Prezentarea schemei electrice

monofilare a statiei electrice


Arefu 220/110/20 KV

ELEV: MAGUREANU CRISTIAN-ALEXANDRU


GRUPA:2302 ME
Cuprins
1.INTRODUCERE
2.STATIA DE 220 KV
3.STATIA DE 110 KV
4.STATIA DE 20 KV
5.FOAIE MANEVRA EXECUTIE
6.AVANTAJE
Introducere

STAȚIA ELECTRICĂ AREFU 220/110/20 KV ESTE


AMPLASATĂ ÎN JUDEŢUL ARGEŞ, PE DRUMUL NAŢIONAL
CURTEA DE ARGEŞ – BÂLEA LAC, LA 20 KM DE CURTEA
DE ARGEŞ, ALIMENTAND CONSUMATORII ZONALI CAT SI
REGIONALI.
CONSUMATORII SUNT GRUPATI IN FUNCTIE DE
LINIA ELECTRICA UTILIZATA SI PUTEREA TRANSMISA PE
LINIE , ASTFEL PRINCIPALII CONSUMATORI SUNT :
-STATIA 220 KV: LEA AREFU-BRADU , RAURENI
-STATIA 110 KV:LEA OIEȘTI,CÂMPULUNG 1 SI
CÂMPULUNG 2 + CHE LEREȘTI
Statia 220 KV
STATIA CUPRINDE :
-LINIA DE 220 KV BRADU
-LINIA DE 220 KV RAURENI
-CUPLA TRANSVERSALA
-DOUA AT 220/110KV DE 200MVA;
-2 CELULE DE MASURA
-2 LINII DE RACORD CU CENTRALA UHE 1 SI 2
Statia 110 KV
STATIA CUPRINDE:
-3 CELULE LEA (OIEȘTI,CÂMPULUNG 1 SI
CÂMPULUNG 2 + CHE LEREȘTI)
-2 CELULE DE AT 220/110 KV
-2 CELULE DE TRANSFORMATOARE (1T SI 2T
DE 110/20 KV -16MVA)
-1 CELULĂ CUPLĂ TRANSVERSALĂ
-2 CELULE DE MASURĂ ȘI DESCĂRCĂTOARE
Celula de Celula de
transforma transforma
re 1 T re 2 T
Statia 20 KV Statia cuprinde :
-Celulă de măsură și
descărcător
-Celula de cupla
transversala
-Celula de trafo servicii
propri
-Celula de transformator
putere 110/20 kV
-9 celule de linie
Foaie manevra de executie
TEMĂ: ADUCEREA ÎN STARE ÎN FUNCŢIUNE A LINIEI LEA 220KV BRADU PE
SISTEMUL DE BARE B1.
SCOP: PUNEREA SUB TENSIUNE A LINIEI LEA 220KV BRADU.
S.O.I.: LINIA LEA 220KV BRADU ÎN REZERVĂ RECE FAŢĂ DE B1.
 
A. DESFĂŞURAREA MANEVREI:
A1. SE VERIFICĂ POZIŢIA DECONECTAT A ÎNTRERUPTORULUI 1.1;
A2. SE VERIFICĂ POZIŢIA DESCHIS A SEPARATORULUI DE LINIE 1.2.3;
A3. SE VERIFICĂ POZIŢIA DESCHIS A SEPARATORULUI DE BARE 1.3;
A4. SE VERIFICĂ POZIŢIA DESCHIS A SEPARATORULUI DE BARE 1.2.1;
A5. SE ÎNCHIDE SEPARATORUL DE BARE 1.3;
A6. SE VERIFICĂ POZIŢIA ÎNCHIS A SEPARATORULUI DE BARE 1.3;
A7. SE ÎNCHIDE SEPARATORUL DE LINIE 1.2.3;
A8. SE VERIFICĂ POZIŢIA ÎNCHIS A SEPARATORULUI DE BARE 1.2.3;
A9. SE CONECTEAZĂ ÎNTRERUPTORUL 1.1 ( CU ACCORDUL DISPECERULUI
);
A10. SE VERIFICĂ POZIŢIA CONECTAT A ÎNTRERUPTORULUI 1.1;
A11. SE VERIFICĂ PREZENŢA TENSIUNII PE LINIA LEA 220KV BRADU PRIN
TRANSFORMATORUL DE TENSIUNE
B. REVENIREA LA STAREA OPERATIVĂ INIŢIALĂ
B1. SE DECONECTEAZĂ ÎNTRERUPTORUL 1.1;
B2. SE VERIFICĂ POZIŢIA DECONECTAT A ÎNTRERUPTORULUI
1.1;
B3. SE DESCHIDE SEPARATORUL DE BARE 1.3;
B4. SE VERIFICĂ POZIŢIA DESCHIS A SEPARATORULUI DE BARE
1.3;
B5. SE DESCHIDE SEPARATORUL DE LINIE 1.2.3;
B6. SE VERIFICĂ POZIŢIA DESCHIS A SEPARATORUL DE LINIE
1.2.3;
B7. SE VERIFICĂ ABSENŢA TENSIUNII PE LINIA LEA 220KV
BRADU PRIN TRANSFORMATORUL DE TENSIUNE
Elemente componente ale statiei
-TRAFO 110/20 KV
-DESCARCATOARE
-LEA 110 KV REZERVA
NEECHIPATA
-AUTOTRAFO 220/110 KV
-1 AT 200 MVA Y0D5
Avantaje
Dezavantaje
-utilizarea întreruptoarelor debroșabile; -Valori ridicate ale curenților de
-realimentarea consumatorilor in cel mai scurtcircuit;
scurt timp; -Investiții ridicate și cheltuieli mari
de mentenanță;
-lichidarea incidentelor si avariilor in cel
mai scurt timp;

Imbunatatiri
-retehnologizarea statiilor