SR EN 15004-8
Înlocuieşte SR EN 15004-8:2008
© ASRO Reproducerea sau utilizarea integrală sau parţială a prezentului standard în orice
publicaţii şi prin orice procedeu (electronic, mecanic, fotocopiere, microfilmare etc.) este
interzisă dacă nu există acordul scris prealabil al ASRO
English Version
14520-13:2015, modified)
Installations fixes de lutte contre l'incendie - Ortsfeste Brandbekämpfungsanlagen - Löschanlagen
Installations d'extinction à gaz - Partie 8 : Propriétés mit gasförmigen Löschmitteln - Teil 8: Physikalische
physiques et conception des systèmes pour agent Eigenschaften und Anlagenauslegung für Löschmittel
extincteur IG-100 (ISO 14520-13:2015, modifiée) IG-100 (ISO 14520-13:2015, modifiziert)
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15004-8:2017 E
worldwide for CEN national Members.
EN 15004-8:2017 (E)
Contents Page
2
EN 15004-8:2017 (E)
European foreword
This document (EN 15004-8:2017) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by June 2018, and conflicting national standards shall be
withdrawn at the latest by June 2018.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
InfoStandard Web, 20325, MINISTERUL AFACERILOR INTERNE
The text of the International Standard ISO 14520-13:2015 from Technical Committee ISO/TC 21
“Equipment for fire protection and firefighting” of the International Organization for Standardization
(ISO) has been taken over as a European Standard by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI, with common modifications which are
indicated by a straight line in the margin of the text.
This European Standard will consist of the following parts, under the general title Fixed firefighting
systems – Gas extinguishing systems:
— Part 2: Physical properties and system design of gas extinguishing systems for FK-5-1-12
extinguishant;
— Part 3: Physical properties and system design of gas extinguishing systems for HCFC Blend A
extinguishant;
— Part 4: Physical properties and system design of gas extinguishing systems for HFC 125
extinguishant;
— Part 5: Physical properties and system design of gas extinguishing systems for HFC 227ea
extinguishant;
— Part 6: Physical properties and system design of gas extinguishing systems for HFC 23
extinguishant;
— Part 7: Physical properties and system design of gas extinguishing systems for IG-01 extinguishant;
— Part 8: Physical properties and system design of gas extinguishing systems for IG-100
extinguishant;
— Part 9: Physical properties and system design of gas extinguishing systems for IG-55 extinguishant;
— Part 10: Physical properties and system design of gas extinguishing systems for IG-541
extinguishant.
3
EN 15004-8:2017 (E)
The International Standards ISO 14520-2 and ISO 14520-11, which dealt with CF3I and HFC 236fa
extinguishants, respectively, have not been implemented by CEN, as CF3I is only valid for local
application and HFC 236fa extinguishant is only applicable for portable fire extinguishers and local
application, respectively, which is not covered by the scope.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
InfoStandard Web, 20325, MINISTERUL AFACERILOR INTERNE
4
EN 15004-8:2017 (E)
1 Scope
1.1 This document specifies requirements for gaseous fire-extinguishing systems, with respect to the
IG-100 extinguishant. It includes details of physical properties, specification, usage and safety aspects.
1.2 This document is applicable for systems operating at nominal pressures of 200 bar at 15 °C and
300 bar at 15 °C. This does not preclude the use of other systems, although design data for other
pressures are not available at this time.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
InfoStandard Web, 20325, MINISTERUL AFACERILOR INTERNE
references, the latest edition of the referenced document (including any amendments) applies.
EN 15004-1:2017, Fixed firefighting systems - Gas extinguishing systems - Part 1: Design, installation and
maintenance
Property Requirement
Purity 99,6 % by volume, min.
Moisture 50 parts per million by mass,
max.
Oxygen 0,1 % by volume, max.
NOTE Only principal contaminants are shown. Other measurements may
include hydrocarbons, CO, NO, NO2, CO2, etc. Most are < 20 × 10−6.
5
EN 15004-8:2017 (E)
IG-100 total flooding systems may be used for extinguishing fires of all classes within the limits
specified in EN 15004-1:2017, Clause 4.
The extinguishant requirements per volume of protected space are shown in Table 3 for various levels
of concentration. These are based on methods shown in EN 15004-1:2017, 7.6.
The extinguishing concentrations and design concentrations for heptane and surface class A hazards
are shown in Table 4.
6
EN 15004-8:2017 (E)
m3/kg 34 % 38 % 42 % 46 % 50 % 54 % 58 % 62 %
–40 0,682 5 0,522 0,601 0,685 0,775 0,872 0,976 1,091 1,217
–35 0,697 1 0,511 0,588 0,671 0,758 0,853 0,956 1,068 1,191
–30 0,711 8 0,501 0,576 0,657 0,743 0,836 0,936 1,046 1,167
InfoStandard Web, 20325, MINISTERUL AFACERILOR INTERNE
–25 0,726 4 0,491 0,565 0,644 0,728 0,819 0,917 1,025 1,143
–20 0,741 1 0,481 0,554 0,631 0,714 0,803 0,899 1,005 1,120
–15 0,755 7 0,472 0,543 0,619 0,700 0,787 0,882 0,985 1,099
–10 0,770 4 0,463 0,533 0,607 0,686 0,772 0,865 0,966 1,078
–5 0,785 0 0,454 0,523 0,596 0,674 0,758 0,849 0,948 1,058
0 0,799 7 0,446 0,513 0,585 0,661 0,744 0,833 0,931 1,038
5 0,814 3 0,438 0,504 0,574 0,649 0,731 0,818 0,914 1,020
10 0,829 0 0,430 0,495 0,564 0,638 0,718 0,804 0,898 1,002
15 0,843 6 0,423 0,486 0,554 0,627 0,705 0,790 0,883 0,984
20 0,858 3 0,416 0,478 0,545 0,616 0,693 0,777 0,868 0,968
25 0,872 9 0,409 0,470 0,536 0,606 0,682 0,764 0,853 0,951
30 0,887 6 0,402 0,462 0,527 0,596 0,670 0,751 0,839 0,936
35 0,902 2 0,395 0,455 0,518 0,586 0,659 0,739 0,825 0,920
40 0,916 9 0,389 0,448 0,510 0,577 0,649 0,727 0,812 0,906
45 0,931 5 0,383 0,440 0,502 0,568 0,639 0,716 0,799 0,892
50 0,946 2 0,377 0,434 0,494 0,559 0,629 0,704 0,787 0,878
55 0,960 8 0,371 0,427 0,487 0,550 0,619 0,694 0,775 0,864
60 0,975 5 0,366 0,421 0,479 0,542 0,610 0,683 0,763 0,851
65 0,990 1 0,360 0,414 0,472 0,534 0,601 0,673 0,752 0,839
70 1,004 8 0,355 0,408 0,465 0,526 0,592 0,663 0,741 0,827
75 1,019 4 0,350 0,403 0,459 0,519 0,584 0,654 0,730 0,815
80 1,034 1 0,345 0,397 0,452 0,511 0,575 0,645 0,720 0,803
85 1,048 7 0,340 0,391 0,446 0,504 0,567 0,636 0,710 0,792
7
EN 15004-8:2017 (E)
m3/kg 34 % 38 % 42 % 46 % 50 % 54 % 58 % 62 %
90 1,063 4 0,335 0,386 0,440 0,497 0,560 0,627 0,700 0,781
95 1,078 0 0,331 0,381 0,434 0,491 0,552 0,618 0,691 0,770
100 1,092 7 0,326 0,376 0,428 0,484 0,545 0,610 0,682 0,760
InfoStandard Web, 20325, MINISTERUL AFACERILOR INTERNE
NOTE This information refers only to the product IG-100, and does not represent any other products
containing nitrogen as a component.
Symbols:
V/V is the agent volume requirements (m3/m3); i.e. the quantity Q R (m3) of agent required at a
reference temperature of 20 °C and a pressure of 1,013 bar per cubic metre of protected volume to
produce the indicated concentration at the temperature specified:
Q R= m ⋅ S R ;
where
SR is the specific reference volume (m3/kg); i.e. the specific vapour volume at the filling
reference temperature for superheated IG-100 vapour at a pressure of 1,013 bar which
may be approximated by the formula:
S R = k 1 + k 2 ⋅ TR ;
where
k1 = 0,799 7
k2 = 0,002 93
TR is the reference temperature (°C); i.e. filling temperature (15 °C in the table)
V 100
m
= ⋅ ln
S 100 − c
V is the net volume of hazard (m3); i.e. the enclosed volume minus the fixed structures
impervious to extinguishant;
T is the temperature (°C); i.e. the design temperature of the protected area;
S is the specific volume (m3/kg); the specific volume of superheated IG-100 vapour at a
pressure of 1,013 bar may be approximated by the formula:
S = k1 + k2 ⋅ T
c is the concentration (%); i.e. the volumetric concentration of IG-100 in air at the
temperature indicated, and a pressure of 1,013 bar absolute.
8
EN 15004-8:2017 (E)
NOTE 3 The minimum design concentration for Surface Class A fuel is the highest value of the
wood crib, PMMA, PP or ABS extinguishment concentrations multiplied by 1,3. In the absence of any
of the 4 extinguishment values, the minimum design concentration for Surface Class A shall be that of
Higher Hazard Class A.
NOTE 4 Higher-Hazard Class A hazards are those having the characteristics described in the
CAUTION statement of EN 15004-1:2017, 7.5.1.3. The minimum design concentration for Higher
Hazard Class A fuels shall be the higher of the Surface Class A or 95 % of the Class B minimum design
concentration.
NOTE 5 See EN 15004-1:2017, 7.5.1.3 for guidance on Class A fuels.
NOTE 6 The extinguishing and design concentrations for room-scale test fires are for informational
purposes only. Lower and higher extinguishing concentrations than those shown for room-scale test
fires may be achieved and allowed when validated by test reports from internationally recognized
laboratories.
5 Safety of personnel
Any hazard to personnel created by the discharge of IG-100 shall be considered in the design of the
system.
Potential hazards can arise from the following:
a) the extinguishant itself, by reduction in oxygen; and
9
EN 15004-8:2017 (E)
Property Value
% by
volume
No observed adverse effect level (NOAEL) 43
Lowest observed adverse effect level (LOAEL) 52
NOTE These values are based on physiological effects in human
subjects of hypoxic atmospheres. These values are the functional
equivalents of NOAEL and LOAEL values, and correspond to 12 %
minimum oxygen for the no-effect level and 10 % minimum oxygen for
InfoStandard Web, 20325, MINISTERUL AFACERILOR INTERNE
6 System design
6.1 Fill pressure
The fill pressure of the container shall not exceed the values given in Tables 6 and 7 for systems
operating at 200 bar at 15 °C and 300 bar at 15 °C respectively.
Other pressures may be used and the minimum design pressure specified accordingly.
The relationships between pressure and temperature are shown in Figure 1.
10
EN 15004-8:2017 (E)
Key
X temperature, °C
Y pressure, bar
Figure 1 — Pressure vs. temperature for IG-100 pressurized to 200 and 300 bar at 15 °C
6.2 Superpressurization
The quantity of extinguishant shall be the minimum required to achieve the design concentration
within the hazard volume at the minimum expected temperature, determined using Table 3 and the
method specified in EN 15004-1:2017, 7.6.
The design concentrations shall be that specified for relevant hazards shown in Table 4. This includes a
1,3 safety factor on the extinguishing concentration.
Consideration should be given to increasing this for particular hazards, and seeking advice from the
relevant authority.
7 Environmental Properties
Extinguishant IG-100 is an inert gas and has zero GWP and zero ODP.
11