely by entering a PIN into the remote telephone
keypad.
Option to associate up to three voice messages for every event, with four message choices:
z two messages, each 32 seconds long;
z four messages, each 16 seconds long;
z one 32 second long message plus four messages, each 8 seconds-long;
z eight messages, each 8 seconds long.
Built-in multiprotocol digital communicator.
Programmable alarm-call activation by positive drop or negative command.
Programmable PIN to Stop Alarm via device keypad.
8 programmable telephone numbers.
Protection against accidental battery polarity inversion.
Battery and system status checks.
255-element logger (event register).
Programming by software or keypad.
Superkey function.
2 programmable OC (Open Collector) outputs.
Telephone line
Test for telephone line cutting.
Signals telephone line failures on an Open Collector output or with a speaker tone.
Excluded line tone control.
Overvoltage protection.
Programmable tone or pulse dialing.
Interface
Digital message recording/playback.
Built-in speaker for message playback.
Single-digit LED display.
Alphanumeric command keypad.
Box
Tamper protection (anti-opening and anti-tearing).
Compartment for 12 V – 1.2 Ah battery (not provided).
DESCRIPTION
Telephone dialers are signaling devices that can call and send pre-recorded messages to a series of programmed telephone numbers.
The B-TEL2 dialer is available in a plastic box (ABS) that can be attached to the exterior of the control panel to which it must be connected.
The dialer is designed to operate 4 channels, and thus control 4 distinct events (such as the burglar and fire alarms). Alarm messages can be
associated with each channel.
These messages are recorded in the solid-state memory, avoiding the problems associated with using magnetic tape, including: loss of message
quality over time, mechanical hitches after long periods of inactivity, etc…
An internal speaker allows one to check the quality and accuracy of recorded messages.
Programming all the typical parameters of this device is simplified by the use of an alphanumeric keypad and LED display. The device can also
be programmed with the appropriate software.
) All programmed data (including alarm messages) are stored in the non-volatile memory for an indefinite length of time, even
when power is not present.
The plastic box is provided with tamper protection (against unauthorized openings) and optional anti-tearing protection. The box can house a 12
V - 1.2 Ah battery
CAUTION - After the dialer is installed, it may be necessary to remove the front panel for maintenance or repair
purposes. Bear in mind that if the tamper switch is connected to the corresponding line of an anti-intrusion
system, the latter can cause an undesired alarm. Therefore, before removing the front panel of the dialer, make
sure that the panel's alarm group is disabled (refer to the control panel's instructions for information on how to
disable the alarm group).
2. Pass the connection cables through the opening [8] and mount the dialer using the holes [3].
3-4 [L.I.] Internal telephone line. These terminals are used to connect other devices that will share the line
(telephone exchanges, telephones, fax, modem, etc.).
the event of an alarm, the dialer will use the telephone line to which it is connected for the time
necessary to carry out the programmed call cycle.
-] Ground
5 [-
CAUTION - As required by telecommunication systems safety standards, the 5 [-] terminal must be connected
to the ground of the electrical circuit to protect the dialer from overvoltage on the telephone line.
6-7 [A.S.] Tamper. These terminals are connected to the tamper switch [14] and are normally closed. They
open when the box's front panel is removed (anti-opening protection). Connect these terminals to the
tamper line of the security system control panel.
CAUTION - During a power failure, no voltage will be present at the [+12] terminal. In order to continue powering
loads, draw the voltage directly from the battery's positive terminal.
11-12-13-14 [L1][L2][L3][L4] Alarm channels. Normally, these terminals must be connected to Positive.
When Positive drops, the dialer will call the telephone numbers and playback the alarm message associated
with that alarm channel.
IMPORTANT - Channel #1 is prioritized over other alarm channels. If channel #1 is activated, the channel
#1 call cycle will be performed, even if the dialer has already begun another channel's call cycle.
15-16 [+12] [M
M] Power supply. The dialer can be powered by two different voltages, 13.8 Vcc or 27.6 Vcc.
7 B-TEL2
CAUTION - Before applying voltage to terminals [+12] and [M
M], ensure that the jumper [18] is correctly
positioned.
BASIC CONNECTIONS
The basic connections are necessary for dialer function. They are illustrated, with the channels highlighted, in
Figure 3. In the connection example, alarm channel L1 is connected to the normally closed contact (NC) of the
burglary system and receives, under normal conditions, the positive input voltage. G
) The dialer's default programming allows for activation by the absence of the positive signal ('Positive drop',
factory setting, see jumper [16]). Should this setting change (activation with a 'Negative command') the
alarm channel must be connected to a ground output in the event of an alarm (for example, Open-Collector).
A UXILIAR
UXILIARYY CONNECTIONS
The dialer does not require auxiliary connections in order to function. However, these connections provide
many useful options. All auxiliary connections are shown in Figure 3 and described in the following paragraphs.
Tamper - Connection to tamper line terminals allows detection of possible attempts to tamper with the dialer
box. In Figure 3, these terminals are connected in series to the security system tamper line.
Connection to other devices - The B-TEL2 is provided with 4 alarm channels. Channel 1 can, for example, be
used to connect the alarm relay of a fire-protection system (as shown in the example), or the anti-theft alarm
relay of a burglary system (connected to Channel 2 in the example) or a radio-receiver relay (telecare).
Interrupt alarm cycle - An alarm channel can be used for the Stop Alarm function. For example, a momentary
positive activation of the 14[L4] terminal can interrupt the alarm cycle already underway (see also "Stop Alarm"
in the PROGRAMMING chapters). In order for this feature to function, Channel L4 must be programmed (by
software or keypad) as "Positive command".
A CTIV
CTIVAATION POLARITY
The dialer can be activated with positive or negative polarity signals (as specified in Table 2). To set activation
polarity, move the jumper [16] (see Figure 1). The dialer is factory-set to be activated with positive polarity
signals.
Activation mode can be programmed via software or keypad. Keep the following considerations in mind:
H With + polarity: dialer is activated by the application of a positive signal (positive command).
With - polarity: dialer is activated by the lack of a negative signal (negative drop).
L With + polarity: dialer is activated by the lack of a positive signal (positive drop).
With - polarity: dialer is activated by the application of a negative signal (negative command).
CAUTION - When using positive command signals with a voltage higher than 20 V, it is necessary to
connect to a 10Kohm resistor (not provided): see Fig. 4.
! "F
#
&
'
()
)
²
)
²
)
, -
.
HOHSRQH
SOX
QWHUQDO
WHOHSRQH
OLQH
URXQG
FRQQHFWLRQ
A B @ ?
?
/ / / /
9 B-TEL2
PROGRAMMING BY PC
This chapter describes how to program the dialer with a PC. A PC can be used to set all the parameters necessary
for dialer operation, as well as modify the dialer's operations to suit the user's specific needs and installation.
This chapter also describes in detail all the parameters that can be programmed by the installer and the user.
A particular cable (GSM/LINK) is also needed to program the dialer by PC. The cable diagram is shown in Figure
2. This cable is connected between the PC's RS232 serial port and the connector [10], present on the dialer's G
board.
Once the PC is connected to the dialer, the software application can be launched and the programming performed,
as described in this chapter.
MAIN WINDOW
Once the application is launched, a window similar to the one shown in Figure 4 will appear. This paragraph
describes all of the window's components.
Menu Bar - This bar contains all the different menu items used not just to program client data, but also to
manage several important PC settings.
Bookmark Bar - The settings of multiple clients can be kept open at the same time (see menu File -> Open...).
One can use the bookmark bar to instantaneously recall the settings of an open client: simply click on the
corresponding "bookmark". Once the "bookmark" is selected, the right mouse key can be clicked to save data
or close the client profile. Be sure to save all client data or changes before closing.
Client Info Button - Click on the button to set client data (name, phone, address, etc.). The Account Code
is a meter that advances automatically. This parameter does not keep track of deleted clients: therefore one will
be assigned the first free number by clicking on the button.
Send/Load All Button - With a single click, these buttons can load all parameters programmed into the dialer
to the PC memory (Board Load, green arrow button, ) or send all client programming to the dialer’s memory
(Send to Board, red arrow button, ).
Choose Programming Page Window - Various programming pages can be selected from this window. When
a page is selected, a series of data to program will appear in the Parameters Area.
Page names may not always be visible. Click on the Client Bar to view page names.
Parameters Area - This part of the window shows all parameters that can be programmed. Parameters are
grouped according to the page selected and are sorted into sections to facilitate data input. See the
PROGRAMMING paragraph for a detailed description of these parameters.
OPTIONS MENU
This menu contains the parameters and options for correct program operation. Items in the Options Menu are the
following:
Serial Ports Sets the serial port (RS232) to connect to the dialer through the GSM/LINK wire, as well as the
number of connection attempts (preset at 3 attempts).
Language Allows one to select the application's default language from those available.
COMMUNICATION MENU
COMMUNICATION
Firmware Upgrade Quickly and easily upgrades the dialer's firmware. Once the new firmware is obtained from
the .HEX file, it can be loaded and sent to the dialer by pressing the button.
PROGRAMMING
The following paragraph describes in detail all the programming pages and their relative parameters.
Send and Load buttons: Except for the Messages Page, all programming pages show the two buttons (Load
data from board, green arrow) and (Send data to board, red arrow). On the Log page, only the Load button
is present. Even though they look the same as the buttons in the Select Programming Page window, the action
range of these two buttons is limited exclusively to the parameters of the single page currently displayed on the
screen.
Phonebook Page
Up to 8 telephone numbers, each 20 digits long, can be programmed on this page. To program one (or more)
telephone numbers, select the corresponding line from the list on the left and enter the data on the right.
To select more numbers, click on the table row while holding down the Control key on the PC keyboard. To
select a continuous series of numbers, select the first number and, holding down the Shift (or Maiusc) key
on the PC keyboard, the last number.
Description - Enter the description for the selected telephone number in this box.
Telephone number - Enter the telephone number in this box (enter only numbers).
Behaviour - Select the use for which the phone number is programmed. To disable the phone number
(leaving it in the memory for future use) select the None option.
Telemonitoring - This section is only available if Telemonitoring is set in the Behaviour section. Click the
Protocol box to select one from those available. Every Telemonitoring protocol requires a 4-digit User PIN (5
digits for CESA protocol).
Button - Click this button to select all telephone numbers on the list. Alternatively, clicking on the triangle
to the right, one can deselect the numbers.
Programmed telephone numbers will appear in the table with a different color, as explained in the Legenda
section
11 B-TEL2
Outputs Page
The parameters for the dialer’s two outputs are programmed on this page.
Events/Actions Page
Actions the dialer must carry out in response to specific events or actions are programmed on this page.
Telephone numbers - Select one or more telephone numbers that the dialer will call when one of the events
listed in the Description column occur. These telephone numbers are programmed on the Phonebook Page.
To select a number, click the appropriate box. The check sign ' will indicate that the telephone number has
been selected.
The Mains fault event occurs only if power is missing for at least 15 minutes.
C-ID - Telemonitoring Contact ID PINs (3 digits) are programmed in this column.
SIA - SIA Telemonitoring PINs (2 digits) are programmed in this column.
To set the Telemonitoring PINs, click the appropriate box twice and enter the PIN.
Mess. # - Up to 3 voice messages can be sent when an event or action listed in the Description column occurs.
To select a message, double-click the appropriate box and choose the message from those available.
Options Page
The options and parameters for correct dialer operation are programmed on this page.
Selection - Click on the appropriate boxes to disable DTMF tone control, select tone dialing, or select pulse
dialing.
Start playing after - manner in which a dialer sends a voice message is programmed in this section.
z If Selection, is chosen, the message will be sent after the remote telephone sends a response signal.
z Voice on-line, is chosen, the message will be sent after the remote operator responds.
z Delay, is chosen, the message will be sent after the timed delay, programmable from 0 to 99 seconds. Set
the delay time by clicking the arrow next to the number, or clicking on the box and manually inserting the number
of seconds.
Vocal messages - The parameters for voice messages are programmed in this section. These parameters
are:
The number of times each message is repeated (minimum 1, maximum 9),
The duration and number of messages as specified in the following:
2 messages = two messages, each 32 seconds long (factory default);
4 messages = four messages, each 16 seconds long;
1 + 4 messages = one 32 second long message and four 8 second long messages;
8 messages = eight messages, each 8 seconds long.
A brief description can be written for each voice message by clicking on the message box.
General options - The dialer's general options are programmed in this section, described as the following:
z Number of rings - The number of rings after which the dialer answers the phone (if able to do so). If the
installer has enabled the Bypass answering machine option, this option will be ignored.
z Call attempts - Number of times a call will be attempted in the event it is not properly completed.
z Tone on PSTN fail - The dialer normally shows the presence or absence of the phone line on its display.
REC Button - Press this button to start recording a new voice message.
STOP Button - Press this button to stop recording or listening to a voice message.
A real-time timer will show the elapsed time while recording or playing a message.
Log Page
On this page, pressing the button allows one to see the list of the last 255 events that occurred.
It is possible to export the displayed list into a file just pressing the button .
13 B-TEL2
PROGRAMMING BY KEYPAD
The dialer's keypad can be used to set all the parameters necessary for dialer operation, as well as modify the
dialer's operations to suit the user's specific needs and installation.
The appropriate software or the dialer's keypad, with the auxiliary display, can be used to program these
parameters. When programming by keypad, the parameter is selected by pressing a series of keys.
The value for that parameter is then entered. G
INTRODUCTION
Restore Factory Settings
To restore all factory settings, remove all power supplies, hold down the , , and togheter, and then
replace the power supplies.
<Installer PIN>
where <Installer PIN> is a number 4 to 6 digits long. The factory-set installer PIN is 0001.
The device will indicate that it has successfully entered programming mode with a letter P on the display.
If a PIN longer than 6 digits or an incorrect PIN is entered, the speaker will emit an error sound (boop).
If, at any point during programming, 5 minutes elapse without a key being pressed, the dialer will
automatically exit programming mode.
Programming values
Unless otherwise indicated, values are programmed in the following manner:
When the key is pressed, the letter b will appear on the display. At this point the value relative to the section
being programmed can be entered.
If the key is pressed again while the <Section Number> is being entered, dialer will exit the section and
return to the standby state
<Section Number>
where <Section Number> is a 3-digit number.
If, for example, one wishes to view the third telephone number programmed (section 103, see Table 3a), the
following procedure will be used:
to select the section;
to select the third telephone number;
to view the requested value, which will be shown on the display in sequence, figure by figure, at regular
intervals. After a value is viewed, or if the section does not contain any programmed data, the dialer returns
to the standby state.
Firmware revision
Find out which revision of B-TEL2 firmware the board is using by entering the programming phase and keying
in the following formula:
The display will show, in order, the firmware revision numbers ( r 1 0 0).
Exit programming mode
To exit programming mode at any moment, press the key once or twice.
If, for example, is pressed while a value is being programmed, or after is pressed, the dialer returns to
the standby state. However, if is pressed when the display shows the letter P, the dialer will exit programming
mode.
15 B-TEL2
PROGRAMMING
If an invalid key is pressed during programming operations, the speaker will emit the classic error sound (boop).
In all other cases, it will emit a normal sound (beep).
For a complete and detailed description of all parameters, consult the "PROGRAMMING BY PC" chapter.
<New Installer PIN>
where <New Installer PIN> is a number 4 to 6 digits long.
<Number of attempts>
where <Number of attempts> is a number between 1 and 9 (factory set at 1).
<Number of rings>
where <Number of rings> is a number between 1 and 9 (factory set at 3).
If the Bypass answer machine option is enabled, the dialer will ignore this parameter.
(to select tone dialing- factory setting)
(to select pulse dialing)
Call all voice messages numbers
Enable/disable the option to call all voice numbers by entering the following formula:
17 B-TEL2
Confirm call result
Enable/disable voice call confirmation by entering the following formula:
<Delay>
where <Delay> is a number between 0 and 240 seconds (factory set at 0, no delay).
(Start playing after 'Delay' = 0 secs.)
(Disable the playing after 'Voice on Line')
One way audio
Select the listen-in mode by entering the following formula:
,::"!G ;#@G
<"#
02*)&/H -0/*,02()%*)&/ &*0
G4
)
:
G5
?
*@
$+
#C
G
G(
G
)
")
$
$+
#6
=
)
"#
#
VWUGWK
)
<;HQ;R4
"
)
.0(&$
0::
#:G
<"#
02*)&/H -0/*,02()%*)&/ &*0
G4
)
:
G5
?
*@ #C
G
G(
G
"6$)
)2
S #6
=
)
"#
#
VWUG
)
<;HQ;R4
"
)
.0(&$
19 B-TEL2
Restore events and actions
When an alarm event is restored (for example, alarm channel, failure, etc.) the dialer can perform up to 8 calls,
send up to 3 voice messages, and/or send a code to the electronic surveillance company.
Tab. 3g, 3h and 3i, describe this type of programming.
H
2
H
"
)
.0(&$
?::
#:<
02*)&/H -0/*,02()%*)&/ &*0
G4
)
:
G5
?
*@ #C
G
G
"6$)
)2
G(
S'
=
J6
H
=
"#
VWUG
H
2
H
"
)
.0(&$
!"
#$#
#$%
?
@
C
#$
@
#$&
#$'
!"#?@ #
#$(
?
#$)
-
$
%$&'()
#$$
A
!*@+*#@*,!" ?A#
21 B-TEL2
Outputs
It is possible to program outputs to respond to one or more events. Moreover, each output can be programmed
as 'Monostable' or 'Bistable'. The following Tab. 3o and 3p describe, respectively, how to program Outputs 1
and 2.
<Message Number/Duration>
where <Message Number/Duration> is a number between 0 and 4:
= two messages, each 32 seconds long (factory setting);
= four messages, each 16 seconds long;
= one 32 second long message and four messages, each 8 seconds long;
= eight messages, each 8 seconds long.
Record Voice Messages
Follow this procedure to record voice messages:
1. Press the key;
2. Key in the number followed by the number of messages that will be recorded (from to );
3. Press the key.
At this time, any message previously recorded will be ERASED.
<Number of repetitions>
where <Number of repetitions> is a number between 1 and 9 (factory set at 1: a voice message will be sent only once).
23 B-TEL2
OPERATING YOUR SYSTEM
CAUTION - Operation of the B-TEL2 is guaranteed only if a qualified professional installs and programs
the device.
In the event of an alarm, all telephone devices connected after the dialer are isolated for the time
necessary to undertake the cycle of programmed calls. To restore the telephone line, interrupt the alarm G
cycle as described in the "Stop Alarm by Keypad" paragraph.
Y SIGN
DISPLAY
DISPLA ALS
SIGNALS
The dialer display is normally turned off in a non-operating state. However, the occurrence of any malfunctions
will immediately be revealed on the display by a letter, as described in the following (in order of priority, in the
event that several malfunctions are present simultaneously):
<User PIN>
where <User PIN> is a number 4 to 6 figures long (the User PIN is factory set at 0002).
When the User Menu is accessed, the letter U will be shown on the display.
If an incorrect PIN or a PIN longer than 6 figures is entered, the speaker will emit an error sound (boop).
If 5 minutes elapse without a key being pressed at any point in the programming process, the dialer will
automatically exit out of the User Menu.
To exit the User Menu in advance, press the key when the display shows the letter U.
Change User PIN
Change the User PIN (factory set at 0002) by entering the following formula:
<New PIN>
where <New PIN> is a number 4 to 6 digits long.
It is also possible to dedicate an alarm channel specifically to the Stop Alarm function. Ask the installer to
perform the wiring required for this option.
To ensure that the dialer has effectively performed the Stop Alarm, press the keypad keys. If the display remains
off, the function was successfully completed. If not, key in the Stop Alarm code again.
(enable responder)
2
$(+ +$3$+ "!# "$
%&'*$
%&'*
&19$
&19(
&%7:7
(
) $
) "
Activate/deactivate outputs
Activate or deactivate the dialer outputs by entering the following formula:
(to activate Output #2)
(to deactivate Output #2)
25 B-TEL2
SUPERKEY
SUPERKEYSS
The dialer has 3 superkeys available, of which one (Key ) is programmable.
For a description of superkey function, consult Tab. 5.
%
&45
G
"6# )$#(! )$
=
% 1
*!! +( !"+$,$+! 7
+!!3!!(89,
)
.(9 *900*(123
"O$ )
*(/"0*A 81
")
$
1*81*"#
(3
*!! !"+$,3!!7
6** "$*
813)$ 1*C 813
*"9($.(9
"O$ =
*900*(123
*(/"0*A 81
1*81*"#
(3
A>B7()/*?02''C%(0)/*?0 E086)''6)*2?=(&
')*0/)/*&
&/&,)(02*)&/'*'E/,-)20-0(
&
21
6
 A voice call is received from the dialer. In this case, the menu can be entered while the message is
being played back, before the dialer ends communication.
 The 'Responder' option, as described in the KEYPAD OPERATIONS paragraph, is enabled. In this
case, the user will call the dialer from a remote telephone and access the remote operations menu
when the dialer responds.
If the entered PIN is valid, a confirmation beep will sound and the DTMF menu will be accessed. The following
operations can be performed from remote access:
z Check the status of the inputs
z Activate/deactivate outputs
z Stop alarm and cancel telephone queue
z Voice functions
Once the DTMF menu is entered, after tone confirmation, the operations listed in Tab. 6 can be performed by
pressing two keys in order:
-.&
).*2&2
4#$" /$0 $ "$ 1*$(,$
)*"8*$;
)*"8*$; $"*
)*"8*$; $"*
)*"8*$;5
6"/;
"/;
$""(
6"/;
"/;
7*4
7 <(
!("8
27 B-TEL2
SensoIRIS S130
Optical-Smoke Fire Alarm Detector
EN54-7
Description
SensoIRIS S130 is an addressable optical-smoke detector designed for installing in
addressable fire alarm systems supporting TTE communication protocol.
The detector is powered on from the panel and can be controlled via the
communication protocol.
335mm
Packing Information
•Master box - 10 units SensoIRIS S130,
109mm
Contact Information
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
SensoIRIS M140
Combined Fire Alarm Detector
EN54-5,7
Description
SensoIRIS M140, is an addressable combined (temperature and optical-smoke)
detector, designed for installing in addressable fire alarm systems supporting TTE
communication protocol.
The detector is powered on from the panel and can be controlled via the
communication protocol.
Contact Information
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
SensoIRIS M140 IS
Combined Fire Alarm Detector
EN54-5,7
Description
SensoIRIS M140 IS, is an addressable combined (temperature and optical-smoke)
detector with built-in isolator module, designed for installing in addressable fire alarm
systems supporting TTE communication protocol.
The detector is powered on from the panel and can be controlled via the
communication protocol.
Contact Information
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
SensoMAG FRL-1
Fire Remote Indicator
Description
SensoMAG FRL-1 is a fire remote indicator with 1 input. The device repeats the status
of 1 or several automatic fire detectors (up to 3 SensoMAG detectors series). The
remote indicator operates with limited current detectors.
Connection Diagrams
FRL-1 FRL-1
Connecting of Connecting of 2 (up to 3)
1 fire detector automatic SensoMAG fire
to FRL-1. detectors to FRL-1.
+ + + + + +
In Out In Out In Out
RI RI RI
Packing Information
•Packing box - 1 unit SensoMAG FRL-1, dimensions 100 x 100 x 20 mm.
•Carton box - 75 units SensoMAG FRL-1, dimensions 400 x 300 x 250 mm.
Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
SensoIRIS WS
Addressable Wall Mount Sounder&Strobe
EN54-3
Description
SensoIRIS WS is аn addressable Wall Mount Sounder and Strobe designed for installing in
addressable fire alarm systems supporting TTE communication protocol.
The device is powered on from the panel and can be controlled via
the communication protocol. SensoIRIS WS is compatible with fire base B124.
Option - built-in isolator module (SensoIRIS Ws IS).
55 mm
Maximal consumption:
- tone type 19, low volume level, no strobe . . . . . . . . <3.5mА@92dB
- tone type 19, high volume level, no strobe . . . . . . . . <9.0mА@100dB
- tone type 19, high volume level, with enabled strobe. <9.5mA@100dB
- no sounder, with enabled strobe . . . . . . . . . . . . . . . <3.0mA
Power volume (selectable from control panel):
- low volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92dB
116 mm
- high volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100dB
Sounder type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piezo
Number of tone types (selectable from the control panel). . . . 32
Supported communication protocol . . . . . . . . . . . . . . . . . . . ТТЕ
Wire Gauge for terminals . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5mm2
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10°C to +50°C
Relative humidity resistance . . . . . . . . . . . . . . . . . . . . . . . . (93 ± 3)% @ 40°C
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP33
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183g
Dimensions (without base) . . . . . . . . . . . . . . . . . . . . . . . . . 116x55mm
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . red
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAN, transparent
Packing Information
•Packing box - 1 unit SensoIRIS WS, dimensions 117x120x57 mm.
•Carton box - 40 units SensoIRIS WS, dimensions 520/250/367 mm.
Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
SensoIRIS WS
Addressable Wall Mount Sounder&Strobe
EN54-3
1 970Hz
2 800Hz/970Hz @ 2Hz
4 970Hz 1s OFF/1s ON
10 550Hz/440Hz @ 0.5Hz
14 400Hz
17 750Hz
18 2400Hz
19 660Hz
Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
ISTISBL2CALL-R 1.0 220207 P7.0
CALL-R24
SIRENA AUTOALIMENTATA
PER USO ESTERNO
La sirena CALL-R24 in condizione di allarme emette Alarm status is signalled by the flasher (visual warn-
un suono continuo di elevata intensità sonora modu- ing) and horn (modulated frequency sound emis-
lato in frequenza. sion).
Gli estremi della modulazione (1100 e 2400 Hz) sono The horn emits a shrill tone (2400 Hz) and a low
stati scelti in modo da poter generare sia una nota tone (1100 Hz) — audible at a considerable dis-
acuta molto fastidiosa, sia una nota bassa che pos- tance.
sa essere udibile a notevole distanza. If the alarm signal is present after 10 minutes
! "#
$
$
!
#
!
#
!
+
#
#
)
)
,
*
-
!
+!
#
#
)
)
,
!!
*
.
+
!.#
$
!!
$/
/!
&0+4566&+
!
0
*3
2&
$*
/0
1*
23
&
+
# 0
&
!+
2
Profili di frequenza dei suoni generati - Frequency profiles of the audible signals.
SEGNALAZIONE SIGNALLING
La sirena CALL-R24, in condizione di allarme, attiva The audible and/or visual signals on the horn and
il lampeggiatore e/o emette un suono di elevata in- strobe/flasher depend on the Alarm signal con-
tensità modulato in frequenza dipendente dalle pro- figuration.
grammazioni fatte. Nel capitolo “PROGRAMMAZIO- The audible signals and modulated frequency
NI” sono riportati i suoni ed il range di frequenza en- range can be found in the “PROGRAMMING” sec-
tro cui i suoni vengono modulati. I range di frequenza tion.
possibili sono 1100/2400 Hz. The frequency range is : 1100/2400 Hz.
$! $!
5(2/
5(2/ 5(2/
$! $!
%&'()##'*'#+
open-collector, in caso di normale funzionamento è The CALL-R24 will accept a maximum of 6 Alarm
collegato a massa, nel caso di batteria inefficiente, signals (for voltage fails on [+N] only) in 4 minutes,
rottura della tromba esponenziale magnetodinamica afterwards, it will block the horn for 4 minutes.
o del filamento della lampada rimane appeso. Per Also this status will be signalled on terminal [G].
proteggersi da malfunzionamenti della centrale, la This process will protect the CALL-R24 against
sirena accetta al più 6 richieste di segnalazione do- persistent Alarms generated by the Control panel.
vute a mancanza di [+N] in 4 minuti. Successive ri-
chieste mandano la sirena in blocco delle suonate
per un tempo di 4 minuti. Anche questa condizione è
segnalata sul morsetto [G].
COLLEGAMENTI CONNECTIONS
Usare sempre cavo schermato con un capo dello Use shielded cable only, with one end connected
schermo collegato alla massa della centrale e l'altro to the Control panel Negative and the other left
lasciato libero. Per il collegamento della sirena alla free.
centrale antincendio, servirsi delle uscite NAC (o Figure 1A, 1B illustrate the connection of the CALL-
Uscite Campana) presenti sulla centrale. Il coman- R24 to the NAC outputs (or bell outputs) of the con-
do di allarme di quest’ultima deve essere applicato trol panel.The control panel alarm output must be
contemporaneamente ai morsetti [A] e [F] della si- connected to terminals [A] and [F] of the CALL-
rena (fig. 1A-1B). R24.
La resistenza di fine linea Reol (rappresentata trat- The Reol resistance (outlined) must be connected
teggiata) deve essere montata sulla morsettiera del- on siren terminals, only if the NAC outputs are
la sirena, solo se è necessario avere le uscite NAC supervisioned.
supervisionate. Figure 1B illustrates the connection for differenti-
Nella fig. 1B è riportato il collegamento per effettua- ated reset (Silence) of audible and visual signalling
re un azzeramento differenziato dell’allarme acu- appliances—the control panel must have a
stico rispetto a quello ottico: per questo tipo di al- silenceable output and a non-silenceable output for
laccio è necessario che la centrale disponga this type of connection.
di uscite tacitabili e non. The eol resistance REOL (outlined) must be con-
La resistenza di fine linea (REOL rappresentata trat- nected only if the outputs are supervisioned.
teggiata) deve essere montata solo se è necessa- Figures 1C, 1D, 1E and 1F illustrate connections
rio avere le uscite NAC supervisionate. using the free voltage relay terminals of the control
E’ anche possibile sfruttare i contatti liberi di un panel.
eventuale relè presente sulla centrale antincendio: In all cases, 27.6 V (min. 0.6 A) must be applied
per questo tipo di collegamento fare riferimento alle across terminals [+N] and [M M ] to charge the bat-
figure 1C, 1D, 1E e 1F. tery, and to maintain standby status.
In tutti i casi, comunque, fra i morsetti [+N] e [M M] In all cases it is possible to use the [G] terminal
della sirena, deve essere sempre applicata una ten- (Open Collector) as Trouble signal terminal.
sione di 27,6 V (min. 0,6 A) che serve, tra l’altro, a If the voltage fails on terminal [+N], in accordance
mantenere carica la batteria interna. with +N wire jumper (connected or disconnected),
In tutti i casi è possibile utilizzare il morsetto [G] the [G] terminal (Open Collector) will be opened or
(uscita Open collector) per la segnalazione dei gua- will be closed to ground (see wire jumper table).
sti. In all cases the siren will sound when the [+N]
Se viene a mancare la tensione sul morsetto [+N], jumper will be disconnected, when the 24V fails.
in funzione del ponticello a filo +N, presente o as- Pay attention to relative Table to program the jump-
sente, l’Open collector [G] (Guasto) si apre o rima- ers.
5
ne chiuso (vedi descrizione ponticelli a filo). PROGRAMMING
In tutti i casi è possibile rimuovere il ponticello [+N]
per far suonare comunque la sirena in mancanza The board Jumpers (Wire and Link) are already
della 24V. connected at default (see fig. 2).
Fare riferimento alla note della relativa tabella, per If you are installing several CALL -R24 hornstrobes
le configurazioni dei ponticelli relative ad ogni colle- in the same area, the T1 and T2 Link Jumper will
gamento. allow you to select a different sound for each one,
thus permitting Users to distinguish between them.
PROGRAMMAZIONI The Link Jumpers T1 and T2 will allow you to select
the sounds, respectively:
Nella scheda della sirena, vedi fig.2, vi sono due tipi di 1) Up and down-scale modulation:
ponticelli: ponticelli estraibili e ponticelli a filo (la scheda T1=0 (K ) and T2=0 (K )
viene fornita con tutti i ponticelli inseriti). I ponticelli 2) Up-scale modulation, T1=1 (“ ) and T2=0 (K )
estraibili T1 e T2 determinano la diversità dei suoni. 3) Multitone, T1=0 (K ) and T2=1 (“ )
Il loro utilizzo è utile quando, ad esempio, vengono 4) Single Tone, T1=1 (“ ) and T2=1 (“ )
installate due sirene vicine; in base al suono emes- The wire jumpers allow you to set:
so, è possibile identificare velocemente quale delle - P: the input polarity on [A] and [F];
due è in allarme. - SD: the expired time for sound and Flasher ;
I suoni sono rispettivamente quelli programmati me- - +N: the presence/absence of 24V to manage
diante i ponticelli estraibili T1 e T2: trouble signal on terminal [G] (Open Collector) ;
1.Modulazione salita e discesa: T1=0 (K) e T2=0 (K) - PUL: the presence/absence of PULL-UP on [A]
2.Modulazione solo salita: T1=1(“ ) e T2=0 (K ) and [F] inputs .
3.Multitono, T1=0 (K ) e T2=1 (“ ) For the various programming options provided by
4.Tono singolo, T1=1 (“ ) e T2=1 (“ ) the Wire and Link Jumpers refer to relative Tables.
I ponticelli a filo sono di facile accesso e permettono
di scegliere;
P: la polarità desiderata sugli ingressi [A] e [F];
SD: la presenza del tempo limite di suono e
lampeggio;
+N: la presenza/assenza di 24V per la gestione dei
guasti sull’uscita Open Collector [G];
PUL: la presenza/assenza della PULL-UP sugli in-
gressi [A] e [F].
La programmazione dei ponticelli a filo e dei ponticelli
estraibili è mostrata nelle relative tabelle.
%
%
/$0
'
'
INSTALLAZIONE INSTALLATION
La sirena Call -R24 va fissata ad una parete che non The CALL-R24 must be mounted on a flat sur-
presenti avvallamenti e/o sporgenze eccessive. face.
Per facilitare l’operazione di installazione, nella con- Drill the holes for wall mounting (use the drilling
fezione troverete una dima per la foratura e viti per il pattern).
fissaggio. Sulla dima sono disegnati 5 fori : F1, F2, F1, F2, F3, F4, F5 on the drilling pattern corre-
F3, F4, F5, corrispondenti a quelli di fissaggio posti spond to the wall mounting holes 5 on the
sul fondo della sirena. Quest’ultima andrà fissata ai backplate.
punti 5 (fig. 3). Pull the control panel cables through the cable
Per il passaggio dei cavi provenienti dalla centrale passage PC (13) (see fig. 3).
utilizzate esclusivamente il foro 13. Fissata la sirena Make the connections on the terminal board 9.
potrete effettuare i collegamenti sulla morsettiera 9 e Install the battery on the support 6 and connect
Fig. 3 - Parti della sirena - siren pats
7
subito dopo collegare la batteria, posizionata sull’ap- as per fig. 3.
posita mensola 6 (fig. 3): la tromba emetterà un pic- At this point the magnetodynamic horn will gener-
colo suono ed il lampeggiatore entrerà in funzione. ate a little sound and the flasher will start. Fit the
Fissate allora il sottocoperchio ed il coperchio della sire- metal innerplate and box.
na ed attendete che il lampeggiatore smetta di funziona- Wait for the flasher to stop (approx. 20 secs) before
re (20 secondi circa). A questo punto la sirena è funzio- testing.
nante e pronta per un eventuale collaudo. WARNING: If you are fitting or removing the metal
N.B. Se in fase di installazione/manutenzione, per innerplate while the flasher is active, DO NOT allow
qualsiasi motivo si volesse montare/rimuovere il it to come into contact with the flasher terminals,
sottocoperchio metallico mentre il lampeggiatore è as this may cause a short-circuit.
attivo, fare molta attenzione a non toccare i terminali
del lampeggiatore con il sottocoperchio stesso,
poichè potrebbe verificarsi un corto.
Se il lampeggiatore non funziona collegata la Flasher does not function when the battery is
batteria, può darsi che quest’ ultima sia scarica. connected.
Chiudete allora i coperchi, attendete 20 secondi cir- The battery may be low:
ca e mandate in allarme l’impianto. -check the battery status
Se la sirena suona (anche piano) ma il lampeggiato- -close the box properly
re non funziona, la batteria è scarica: si ricaricherà -wait approximately 20 seconds and then simulate
in qualche ora attraverso il morsetto [+N]. alarm status. If the horn output is low and the flasher
Se collegata la batteria, chiusi i coperchi e trascorsi is inactive—the battery is obviously low. Charge the
20 secondi circa il lampeggiatore non cessa di battery for several hours (use terminal [+N]).
funzionare, controllate che sui morsetti di allarme Flasher continues flashing after 20 seconds (bat-
siano presenti i giusti potenziali (27.6 V su [+N]). tery connected—box closed):
Questa sirena NON può essere usata come -check the electrical status on alarm terminals (i.
dispositivo di segnalazione in sistemi di e. 27.6 V on [+N]).
rilevazione incendio This siren is NOT intended to be used as sig-
nalling device with fire detection systems.
Le informazioni contenute nel presente documento sono BENTEL SECURITY S.r.l. reserves the right to change the
soggette a modifiche senza preavviso e non rappresentano technical specifications of this product without prior notice.
un impegno da parte della BENTEL SECURITY S.r.l.
Description
SensoIRIS MCP 150, is a manual call point with built-in isolator module, designed for
installing in addressable fire alarm systems supporting TTE communication protocol.
The detector is powered on from the panel and can be controlled via the
communication protocol.
90mm
Consumption with communication . . . . . . . . . . . . . . . . . . 160μA@27VDC
Consumption in Fire mode . . . . . . . . . . . . . . . . . . . . . . . 3mA
Type of the working element . . . . . . . . . . . . . . . . . . . . . . resettable (flexible)
Type, according EN54-11 . . . . . . . . . . . . . . . . . . . . . . . . A
Wire Gauge for terminals. . . . . . . . . . . . . . . . . . . . . . . . . 0.4mm2 - 2.0mm2
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . -10°C to +60°C
Relative humidity resistance . . . . . . . . . . . . . . . . . . . . . . (93 ± 3)% @ 40°C
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP40
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ~175g
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90x90x57mm
Material (plastic), color . . . . . . . . . . . . . . . . . . . . . . . . . . ABS, red
1293-CPD-0257
Packing Information
•Packing box - 1 unit SensoIRIS MCP150, dimensions 96x96x65 mm.
Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
SensoIRIS MCP150
Manual Call Point
EN54-11
Connection Diagrams
L- L+ Izo L- L+ L- L+ Izo L- L+
Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com
VRLA Battery SPA 12-18
Nominal Voltage 12 V
Specifications
Rated Capacity 20hr Rate (1,80V/cell) 10hr Rate (1,80V/cell) 5hr Rate (1,70V/cell) 1hr Rate (1,60V/cell)
0
(25 C) 18 Ah 15,8 Ah 13,6 Ah 11,6 Ah
Dimensions (mm) Length Width Height Overall Height Weight
& Weight (kg) 181mm 77mm 167mm 167mm 5,70kg
Number / Type of Terminals 2 / F2
Technical Characteristics
Design Life at 200C 5 years
Eurobat Classification Standard Commercial
Internal Resistance (Fully charged - 250C) 16 mΩ
Short-circuit current 850 A
Max Charging Current 6,8 A
Min safe end Discharge Voltage 1,60 V/cell
Self discharge per month at 200C 3%
Recommended Charging Voltage at 200C Stand-by use (V/cell): 2,25 to 2,30
Cycle use (V/cell): 2,40 to 2,50
Container Material ABS-UL94 HB
Electrolyte Type Sulfuric Acid
Type of plates / Alloy Flat plates / Lead-Calcium-Tin alloy
Type of Separator Absorbant Glass Mat
Valve Type / Operational Pressure Rubber / 1-3 psi (70-200 mbar)
Operating Temperature Range -20 to +500C
Storage time at 200C 9 months
Description
The Repeater fire alarm panel is designed to work with Teletek Electronics
addressable fire alarm panels IRIS, IRIS PRO and SIMPO. It is used to display the
events of the connected to network addressable panels.
The connection between Repeater panel and other addressable panels IRIS and/or
SIMPO is via redundant network module based on RS485 interface. Maximum
number of fire alarm panels in network is 32. Maximum distance between two
panels is up to 1000m.
The information for events are visualized on LCD display and LED indication for the
system status. The Repeater panel has a built-in real time clock. Available micro
USB for latest software and firmware updates.
Packing Information
•Single packing box - 1 unit Repeater panel, dimensions 205x335x53mm
•Carton packing box - 6 units Repeater panel, dimensions 360x345x252mm
Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria www.teletek-electronics.com