Documente Academic
Documente Profesional
Documente Cultură
Perioada normala - 1
Element Suprafata
θimed θi θe τ Af Af*θi
Nr. Crt. anvelopa Tip Nr. Buc. Suprafata totala R' τ Lj= (Stot/R')*τ
2 2 2
- - - - (m ) (m ) (m K/W) - (W/K) (K) (K) (K) -
0 1 2 3 4 5=3*4 6 7 8=(5/6)*7 1 2 3 4=(1-3)/(2-3)
P1 1 8,807 8,807 1,242 0,947 6,716 18 20 -18 0,947 0 0,00
P2 1 7,245 7,245 0,936 0,947 7,335 18 20 -18 0,947 2,025 36,45
P3 1 6,47 6,470 0,837 1,000 7,726 20 20 -18 1,000 2,8 56,00
P4 1 6,47 6,470 0,852 1,000 7,593 20 20 -18 1,000 2,8 56,00
P5 1 8,43 8,430 1,008 1,000 8,359 20 20 -18 1,000 0,84 16,80
P6 1 8,43 8,430 1,008 1,000 8,359 20 20 -18 1,000 0,84 16,80
P7 1 6,47 6,470 0,852 1,000 7,593 20 20 -18 1,000 2,8 56,00
P8 1 6,47 6,470 0,837 1,000 7,726 20 20 -18 1,000 2,8 56,00
P9 1 6,0065 6,007 0,813 1,000 7,391 20 20 -18 1,000 2,8 56,00
P10 1 8,8065 8,807 1,098 1,000 8,022 20 20 -18 1,000 0 0,00
P11 1 9,27 9,270 1,127 1,000 8,224 20 20 -18 1,000 0 0,00
P12 1 9,27 9,270 1,127 1,000 8,224 20 20 -18 1,000 0 0,00
P13 1 8,8065 8,807 1,098 1,000 8,022 20 20 -18 1,000 0 0,00
P14 1 6,0065 6,007 0,813 1,000 7,391 20 20 -18 1,000 2,8 56,00
P15 1 6,47 6,470 0,837 1,000 7,726 20 20 -18 1,000 2,8 56,00
P16 1 6,0065 6,007 0,813 1,000 7,391 20 20 -18 1,000 2,8 56,00
P17 1 2,9355 2,936 1,242 1,000 2,363 20 20 -18 1,000 0 0,00
P18 1 9,7335 9,734 1,267 0,947 7,278 18 20 -18 0,947 0 0,00
P19 1 5,6835 5,684 0,917 0,947 5,871 18 20 -18 0,947 4,05 72,90
P20 1 2,9355 2,936 1,242 1,053 2,487 22 20 -18 1,053 0 0,00
P21 1 6,5665 6,567 0,833 1,009 7,949 20,33 20 -18 1,009 2,24 45,54
P22 1 5,705 5,705 0,797 0,868 6,217 15 20 -18 0,868 3,57 53,55
P23 1 5,705 5,705 0,788 0,947 6,858 18 20 -18 0,947 3,57 64,26
P24 1 6,0065 6,007 0,813 0,868 6,418 15 20 -18 0,868 2,8 42,00
P25 1 6,8065 6,807 0,841 0,868 7,028 15 20 -18 0,868 2,00 30,00
P26 1 8,27 8,270 1,010 0,868 7,111 15 20 -18 0,868 1,00 15,00
P27 1 8,27 8,270 1,010 0,945 7,740 17,92 20 -18 0,945 1,00 17,92
P28 1 5,7815 5,782 0,778 0,757 5,625 10,75 20 -18 0,757 3,025 32,52
PERETI
153
CLADIREA REALA - CENTRALIZAREA DATELOR
Perioada de noapte -2
Element Suprafata
θimed θi θe τ Af Af*θi
Nr. Crt. anvelopa Tip Nr. Buc. Suprafata totala R' τ Lj= (Stot/R')*τ
2 2 2
- - - - (m ) (m ) (m K/W) - (W/K) (K) (K) (K) -
0 1 2 3 4 5=3*4 6 7 8=(5/6)*7 1 2 3 4=(1-3)/(2-3)
P1 1 8,807 8,807 1,242 0,939 6,659 13 15 -18 0,939 0 0,00
P2 1 7,245 7,245 0,936 0,939 7,273 13 15 -18 0,939 2,025 26,33
P3 1 6,47 6,470 0,837 1,000 7,726 15 15 -18 1,000 2,8 42,00
P4 1 6,47 6,470 0,852 1,000 7,593 15 15 -18 1,000 2,8 42,00
P5 1 8,43 8,430 1,008 1,000 8,359 15 15 -18 1,000 0,84 12,60
P6 1 8,43 8,430 1,008 1,000 8,359 15 15 -18 1,000 0,84 12,60
P7 1 6,47 6,470 0,852 1,000 7,593 15 15 -18 1,000 2,8 42,00
P8 1 6,47 6,470 0,837 1,000 7,726 15 15 -18 1,000 2,8 42,00
P9 1 6,0065 6,007 0,813 1,000 7,391 15 15 -18 1,000 2,8 42,00
P10 1 8,8065 8,807 1,098 1,000 8,022 15 15 -18 1,000 0 0,00
P11 1 9,27 9,270 1,127 1,000 8,224 15 15 -18 1,000 0 0,00
P12 1 9,27 9,270 1,127 1,000 8,224 15 15 -18 1,000 0 0,00
P13 1 8,8065 8,807 1,098 1,000 8,022 15 15 -18 1,000 0 0,00
P14 1 6,0065 6,007 0,813 1,000 7,391 15 15 -18 1,000 2,8 42,00
P15 1 6,47 6,470 0,837 1,000 7,726 15 15 -18 1,000 2,8 42,00
P16 1 6,0065 6,007 0,813 1,000 7,391 15 15 -18 1,000 2,8 42,00
P17 1 2,9355 2,936 1,242 1,000 2,363 15 15 -18 1,000 0 0,00
P18 1 9,7335 9,734 1,267 0,939 7,217 13 15 -18 0,939 0 0,00
P19 1 5,6835 5,684 0,917 0,939 5,821 13 15 -18 0,939 4,05 52,65
P20 1 2,9355 2,936 1,242 1,061 2,506 17 15 -18 1,061 0 0,00
P21 1 6,5665 6,567 0,833 1,010 7,959 15,33 15 -18 1,010 2,24 34,34
P22 1 5,705 5,705 0,797 0,848 6,074 10 15 -18 0,848 3,57 35,70
P23 1 5,705 5,705 0,788 0,939 6,800 13 15 -18 0,939 3,57 46,41
P24 1 6,0065 6,007 0,813 0,848 6,271 10 15 -18 0,848 2,8 28,00
P25 1 6,8065 6,807 0,841 0,848 6,867 10 15 -18 0,848 2,00 20,00
P26 1 8,27 8,270 1,010 0,848 6,948 10 15 -18 0,848 1,00 10,00
P27 1 8,27 8,270 1,010 0,937 7,672 12,92 15 -18 0,937 1,00 12,92
P28 1 5,7815 5,782 0,778 0,720 5,351 5,75 15 -18 0,720 3,025 17,39
PERETI
154
CLADIREA REALA - CENTRALIZAREA DATELOR
Perioada de vacanta -3
Element Suprafata
θimed θi θe τ Af Af*θi
Nr. Crt. anvelopa Tip Nr. Buc. Suprafata totala R' τ Lj= (Stot/R')*τ
2 2 2
- - - - (m ) (m ) (m K/W) - (W/K) (K) (K) (K) -
0 1 2 3 4 5=3*4 6 7 8=(5/6)*7 1 2 3 4=(1-3)/(2-3)
P1 1 8,807 8,807 1,242 1,000 7,089 12 12 -18 1,000 0 0,00
P2 1 7,245 7,245 0,936 1,000 7,742 12 12 -18 1,000 2,025 24,30
P3 1 6,47 6,470 0,837 1,000 7,726 12 12 -18 1,000 2,8 33,60
P4 1 6,47 6,470 0,852 1,000 7,593 12 12 -18 1,000 2,8 33,60
P5 1 8,43 8,430 1,008 1,000 8,359 12 12 -18 1,000 0,84 10,08
P6 1 8,43 8,430 1,008 1,000 8,359 12 12 -18 1,000 0,84 10,08
P7 1 6,47 6,470 0,852 1,000 7,593 12 12 -18 1,000 2,8 33,60
P8 1 6,47 6,470 0,837 1,000 7,726 12 12 -18 1,000 2,8 33,60
P9 1 6,0065 6,007 0,813 1,000 7,391 12 12 -18 1,000 2,8 33,60
P10 1 8,8065 8,807 1,098 1,000 8,022 12 12 -18 1,000 0 0,00
P11 1 9,27 9,270 1,127 1,000 8,224 12 12 -18 1,000 0 0,00
P12 1 9,27 9,270 1,127 1,000 8,224 12 12 -18 1,000 0 0,00
P13 1 8,8065 8,807 1,098 1,000 8,022 12 12 -18 1,000 0 0,00
P14 1 6,0065 6,007 0,813 1,000 7,391 12 12 -18 1,000 2,8 33,60
P15 1 6,47 6,470 0,837 1,000 7,726 12 12 -18 1,000 2,8 33,60
P16 1 6,0065 6,007 0,813 1,000 7,391 12 12 -18 1,000 2,8 33,60
P17 1 2,9355 2,936 1,242 1,000 2,363 12 12 -18 1,000 0 0,00
P18 1 9,7335 9,734 1,267 1,000 7,683 12 12 -18 1,000 0 0,00
P19 1 5,6835 5,684 0,917 1,000 6,197 12 12 -18 1,000 4,05 48,60
P20 1 2,9355 2,936 1,242 1,000 2,363 12 12 -18 1,000 0 0,00
P21 1 6,5665 6,567 0,833 1,000 7,881 12 12 -18 1,000 2,24 26,88
P22 1 5,705 5,705 0,797 1,000 7,159 12 12 -18 1,000 3,57 42,84
P23 1 5,705 5,705 0,788 1,000 7,239 12 12 -18 1,000 3,57 42,84
P24 1 6,0065 6,007 0,813 1,000 7,391 12 12 -18 1,000 2,8 33,60
P25 1 6,8065 6,807 0,841 1,000 8,093 12 12 -18 1,000 2,00 24,00
P26 1 8,27 8,270 1,010 1,000 8,188 12 12 -18 1,000 1,00 12,00
P27 1 8,27 8,270 1,010 1,000 8,188 12 12 -18 1,000 1,00 12,00
P28 1 5,7815 5,782 0,778 1,000 7,435 12 12 -18 1,000 3,025 36,30
PERETI
155
VI. Parametrii climatici :
1. Temperatura conventionala exterioara de calcul
Temperatura conventionala exterioara de calcul pentru iarna se considera
conform STAS 1907/1-97. Pentru localitatea Nazna, comuna Sancraiu de Mures
2. Intensitatea radiatiei solare si temperaturile exterioare medii lunare
Intensitatea radiatiei solare si temperaturile exterioare medii lunare se
stabilesc conform cu Mc001-1, anexa A.9.6, respectiv SR 4839.
156
Parametrii climatici
157
VII. Calculul coeficientilor de pierderi de caldura HT si HV :
1. Calculul coeficientului de pierderi de caldura al cladirii H
H= HT+ HV (W/K)
2. Calculul coeficientului de pierderi de caldura al cladirii, prin ventilare
HV
HV= ρa*ca*na*V
ρa*ca- capacitatea termica volumica (Mc001-1, pag 49)
ρa*ca=1200 (J/m3K) = 0.34 (Wh/m3K)
na- numarul mediu de schimburi de aer (conf. Mc001-1 pag 49)
V- volumul incalzit direct sau indirect, al cladirii (m3)
Pentru cladirile de locuit sau asimilate acestora, numarul de schimburi de
aer pe ora poate fi evaluat infunctie de:
- Categoria cladirii
- Clasa de adapostire a cladirii
- Clasa de permeabilitate la aer a caldirii
3. Calculul coeficientului de pierderi de caldura al cladirii, prin transmisie
HT
Conform Mc001-1 (pag 34)
HT=L+LS+Hu (W/K)
L- coeficient de cuplaj termic prin anvelopa cladirii (W/K)
LS- coeficientul de cuplaj termic prin sol, se admite a fi calculat in regim
stationar, conf. SR EN ISO 13789 (W/K)
Hu- coeficient de pierderi termice prin spatii neincalzite, conf. SR EN ISO
13789 (W/K)
L= ΣUjAj+Σψklk+Σχj (W/K)
Uj- transmitanta termica a partii j de anvelopa a cladirii (W/m2K)
Aj- aria pentru care se calculeaza Uj (m2)
ψk- transmitanata termnica liniara a puntii termice liniare „k” (W/mK)
lk- lungimea pe care se aplica ψk (m)
χj- transmitanta termica punctuala a puntii termice punctuale „j” (W/K)
L= Σ(Σ(A/R’*τ)
158
CLADIREA REALA
CALCULUL COEFICIENTILOR DE PIERDERI DE CALDURA H T si HV - perioada normala - 1
a) Calculul coeficientului de pierderi de caldura H
H=HT + HV
1
HT=L= 1613,59818 (W/K)
159
CLADIREA REALA
CALCULUL COEFICIENTILOR DE PIERDERI DE CALDURA H T si HV - perioada de noapte - 2
a) Calculul coeficientului de pierderi de caldura H
H=HT + HV
1
HT=L= 1539,31551 (W/K)
160
CLADIREA REALA
CALCULUL COEFICIENTILOR DE PIERDERI DE CALDURA H T si HV - perioada de vacanta - 3
a) Calculul coeficientului de pierderi de caldura H
H=HT + HV
1
HT=L= 1557,224 (W/K)
161
VIII. Stabilirea perioadei de incalzire preliminara :
In prima faza a calculului consumurilor de energie se stabileste perioada de
incalzire preliminara, conf. SR 4839. In acest caz temperatura conventionala de
echilibru este θe= 12°C.
Temperatura exterioara medie pe sezonul de incalzire se calculeaza ca o
medie ponderata a temperaturilor medii lunare cu numarul de zile ale fiecarei luni.
Se determina grafic astfel:
- In abscisa se reprezinta la scara lunile anului cu durata in zile;
- In ordonata se marcheaza temperaturile medii lunare, la mijlocul
fiecarei luni, rezultand curba de variatie a temperaturilor medii
lunare;
- In ordonata, de la temperatura de 12°C se duce o paralela cu axa
lunilor. Punctele de intersectie ale dreptei D12 cu curba
temperaturilor medii lunare reprezinta inceputul si sfarsitul perioadei
de incalzire.
∑( ∗ )
θim= ∑
162
Qg= Qi+Qs (kWh/an)
Qi- degajari de caldura interna, datorate locatarilor si aparaturii
electrocasnice
Qs- aporturile solare prin elemente vitrate
Qi= [Φih+(1-b)*Φiu]*t
Φih- flux termic mediu al degajarilor interne in spatiile incalzite
Φih= Φi*Ainc
Ainc- aria totala a spatiului incalzit
Φiu=0 – fluxul termic mediu al degajarilor interne in spatiile neincalzite
Qs=Σ(Isj*ΣAsnj)*t
Isj- radiatia solara totala medie pe perioada de calcul pe o suprafata de 1 m2
avand orientarea „j”
Asnj- aria receptoare echivalenta a suprafetei „n” avand orientarea „j”
Asnj= Af*Fs*FF*g (m2)
Af- aria totala a elementului vitrat „n”
Fs- factor de umbrire a suprafetei „n”
FF- factorul de reducere pentru ramele vitrajelor
g- transmitanta totala la energie solara a suprafetei „n”
Fluxul aporturilor totale de caldura
η1=
163
a=a0+
a0= 0.8 – parametru numeric, conf. Mc 001-2, pag 24, tab 1.2
τ0=30h – conf. Mc001-2, pag 24, tab 1.2
τ=
τ- constanta de timp care caracterizeaza inertia termica interioara a spatiului
incalzit (h)
C- capacitatea termica interioara a cladirii
H- coeficientul de pierderi de caldura
C=Σ(Xj*Aj)= ∑ ∑ ∗ ∗ ∗
Xj- capacitatea termica interna a elementului interior „j” (kJ/m2K)
Aj- aria elementului „j” (m2)
ρij- densitatea materialului din stratul „i” al elementului „j” (kg/m3)
cij- caldura specifica a materialului din stratul „i” al elementului „j”
(kJ/kgK)
dij- grosimea stratului „i” al elementului „j” (m)
4. Determinarea temperaturii de echilibru si perioada de incalzire reala a
cladirii
∗
θe= θi-
θe- temperatura de echilibru
θi- temperatura interioara de calcul
η- factorul de utilizare al aporturilor
Φa- aporturile solare si interne medii pe perioada de incalzire
H- coeficientul de pierderi de caldura al cladirii
In functie de temperatura de echilibru reala se restabileste perioada de
incalzire a cladirii utilizand graficul temperaturilor exterioare medii lunare.
IX. Programul de functionare si regimul de furnizare a agentului
termic :
Consideram porgram de functionare discontinuu, impartit in 3 perioade:
perioade normala (de zi) 10 ore/zi, perioada de noapte 14 ore zi si perioada de
vacante si weekenduri 24 ore/zi.
X. Calculul pierderilor de caldura ale cladirii reale :
QL,real= ∑ ∗ ∗( , − )*tj (kWh/an)
164
tj- numarul de ore in perioada de incalzire aferent temperaturii de echilibru
reale pentru perioada j
XI. Calculul aporturilor de caldura ale cladirii reale :
Qg,real= Qi+Qs (kWh/an)
Qi- degajari de caldura interna, datorate locatarilor si aparaturii
electrocasnice
Qs- aporturile solare prin elemente vitrate
Qi,real= [Φih+(1-b)*Φiu]*t
Φih- flux termic mediu al degajarilor interne in spatiile incalzite
Φih= Φi*Ainc
Ainc- aria totala a spatiului incalzit
Φiu=0 – fluxul termic mediu al degajarilor interne in spatiile neincalzite
Qs=Σ(Isj*ΣAsnj)*t
Isj- radiatia solara totala medie pe perioada de calcul pe o suprafata de 1 m2
avand orientarea „j”
Asnj- aria receptoare echivalenta a suprafetei „n” avand orientarea „j”
Asnj= Af*Fs*FF*g (m2)
Af- aria totala a elementului vitrat „n”
Fs- factor de umbrire a suprafetei „n”
FF- factorul de reducere pentru ramele vitrajelor
g- transmitanta totala la energie solara a suprafetei „n”
Fluxul aporturilor totale de caldura
165
CLADIREA REALA
Calculul perioadei de incalzire preliminara
Se face calculul preliminar conform SR4839 pentru temperatura exterioara medie Ɵe0=12°C
PERIOADA IULIE AUG SEPT OCT NOI DEC IAN FEB MAR APR MAI IUN
TEMP.EXT. 19,3 18,7 14,8 9 3,8 -1,2 -4,4 -1,4 4,2 10 15 17,9
Tg Mures 12 12 12 12 12 12 12 12 12 12 12 12
25
20
15
10
0
IULIE AUG SEPT OCT NOI DEC IAN FEB MAR APR MAI IUN
°C z=nr. zilelor in perioada considerata
-5 191 zile
Ɵem=ƩƟe(x=1-n)/z
NUMAR Qe0 Qext Dz
LUNA ZILE [˚C] [˚C] ZILE Qem
August 31 12,00 18,7 0
Septembrie 30 12,00 14,8 0
Octombrie 31 12,00 9 20
Noiembrie 30 12,00 3,8 30
Decembrie 31 12,00 -1,2 31
Ianuarie 31 12,00 -4,4 31
2,15
Februarie 28 12,00 -1,4 28
Martie 31 12,00 4,2 31
Aprilie 30 12,00 10 20
Mai 31 12,00 15 0
Iunie 30 12,00 17,9 0
Iulie 31 12,00 19,3 0
Σ 191
166
CLADIREA REALA
Temperatura interioara de calcul - perioada normala (zi)
Ɵi=ƩƟijxAj/ƩAj conf. C107/5 ,pct. 5.3 -pag11
Aj=aria incaperii j
Ɵij=temperatura incaperii j
Bucatarie 18,570 15
Vesela 4,720 18
Spalator vase 4,450 18
Camera tampon 9,690 18
Vestiar personal 7,110 22
Preparare carne 5,530 18
Spalare si dezinfectare oua 2,900 18
Preparare zarzavaturi 2,900 18
Depozit de alimente 5,200 5
Coridor 4,770 18
Hol 1,950 18
Parter
C.T. 9,620 15
G.S. izolator 1,350 20
Izolator 8,380 22
Hol+casa scarii 14,420 18
Sala de grupa 50,020 20
Sala de grupa 50,020 20
Grupa sanitar fete 12,600 20
Grup sanitar educatoare 1,270 20
Grup sanitar baieti 9,920 20
Hol+vestiar 27,140 20
Sala de mese 33,060 20
Sala multifunctionala 67,210 18
Birou 9,370 20
Spalatorie 9,200 15
Casa scarii 14,330 18
Sala de grupa 50,060 20
Sala de grupa 50,060 20
Etaj
Grupa sanitar fete 12,510 20
Grup sanitar educatoare 1,350 20
Grup sanitar baieti 9,820 20
Hol 34,080 20
Depozit jucarii si materiale ed. 32,900 16
167
CLADIREA REALA
Temperatura interioara de calcul pentru perioada de noapte
Ɵi2=ƩƟijxAj/ƩAj conf. C107/5 ,pct. 5.3 -pag11
Aj=aria incaperii j
Ɵij=temperatura incaperii j
Bucatarie 18,570 10
Vesela 4,720 13
Spalator vase 4,450 13
Camera tampon 9,690 13
Vestiar personal 7,110 17
Preparare carne 5,530 13
Spalare si dezinfectare oua 2,900 13
Preparare zarzavaturi 2,900 13
Depozit de alimente 5,200 5
Coridor 4,770 13
Hol 1,950 13
Parter
C.T. 9,620 10
G.S. izolator 1,350 15
Izolator 8,380 17
Hol+casa scarii 14,420 13
Sala de grupa 50,020 15
Sala de grupa 50,020 15
Grupa sanitar fete 12,600 15
Grup sanitar educatoare 1,270 15
Grup sanitar baieti 9,920 15
Hol+vestiar 27,140 15
Sala de mese 33,060 15
Sala multifunctionala 67,210 13
Birou 9,370 15
Spalatorie 9,200 10
Casa scarii 14,330 13
Sala de grupa 50,060 15
Sala de grupa 50,060 15
Etaj
Grupa sanitar fete 12,510 15
Grup sanitar educatoare 1,350 15
Grup sanitar baieti 9,820 15
Hol 34,080 15
Depozit jucarii si materiale ed. 32,900 11
168
CLADIREA REALA
Temperatura interioara de calcul pentru perioada de vacanta si weekend
Ɵi3=ƩƟijxAj/ƩAj conf. C107/5 ,pct. 5.3 -pag11
Aj=aria incaperii j
Ɵij=temperatura incaperii j
Bucatarie 18,570 12
Vesela 4,720 12
Spalator vase 4,450 12
Camera tampon 9,690 12
Vestiar personal 7,110 12
Preparare carne 5,530 12
Spalare si dezinfectare oua 2,900 12
Preparare zarzavaturi 2,900 12
Depozit de alimente 5,200 5
Coridor 4,770 12
Hol 1,950 12
Parter
C.T. 9,620 12
G.S. izolator 1,350 12
Izolator 8,380 12
Hol+casa scarii 14,420 12
Sala de grupa 50,020 12
Sala de grupa 50,020 12
Grupa sanitar fete 12,600 12
Grup sanitar educatoare 1,270 12
Grup sanitar baieti 9,920 12
Hol+vestiar 27,140 12
Sala de mese 33,060 12
Sala multifunctionala 67,210 12
Birou 9,370 12
Spalatorie 9,200 12
Casa scarii 14,330 12
Sala de grupa 50,060 12
Sala de grupa 50,060 12
Etaj
Grupa sanitar fete 12,510 12
Grup sanitar educatoare 1,350 12
Grup sanitar baieti 9,820 12
Hol 34,080 12
Depozit jucarii si materiale ed. 32,900 12
169
CLADIREA REALA
Calculul pierderilor de caldura pentru temperatura preliminara Ɵe=12 °C
Q g =Q i+ Q s
Qi=degajarile de caldura interne date de persoane si aparatura
Qs=aporturiel solare prin elementele vitrate
Qi=(Qih+(1-b)x ɸ iu )xt KWh conform Mc001-1-2-3,pag.19 (pag 186 din pdf)
Qih=se refera la degajarile de caldura in spatiul incalzit
(1-b)xɸiu
(1-b)xɸiu se refera la degajarile de caldura a spatiilor neincalzite KW
Qi=Qih x t 0
Qih=ɸi x A inc ɸi=fluxul termic mediu
A inc 576,480 m²
ɸi= 4 W/m² conf. SR EN 13790 anexa K- pag 60
Qih= 2305,92 W
t= 4584
Qi=Qih x t 10570,34 KWh
Qs=0.40x Ʃ ij I gj x g x Af ij/V calcul simplificat conf C107/1-pect. 7.6.1,pg.19
Igj =radiatia solara totala pe suprafata de 1 mp pe orientarea j J/m²
Afij=aria suprafetei vitrate i cu orientarea j
g=gradul de penetrare al energiei solare a suprafetei n
g= 0,75 conf. C107/1-pag. 20
V=volumul incalzit mc
V= 1902,744 mc
170
CLADIREA REALA
Calculul ariei receptoare echivalente a suprafetei n pe orientarea j
FERESTRE DUBLE DIN LEMN 0,40 g Afijxgx0.4
ORIENTARI L (m) H (m) Buc S (mp)
FERESTRE 0,80 1,25 5 5,000
N-E FERESTRE 0,80 1,40 5 5,600 0,40 0,75 3,788
USI 0,90 2,25 1 2,025
FERESTRE 0,00 0,00 0 0,000
S-V 0,40 0,75 0,608
USI 0,90 2,25 1 2,025
FERESTRE 2,00 1,40 12 33,600
FERESTRE 1,00 1,40 1 1,400
FERESTRE 0,60 1,40 1 0,840
N-V 0,40 0,75 14,106
FERESTRE 1,10 1,40 2 3,080
USI 1,80 2,25 1 4,050
USI 0,90 2,25 2 4,050
FERESTRE 2,00 1,40 10 28,000
S-E FERESTRE 0,60 1,40 4 3,360 0,40 0,75 10,016
USI 0,90 2,25 1 2,025
SUPRAFATA TOTALA 95,055
171
CLADIREA REALA
Fluxul aporturilor de caldura
ɸg=Qg/t W
ɸg= 2931,585 t= 4584 h
Determinarea factorului de utilizare preliminar ɳ1
Determinam coef adimensional ɣ=Qg/QL Qg= 13438,386
QL= 129169,47
ρ d c λ A C
Elem. de c-tie
(kg/m3) (m) (J/kgK) (W/mK) m² J/K
Pereti exteriori
Tencuiala interioara 1700 0,02 840 0,870 394,322 9797785,175
Zidarie BCA 725 0,35 870 0,300 394,322 26115420,04
Tencuiala exterioara 1700 0,03 840 0,870 394,322 14696677,76
Placa pe sol-pardoseala rece 50609882,98
Gresie 2400 0,01 920 2,03 177,170 7941184,608
Adeziv gresie 1800 0,005 840 0,93 177,170 1245646,836
Sapa egalizare 1800 0,03 840 0,93 177,170 7473881,016
Beton armat 2400 0,15 840 1,74 177,170 93222601,92
Placa pe sol-pardoseala calda 109883314,4
Parchet 800 0,02 2510 0,23 108,420 1001453,856
Polistiren extrudat 20 0,006 1460 0,03 108,420 569,85552
Sapa egalizare 1800 0,03 840 0,93 108,420 4573676,016
Beton armat 2400 0,15 840 1,74 108,420 57048001,92
Placa pod 62623701,65
Tencuiala 1800 0,020 840 0,870 306,400 9596,448
Beton armat 2400 0,120 840 1,740 306,400 128976261,1
128985857,6
C= 352102756,576
ɽ=C/H H= 2325,224 W/K
C= 352102756,58 J/K
ɽ= 42,063 h 151427,428 sec
a=a0+(ɽ/ɽ0) 2,202
ɳ=(1-ɣa)/(1-ɣa+1)= 0,996588814 factorul de utilizare al aporturilor de caldura - conf. Mc001-1-2-3 pag 23 (pag 190 din pdf)
172
CLADIREA REALA
Determinarea temperaturii de echilibru si perioada de incalzire reala a cladirii
PERIOADA IULIE AUG SEPT OCT NOI DEC IAN FEB MAR APR MAI IUN
TEMP.EXTER 19,3 18,7 14,8 9 3,8 -1,2 -4,4 -1,4 4,2 10 15 17,9
17,73 17,73 17,73 17,73 17,73 17,73 17,73 17,73 17,73 17,73 17,73 17,73
25
20
15
10
0
IULIE AUG SEPT OCT NOI DEC IAN FEB MAR APR MAI IUN
-5
Ɵem=ƩƟe(x=1-n)/z
NUMAR Qe0 Qext Dz
LUNA ZILE [˚C] [˚C] ZILE θem
August 31 17,73 18,7 0
Septembrie 30 17,73 14,8 30
Octombrie 31 17,73 9 31
Noiembrie 30 17,73 3,8 30
Decembrie 31 17,73 -1,2 31
Ianuarie 31 17,73 -4,4 31
5,57
Februarie 28 17,73 -1,4 28
Martie 31 17,73 4,2 31
Aprilie 30 17,73 10 30
Mai 31 17,73 15 31
Iunie 30 17,73 17,9 0
Iulie 31 17,73 19,3 0
Σ 273
173
CLADIREA REALA
Calculul pierderilor de caldura ale cladirii (Ɵe=17,73 °C)
Q g,real =Q i+ Q s
Qi=degajarile de caldura interne date de persoane si aparatura
Qs=aporturiel solare prin elementele vitrate
Qi=(Qih+(1-b)x ɸ iu )xt KWh conform Mc001-1-2-3,pag.19 (pag 186 din pdf)
Qih=se refera la degajarile de caldura in spatiul incalzit
(1-b)xɸiu
(1-b)xɸiu se refera la degajarile de caldura a spatiilor neincalzite KW
Qi=Qih x t 0
Qih=ɸi x A inc ɸi=fluxul termic mediu
A inc 576,480 m²
ɸi= 4 W/m² conf. SR EN 13790 anexa K- pag 60
Qih= 2305,92 W
t= 6552
Qi=Qih x t 15108,39 KWh
Qs=0.40x Ʃ ij I gj x g x Af ij/V calcul simplificat conf C107/1-pect. 7.6.1,pg.19
Igj =radiatia solara totala pe suprafata de 1 mp pe orientarea j J/m²
Afij=aria suprafetei vitrate i cu orientarea j
g=gradul de penetrare al energiei solare a suprafetei n
g= 0,75 conf. C107/1-pag. 20
V=volumul incalzit mc
V= 1902,744 mc
174
CLADIREA REALA
Calculul ariei receptoare echivalente a suprafetei n pe orientarea j
FERESTRE DUBLE DIN LEMN 0,40 g Afijxgx0.4
ORIENTARI L (m) H (m) Buc S (mp)
FERESTRE 0,80 1,25 5 5,000
N-E FERESTRE 0,80 1,40 5 5,600 0,40 0,75 3,788
USI 0,90 2,25 1 2,025
FERESTRE 0,00 0,00 0 0,000
S-V 0,40 0,75 0,608
USI 0,90 2,25 1 2,025
FERESTRE 2,00 1,40 12 33,600
FERESTRE 1,00 1,40 1 1,400
FERESTRE 0,60 1,40 1 0,840
N-V 0,40 0,75 14,106
FERESTRE 1,10 1,40 2 3,080
USI 1,80 2,25 1 4,050
USI 0,90 2,25 2 4,050
FERESTRE 2,00 1,40 10 28,000
S-E FERESTRE 0,60 1,40 4 3,360 0,40 0,75 10,016
USI 0,90 2,25 1 2,025
SUPRAFATA TOTALA 95,055
175
CLADIREA REALA
Fluxul aporturilor de caldura
ɸg=Qg/t W
ɸg= 2837,588 t= 6552 h
Determinarea factorului de utilizare preliminar ɳ1
Determinam coef adimensional ɣ=Qg/QL Qg= 18591,878
QL= 117706,1403
ρ d c λ A C
Elem. de c-tie
(kg/m3) (m) (J/kgK) (W/mK) m² J/K
Pereti exteriori
Tencuiala interioara 1700 0,02 840 0,870 394,322 9797785,175
Zidarie BCA 725 0,35 870 0,300 394,322 26115420,04
Tencuiala exterioara 1700 0,03 840 0,870 394,322 14696677,76
Placa pe sol-pardoseala rece 50609882,98
Gresie 2400 0,01 920 2,03 177,170 7941184,608
Adeziv gresie 1800 0,005 840 0,93 177,170 1245646,836
Sapa egalizare 1800 0,03 840 0,93 177,170 7473881,016
Beton armat 2400 0,15 840 1,74 177,170 93222601,92
Placa pe sol-pardoseala calda 109883314,4
Parchet 800 0,02 2510 0,23 108,420 1001453,856
Polistiren extrudat 20 0,006 1460 0,03 108,420 569,85552
Sapa egalizare 1800 0,03 840 0,93 108,420 4573676,016
Beton armat 2400 0,15 840 1,74 108,420 57048001,92
Placa pod 62623701,65
Tencuiala 1800 0,020 840 0,870 306,400 9596,448
Beton armat 2400 0,120 840 1,740 306,400 128976261,1
128985857,6
C= 352102756,576
ɽ=C/H H= 2325,224 W/K
C= 352102756,58 J/K
ɽ= 42,063 h 151427,428 sec
a=a0+(ɽ/ɽ0) 2,202
ɳ=(1-ɣa)/(1-ɣa+1)= 0,994327429 factorul de utilizare al aporturilor de caldura - conf. Mc001-1-2-3 pag 23 (pag 190 din pdf)
176
XII. Consumul de energie pentru incalzire, Qfh :
Qfh=Qh,real+Qth-Qrhh-Qrwh (kWh/an)
Qh,real- necesarul de energie reala pentru incalzirea cladirii
Qth-totalul pierderilor de caldura datorate instalatiei de incalzire, inclusiv
pierderile de caldura recuperate. Se includ de asemenea pierderile de caldura
suplimentare datorate distributiei neuniforme a temperaturii in incinte si reglarea
imperfecta a temperaturii interioare, in cazul in care nu sunt luate deja in
considerare la temperatura interioara conventionala
Qrhh-caldura recuperata de la subsistemul de incalzire: coloane+racorduri
Qrwh – caldura recuperata de la susbsistemul de preparare a apei calde pe
perioada de incalzire
Qth= Qem+Qd (kWh/an)
Qem- pierderile de caldura cauzate de un sistem non-ideal de transmisie a
caldurii la consumator
Qd – energia termica pierduta pe reteaua de distributie
Qem= Qemstr+Qemc (kWh)
Qemstr - pierderi de caldura cauzate de distributia neuniforma a temperaturii
Qemc – pierderi de caldura cauzate de dispozitive de reglare a temperaturii
interioare utilizand metoda bazata pe eficienta sistemului de reglare
( )
Qemstr= ∗ , (kWh)
ηem- eficienta sistemului de transmisie a caldurii in functie de tipul de corp
de incalzire, conf. McII-1, anexa II, tab 1B
( )
Qemc= ∗ , (kWh)
ηc- eficienta sistemului de reglare, conf. McII-1, anexa II, tab 3B, pag 59
Qd=∑ ( ∗( − ) ∗ ∗ ) (kWh/an)
U’i- valoarea coeficientului de transfer termic de caldura
θm- temperatura medie a agentului termic
θai- temperatura aerului exterior conductelor
Li- lungimea conductei
tH- numarul de ore in pasul de timp
θm=
U’i= (W/mK) – valoarea coeficientului de transfer de
∗
∗
caldura
λiz- coeficient de conductie a izolatiei
da- diametrul exterior al conductei cu izolatie
di- diametrul conductei fara izolatie
αa- coeficient global de transfer termic
177
Pierderile de caldura a elementelor conexe (robinete, armaturi, suporturi
neizolate etc.) se iau in calcul ca o lungime echivalenta stabilita conform Mc001-
2 tab 1.3., in functie de diametru si de existenta sau inexistenta izolatiei.
178
CLADIREA REALA
CONSUMUL DE ENERGIE PENTRU INCALZIRE - Qfh
Qth-totalul pierderilor de caldura datorate instalatiei de incalzire, inclusiv pierderile de caldura recuperate. Se includ de asemenea
pierderile de caldura suplimentare datorate distributiei neuniforme a temperaturii in incinte si reglarea imperfecta a temperaturii
interioare, in cazul in care nu sunt luate deja in considerare la temperatura interioara conventionala
Qrhh- caldura recuperata de la subsistemul de incalzire: coloane+racorduri
Qrwh - caldura recuperata de la subsistemul de preparare a apei calde pe perioada de incalzire
Qemc- piereri de caldura cauzate de dispozitive de reglare a temperaturii interioare utilizand metoda bazata pe eficienta sistemului de reglare
Qemc= (1-ηc)/ηc*Qh 3068,6513 (kWh/an) (conf. Mc001-4 pag 26)
ηc- eficienta sistemului de reglaj (conf. Mc001-1-2-3 pag 59- pag 226 in pdf)
ηc= 0,97 pt. reglare locala+reglarea temperaturii a agentului termic tot-nimic (on-off)cu histerezis, radiatoare si convectoare
179
Qem= Qemstr+Qemc= 10536,803 (kWh/an)
Racdorduri
L= 570 m
Da=Di= 0,015 m
1/2*λD= 10,822511
180
ln(Da/Di)= 0
1/(αa*Da)= 2200
U'2= 0,0014273
Di Da Li Lea Ui θm θai tH Qd
(m) (m) (m) (m) (W/mK) (°C) (°C) (h) kWh
Coloane 0,035 0,035 30 4 0,00333 70 18,905 6552 37,90661
Racorduri 0,015 0,015 570 4 0,001427 70 18,905 6552 274,2655
TOTAL 312,1721
181
CONSUMUL DE ENERGIE PENTRU CLIMATIZARE - QR
- calculul necesarului de energie pentru racire
în care:
- Q R - energia necesară pentru răcirea clădirii, [MJ];
- QTr- energia totală transferată între clădire şi mediul exterior, în situaţia răcirii
clădirilor, [MJ];
- Qsurse - energia totală furnizată de sursele de căldură, în situaţia răcirii clădirii,
[MJ];
- ηR - factorul de utilizare a pierderilor de căldură, în situaţia răcirii
Transfer de caldura
HT=L+Ls+Hu
L-coeficient de cuplaj termic prin anvelopa cladirii
Hu=0 – coeficientul de pierderi termice prin spatii neincalzite ;
Qsurse.interne=(ΣΦi.R+Σ(1-bj)Φi.u.j)xNore /1000
Φi.R- Fluxul termic mediu al degajarilor interne in spatiile incalzite, conform Mc 001-PII
(Anexa II.2.D) este 6W/mp.
Φi.u.j –fluxul termic mediu al degajarilor interne in spatii neincalzite este 0 w/mp;
Qsurse=Qsolar +Qsurs.interne
QR=Qsurse –ηR x Qtransfer - Qvent.nocturna
Qvent.nocturna=0
1 − λαRR
ηTr ,R =
1 − λαRR +1
- dacă λR>0 şi λR ≠ 1 atunci ;
αR
- dacă λR =1 atunci ηTr , R = ;
αR +1
- dacă λR < 0 atunci η Tr , R = 1
în care, pentru fiecare lună şi pentru fiecare zonă considerată:
ηTr,R factorul de utilizare a pierderilor de căldură în situaţia răcirii;
λR raportul dintre aporturile şi pierderile de căldura ale zonei în perioada de răcire;
Qsurse, R
λR =
Qt , R
Qsurse,R aporturile de căldura totale pentru răcire
QTr,R energia totală transferată între clădire şi mediul exterior
αR parametru numeric adimensional ce depinde de constanta de timp a clădirii pentru răcire τR, care
se calculează cu relaţia:
τR
α R = α 0R +
τ 0R
unde:
α 0 R =1.0 parametru numeric de referinţă, determinat conform tabelului 2.9;
τ R
=26.0l constanta de timp pentru răcire;
τ 0 R =15 constanta de timp de referinţă pentru răcire, determinată conform tabelului 2.9
CLADIREA REALA
CONSUMUL DE ENERGIE PENTRU CLIMATIZARE - QR
Calculul energiei disipate de clădire prin transmisie
QT = Σk { HT,k. (θi – θe,k)}.t
Luna HTk θi,med θ e.k Nore QT
[ W/K ] [ °C ] [ °C ] [h] [ kWh ]
Mai 1613.6 25 15 230 3711.28
Iunie 1613.6 25 17.9 230 2635.009
Iulie 1613.6 25 19.3 230 2115.43
August 1613.6 25 18.7 230 2338.106
Septembrie 1613.6 25 14.8 230 3785.506
TOTAL 14585.33
astfel pentru:
- ventilator grup sanitar si anexe 100 mc/h 25 W 10 buc 179 h/an 45 kWh/an
- ventilatoare hota bucatarie (ev/in) (3350/2600) 750 mc/h 900 W 1 buc 358 h/an 322 kWh/an
- ventilator spalatorie/calcatorie 350 mc/h 400 W 2 buc 179 h/an 143 kWh/an
- instalatia de evacuare/introducere din bucatarie (3350/2600 mc/h):
astfel:
Qvt = Qv1 + Qv2 + Qv3 = 212 kWh/an
si
q = qv1 + qv 2 + qv 3 = 8,049 kWh/mp,an
182
XIII. Consumul de energie pentru prepararea apei calde menajere,
Qacm
Qacm=Qac+Qacc+Qacd (kWh/an)
Qacm- consumul de energie pentru prepararea apei calde
Qac- necesarul de caldura pentru prepararea apei calde de cosnum livrata
Qacc- pierderi de caldura aferente pierderilor si risipei de apa calda
Qacd- pierderi de caldura pe conductele de distributie a apei calde menajere
Qac= ρ*c*Vac*(θac-θar) (kWh/an)
ρ- denistatea apei calde de consum la temperatura de 60°C, tab 3.3 pag 14
Mc003
c- Caldura specifica a apei calde menajere la temperatura de 60°C
Vac- volumul necesar de apa calda menajera
θac-temperatura apei calde de consum
θar-temperatura apei reci care intra in sistemul de preparare a a apei calde
ρ= 983.2 (kg/m3)
c= 4.183*103 (J/kgK)
Vac= a* (m3/an)
a- Necesarul specific de apa calda menajera pentru o persoana
Nu- numar de persoane
Qacc=Σρ*c*Vacc*( θacc-θar)
Vacc- volumul corespunzator pierderilor si risipei de apa calda menajera
θacc-temperatura de furnizare/utilizare a apei calde
Qacd= Σ[U’i*( θm-θai)*Li*tH] (kWh/an)
U’i- valoarea coeficientului de transfer de caldura
Li- lungimea conductei
tH- numarul de ore in pasul de timp
U’i= (W/mK)
∗
∗
183
CLADIREA REALA
b)Calculul energiei pentru prepararea apei calde
Qacd=ΣUi*(θm-θa,i)*Li*tH (kWh/an)
Qacd- pierderile de caldura prin sistemul de distributie
Ui-valoarea coeficientului de transfer termic W/mK
θm- temperatura medie a agentului termic °C
θa,i-temperatura aerului exterior (ambianta) °C
Li- lungimea conductei
tH- numarul de ore in pasul de timp h/pasul de timp
U=π/((1/(2*λD))*ln(Da/Di)+(1/(αa*Da)))
Da,Di- diametrele conductei fara izolatie, respectiv diametrul exterior al conductei (m)
2
αa- coeficientul global de transfer termic la exteriorul conductei (W/m K)
184
λD- coeficientul de conductie al izolatiei (W/mK)
λ D= 0,0462 W/mK
3
αa= 1/33 0,03030303 W/m K
L= 210 m
Da=Di= 0,025 m
1/2*λD= 10,82251082
ln(Da/Di)= 0
1/(αa*Da)= 1320
U'1= 0,002378788
L= 69 m
Da=Di= 0,032 m
1/2*λD= 10,82251082
ln(Da/Di)= 0
1/(αa*Da)= 1031,25
U'2= 0,003044848
L= 58 m
Da=Di= 0,04 m
1/2*λD= 10,82251082
ln(Da/Di)= 0
1/(αa*Da)= 825
U'3= 0,003806061
Di Da Li Ui θm θai tH Qd
(m) (m) (m) (W/mK) (°C) (°C) (h) kWh/an
0,025 0,025 210 0,00237879 60 18,905 8760 179,8325
0,032 0,032 69 0,00304485 60 18,905 8760 75,6324
0,04 0,04 58 0,00380606 60 18,905 8760 79,46882
TOTAL 255,4649
185
XIV. Consumul de energie pentru iluminat
∗∑
Wil=6A+ (kWh/an)
tu=(tD+FD+Fo)+(tN*Fo)
Pn- puterea instalata
tD- timpul de utilizare al luminii de zi in functie de timpul cladirii
tN- timpul in care nu este utilizata lumina naturala
FD- factorul de dependenta de lumina de zi
Fo- factorul de dependenta de durata de utilizare
A- Aria pardoselii folosite in cladire
Numarul 6 din relatia consumului de energie Wil este egal cu 1 kWh/mp/an
reprezinta consumul de energie estimat pentru incarcarea bateriilor corpurilor de
iluminat de siguranta, la care se adauga 5kWh/mp/an, care reprezinta consumul
de energie electrica pentru sistemul de control al iluminatului.
Factorii tD,FD,Fo,tN de gasesc in tabele in Mc001.
Valoarea consumului total se corecteaza cu anumiti coeficienti in functie de:
- Raportul dintre supraftaa vitrata a anvelopei si suprafata pardoselii
spatiului incalzit
- Faptul ca grupurile sanitare nu sunt prevazute cu ferestre exterioare.
186
CLADIREA REALA
CONSUMUL DE ENERGIE PENTRU ILUMINAT
Wilum=6A+( tuΣPn/1000) (kWh/an) (conf. Mc001- II.4, pag 8, pag 413 in pdf)
tu=(tD*FD*FO)+(tN*FO)
Pn-puterea instalata
tD- timpul de utilizare a iluminatului artificial pe timp de zi (conf. Mc-001-anexa II.4.B1, tab 1, pag 33, pag 438 din pdf)
tN- timpul in care nu este utilizata lumina naturala (conf. Mc-001-anexa II.4.B1, tab 2, pag 33, pag 438 din pdf)
FD- factorul de depeundenta de lumina de zi (conf. Mc-001-anexa II.4.B1, tab 2, pag 33, pag 438 din pdf)
FO- factorul de dependenta de durata de utilizare (conf. Mc-001-anexa II.4.B1, tab 3, pag 34, pag 439 din pdf)
2
A- aria totala a pardoselii folosite in cladire (m )
Nota: nr. 6 din relatia de calcul reprezinta 1 kWh/m2/an ( consumul de energie estimat pentru incarcarea bateriilor
corpurilor de iluminat de siguranta) la care se adauga 1 kWh/m2/an (consumul de energie electrica pentru sistemul de
tD 1800 h/an
tN 200 h/an
FD 1 (pentru cladiri de invatamant si tipul sistemului de control manual)
FO 1 (pentru cladiri de invatamant si tipul sistemului de control manual)
Nota: pentru calculul puterii instalate se pot lua in calcul valorile din Mc001
anexa II.4.A1, considerand ca iluminatul atinge cerintele standard al nivelului
de iluminare in functie de destinatia incaperilor - pag 23, pag 428 din pdf
Pn 7,304 kW
2
A 591,99 m
tu=(tD*FD*FO)+(tN*FO) 2000
Wilum=6A+( tuΣPn/1000) 18159,94 kWh/an
187
XV. Energia primara si emisiile de CO2
Ep= Qfhl*fhl+ Qfwl* fwl +Wil. tot * fil (kWh/an)
Qfhl- energia consumata pentru incalzire, combustibil gaz natural
Qfwl- energia consumata pentru prepararea apei calde menajere, combustibil
gaz natural
Wil. tot – energia consumata pentru iluminat
fwl= fhl- factorul de conversie in energia primara pentru gaz natural
fil- factorul de conversie in energie primara pentru energie electrica
Qfhl= Qfh
Qfwl= Qacm
fwl, fhl, fil- se considera conform Mc001-PI.1, pag 52, tab. I.1.12
ECO2= Qfhl*fhCO2+Qfwl*fwCO2+Wil.tot*fiCO2 (kg/an)
ICO2= (kgCO2/m2an)
188
CLADIREA REALA
ENERGIA PRIMARA SI EMISIILE DE CO2
1. Energia primara
Qf,i=Qfhi+Qfvi+Qfci+Qfwi+QfLi (kWh/an)
Qfhi- energia consumata pentru incalzire
Qfvi- energia consumata pentru ventilare
Qfci- energia consumata pentru racire
Qfwi- energia consumata pentru preparare apa calda menajera
QfLi- energia consumata pentru iluminat
Qfhi 109565.45 (kWh/an)
Qfvi 212.13 (kWh/an)
Qfci 30148.37 (kWh/an)
Qfw 54173.30 (kWh/an)
QfLi 19975.93 (kWh/an)
Qf,i 214075.19 (kWh/an)
Wh 0 (kWh/an)
Qex,i 0 (kWh/an)
fphl 1.1 gaz natural (conf. Mc001 tab I.1.12 pag 52, pag 219 din pdf)
fpwl 1.1 gaz natural (conf. Mc001 tab I.1.12 pag 52, pag 219 din pdf)
energie
fpvi 2.8 electrica (conf. Mc001 tab I.1.12 pag 52, pag 219 din pdf)
energie
fpci 2.8 electrica (conf. Mc001 tab I.1.12 pag 52, pag 219 din pdf)
energie
fpLi 2.8 electrica (conf. Mc001 tab I.1.12 pag 52, pag 219 din pdf)
Ep=Qfhl*fphl+Qfvi*fpvi +Qfvi*fpvi ++Qfwl*fpwl+QfLi*fpLi
Ep 321054.65 (kWh/an)
e= Ep,h/Qh
e- coeficientul de performanta energetica a sistemului de instalatii
Ep,h- energia primara consumata de sistem
Qh- necesarul de caldura pentru incalzire
Ep,h- energia primara consumata de sistem
Ep,h=Qfhl*fphl
Ep,h 120522.0001 (kWh/an)
Qh 99219.72569 (kWh/an)
e 1.215
3. Emisia de CO2
ECO2=Σ(Qf,i*fCO2,i+ΣWh*fCO2,i)-Σ(Qex,i*fCO2,i)
fCO2,i- factorul de emisie conf. Mc001 tab I.1.13 si I.1.14, pag 53, pag 220 din pdf)
fCO2,gaz 0.205 (kg/kWh)
fCO2,electricitate 0.09 (kg/kWh)
ECO2 38096.72 kg/an
XVI. Certificarea energetica a cladirii reale
1. Penalizari acordate cladirii certificate.
Penalizarile acordate cladirii la notarea din punct de vedere energetic a
acesteia sunt datorate unor deficiente de intretinere si exploatare a cladirii si
instalatiilor aferente acesteia, avand drept consecinte utilizarea nerationala a
energiei.
Acestea se detrmina cu relatia:
p0=p1*p2*p3*p4*p5*p6*p7*p8*p9*p10*p11*p12
p1- coeficient de penalizare functie de starea subsolului tehnic al cladirii
p2- coeficient de penalizare functie de utilizarea usii de intrare in cladire
p3- coeficient de penalizare functie de starea elementelor de inchidere mobile
din spatiile comune catre exterior sau catre ghene de gunoi
p4- coeficient de penalizare functie de starea armaturilor de inchidere si reglaj
de la corpurile statice
p5- coeficient de penalizare functie de spalarea/curatirea instalatieie de
incalzire interioare
p6- coeficient de penalizare functie de existenta armaturilor de separare si
golire a coloanelor de incalzire
p7- coeficient de penalizare functie de existenta echipamentelor de masura
pentru decontarea consumurilor de caldura
p8- coeficient de penalizare functie de starea finisajelor exterioare ale
peretilor exteriori
p9- coeficient de penalizare functie de starea peretilor exteriori din punct de
vedere al continutului de umiditate al acestora
p10- coeficient de penalizare functie de starea acoperisului peste pod- pentru
cladiri prevazute cu pod nelocuibil
p11- coeficient de penalizare functie de starea cosurilor de evacuare a fumului
– pentru cladiri dotate cu sisteme locale de incalzire/preparare acm cu combustibil
lichid sau solid
p12- coeficient de penalizare care tine seama de posibilitatea asigurarii
necesarului de aer proaspat la valoarea de confort
2. Nota energetica
Notarea din punct de vedere energetic a unei cladiri se efectueaza functie de
consumul specific anual normal de caldura estimat pe baza analizei termice si
energetice a cladirii.
- Consumul anual specific de energie pentru incalzirea spatiilor
qinc= (kWh/m2an)
- Consumul anual specific de energie pentru prepararea apei calde
menajere
qacm= (kWh/m2an)
- Consumul specific de energie pentru iluminat
190
.
wil= (kWh/m2an)
- Consumul total anual specific de energie
qtot= qinc+qacm+wil (kWh/m2an)
191
PENALIZARI ACORDATE CLADIRII CERTIFICATE
p0= p1*p2*p3*p4*p5*p6*p7*p8*p9*p10*p11*p12 conf. Mc001 II.4.5 pag 29, pag 512 din pdf
p3- coeficient de penalizare functie de starea elementelor de inchidere mobile din spatiile comune catre exterior
conf. Mc001 II.4.5 , tab II.4.5, pag 30 (513)
p3 1,02 ferestre/usi in stare buna, dar neetanse
p4- coeficient de penalizare functie de starea armaturilor de inchidere si reglaj de la corpurile statice
conf. Mc001 II.4.5 , tab II.4.6, pag 30 (513)
p4 1,00 corpurile statice sunt dotate cu armaturi de reglaj si acestea sunt functionale
p6- coeficient de penalizare functie de existenta armaturilor de separare si golire a coloanelor de incalzire
conf. Mc001 II.4.5 , tab II.4.8, pag 31 (514)
p6 1,00 coloanele sunt prevazute cu armaturi de separare si golire
p7- coeficient de penalizare functie de existenta echipamentelor de masura pentru decontarea consumurilor de caldura
conf. Mc001 II.4.5 , tab II.4.9, pag 31 (514)
p7 1,00 cladirea are sistem propriu de incalzire
p8- coeficient de penalizare functie de starea finisajelor exterioare ale peretilor exteriori
conf. Mc001 II.4.5 , tab II.4.10, pag 31 (514)
p8 1,00 stare buna a tencuielii exterioare
p9- coeficient de penalizare functie de starea peretilor exteriori din punct de vedere al continutului de umiditate
conf. Mc001 II.4.5 , tab II.4.11, pag 32 (515)
p9 1,00 pereti exteriori uscati
p12- coeficient de penalizare care tine seama de posibilitatea asigurarii necesarului de aer proaspat la valoarea de confort
conf. Mc001 II.4.5 , tab II.4.14, pag 32 (515)
p12 1,00 cladire cu sistem de ventilare organizata
p0 1,03
192
CLADIREA REALA
CERTIFICAREA ENERGETICA A CLADIRII REALE
CLASA D
CLASA E
qv = 8.05 kWh/m²an
CLASA C
qc = 50.93 kWh/m²an
CLASA C
qtot=qinc +qacm+qilum+qv+qc
qtot= 369.31 kWh/m²an
CLASA C
CLADIREA REALA
NOTA ENERGETICA
conf. II.4.4 pag 28 (511)
N= exp(-B1*qtot*p0+B2) pentru (qtot*p0)> qTM kWh/m²an
N=100 pentru (qtot*p0)≤ qTM kWh/m²an
B1,B2- coeficienti numerici dterminati din tab II.4.2 in functie de cazul de incadrare a cladirii din
punct de vedere al utilitatilor existente conform tab. II.4.1
B1 0.001053
B2 4.73677
qTM 125 kWh/m²an
qtot*p0 380.46 kWh/m²an
(qtot*p0)> qTM=>
Nc 76.41214