POPESCU DANIEL Facultatea de Instalaii, U.T.C.B., dpopescu@instal.utcb.ro IANCU NICOLAE Facultatea de Instalaii, U.T.C.B., nicu1iancu@yahoo.com Abstract The article treats the problem of automatic operate of a reserve electricity power supply to a hospital (AAR), for uninterrupted supply of electricity to major consumers and has a number of specific issues related to design and implement of such an automated system for a hospital. It shows undesirable effects that may be supported by the consumer in case of accidental interruptions in power supply, or in other cases in which is negatively affected the continuity of supply of electricity. The article propose a concrete solution to achieve an automated system for AAR to a hospital. Control logic is implemented with existing programmable controllers, using specific programming techniques. Finally, the article presents a series of conclusions which recommends using programmable controllers in applications aimed uninterrupted electricity supply to consumers.
1. Anclanarea automat a rezervei necesitate pentru alimentarea nentrerupt cu energie electric a consumatorilor vitali
Anclanarea automat a rezervei (AAR) reprezint operaia de conectare rapid a consumatorilor electrici la un circuit de rezerv (linie electric sau transformator), n cazul cderii circuitului normal de alimentare, ca urmare a unui deranjament sau a unei deconectri impuse de ctre dispozitivele de protecie [1,2]. Operaia poate fi aplicat consumatorilor sensibili la goluri de tensiune [3] ce beneficiaz de dou sau mai multe alimentri cu energie electric din surse diferite. Impactul negativ al golurilor de tensiune asupra calitii energiei electrice furnizate consumatorilor este deosebit de important i depinde de tipul acestor goluri de tensiune ct i de curbele de acceptabilitate ale diferitelor clase de echipamente consumatoare de energie electric [4]. Golul de tensiune se definete ca o reducere brusc de tensiune, sub un nivel de prag, urmat de o revenire dup un interval de timp relativ scurt. Nivelul acestei perturbaii ce afecteaz negativ consumatorii este determinat att de procentul de reducere al tensiunii ct i de durat [5]. Consumatorii foarte importani ce nu suporta golurile de tensiune, materializate prin ntreruperea accidentala a furnizrii energiei electrice, sunt denumii consumatori vitali. Efectele produse de golurile de tensiune pot afecta sntatea uman, chiar i viaa, n cazul activitii n domeniul sanitar (spre exemplu aparatura slilor de operaie sau a centrelor de dializ), mediul nconjurtor n cazul echipamentelor de depoluare atmosferic i epurare a apei, confortul sau sigurana oamenilor n cazul slilor de conferin, de spectacole, etc. Pentru evitarea acestor efecte se alege soluia alimentrii consumatorilor vitali din alte surse disponibile, n cazul ntreruperii accidentale a alimentrii de baz. Aceste surse pot proveni din alte reele sau dintr-un grup electrogenerator propriu. Reelele electrice de rezerv pot prelua n ntregime puterea consumat. n cazul grupului electrogenerator, acesta dispune
de putere limitat i de aceea se va face o selecie a consumatorilor ce vor rmne cuplai la acesta, n funcie de importana consumatorilor. Alimentarea consumatorilor vitali din sursele de rezerv, n cazul ntreruperii accidentale a alimentrii de baz, se face cu ajutorul unui echipament AAR. Acesta asigur continuitatea alimentrii cu energie electric a consumatorilor ce nu suporta goluri de tensiune cu o durat mai mare de 23 secunde. n general, AAR este necesar pentru alimentarea cu energie electric: - n instalaii cu flux continuu i n diferite procese tehnologice; - n spitale sau instituii publice de interes naional unde continuitatea n funcionare este un factor vital; - n zonele n care exist probleme n alimentarea cu energie electric.
cu logic programat (se folosesc automate programabile i tehnici adecvate de programare; manevrele de anclanare a rezervei se fac dup o logic programat). Pentru ambele variante de implementare, sistemul de comand al AAR primete informaii despre starea dispozitivelor de protecie, despre starea contactelor auxiliare ale ntreruptorului circuitului de alimentare normal i despre starea tensiunii pe barele de alimentare i apoi, conform procedurilor din sistemul electroenergetic, comand corespunztor ntreruptoarele IA.
Fig. 1. Schema monofilar de principiu pentru AAR. n exemplul din figura 2 se prezint schema de principiu a unei instalaii AAR [6] ce alimenteaz barele staiei C prin linia principal L1, din staia A i linia de rezerv L2 din staia B.
Fig. 2. Schema electric monofilar de principiu a AAR pentru alimentarea unei staii de transformare.
Semnificaiile notaiilor din figura 2 sunt urmtoarele: Q1...Q4 ntreruptoare, BD bobina declanatorului, TT transformator de tensiune, F1, F2, F3 relee minimale de tensiune, K1T releu de timp cu temporizare la revenire, K2T releu de timp cu temporizare la acionare, K3 releu intermediar. n funcionarea normal alimentarea staiei C se face prin linia L1, ntreruptorul Q1 fiind nchis; deci releul intermediar cu temporizare K1T este acionat, datorit contactelor 1416, 18-20 ale ntreruptorului Q2, avnd cele dou contacte nchise. Dac valoarea tensiunii de la staia C este n domeniul admisibil, atunci releele minimale de tensiune F1 i F2, alimentate de la barele staiei C printr-un transformator de tensiune nereprezentat n schem, sunt acionate i au contactele deschise. Dac pe linia de rezerv L2 avem tensiune, atunci releul maximal de tensiune F3 (alimentat prin TT) este acionat i contactul su este nchis. Dac printr-un motiv oarecare se declaneaz ntreruptorul Q2, atunci contactele sale auxiliare 14-16 i 18-20 se deschid i contactul 11-13 se nchide. Astfel releul K1T rmne fr alimentare, dar prin contactul 11-13 al ntreruptorului Q2 contactul inferior cu temporizare la deschidere al releului K1T i contactul nchis 11-13 al ntreruptorului Q4 se alimenteaz bobina de anclanare BA a ntreruptorului Q4. Aceasta conduce la alimentarea staiei prin linia de rezerv L2. Anclanarea automat a rezervei are loc i n cazurile n care alimentarea de baz dispare, ca urmare a declanrii ntreruptorului Q1 a liniei L1, sau dac tensiunea la barele staiei C scade sub o valoarea admisibil. La dispariia sau scderea tensiunii la barele staiei C, releele minimale de tensiune F1 i F2 i nchid contactele i provoac prin contactul superior nchis al releului K1T i contactul nchis al releului F3 alimentarea releului de timp K2T, care dup timpul reglat comand prin releul intermediar K3 alimentarea bobinei de declanare BD a ntreruptorului Q2. Declanarea ntreruptorului Q2 determin n modul descris anterior anclanarea automat a ntreruptorului Q4 i deci alimentarea staiei C de la linia de rezerv.
SUR SA1
SU RSA2
G ENERATO R
Q1b
Q2b
Q1a
BARE"b" -F2.4 -F1.4 U< Spre consum atorii obisnuiti -F2.5 -F1.5 U<
Fig. 3. Schema monofilar de principiu pentru AAR n cazul unui spital. n cazul unei avarii la sursa 1 (de baz) sau pe linia de alimentare de la sursa 1 a barelor b, dispozitivul AAR va comanda anclanarea ntreruptorului Q2b, al sursei 2 (de rezerv), innd cont de condiia de declanare a ntreruptorului Q1b i de existena tensiunii la sursa 2. Tensiunea sursei 2 este supravegheat cu ajutorul releului F1.2. Odat cu declanarea sursei 1 se va comanda i pornirea grupului electrogen, care va trebui s i realizeze ciclul de pornire pentru a ajunge la parametrii nominali de funcionare. n cazul n care sursa 2 va fi conectat la sistemul de bare b i funcioneaz la parametrii normali, atunci se va comanda oprirea grupului electrogen. n situaia n care parametrii de funcionare ai sursei 2 nu corespund sau ntreruptorul Q2b al acesteia este indisponibil, atunci se va comanda anclanarea ntreruptorului Q1a al grupului electrogenerator, numai dup ndeplinirea urmtoarelor condiii: deschiderea cuplei Q0a i intrarea n regim normal de funcionare a generatorului (tensiunea se supravegheaz cu ajutorul releului F1.3.). Pentru funcionarea corect a AAR este necesar supravegherea tensiunii fazelor i succesiunea corect a acestora, pentru cele trei alimentari (sursa 1, sursa 2, generator), ct i pe cele dou sisteme de bare a i b, cu ajutorul F1.1, F1.2, F1.3, F1.4, F1.5. Logica de comand pentru AAR se implementeaz pe un automat programabil, folosind tehnici specifice de programare [7,8]. Principalele etape necesare a fi parcurse pentru realizarea AAR implementat cu automat programabil pentru un spital sunt urmtoarele: - se ntocmete caietul de sarcini al automatului secvenial pentru comanda instalaiei AAR sub forma GRACET sau reea Petri; - se codific etapele sau locaiile n cod distributiv; - se stabilesc ecuaiile logice pentru biii de stare; - se stabilesc ecuaiile logice pentru mrimile de ieire (comand); - se scrie programul de lucru al automatului programabil; - se ntocmete schema de conexiuni electrice pentru automatul programabil.
Bibliografie [1] *** Dicionar electrotehnic, http://www.instalatiielectrice.lx.ro/ie_h_glosara2.html [2] *** http://www.elewatt.ro/Instalatii-electrice/Agenda-tehnica/anclansarea-automata-arezervei-aar.html [3] Albu, M., M., Goluri de tensiune. Caracteristici, tehnici de monitorizare i definire a unui indice de calitate a serviciului de furnizare a energiei electrice., Revista Energetica, cod CNCSIS 512, categoria B, ISSN 1220-5133, februarie 2004. [4] Stoian, C., Clugru, t., Rusu, L., Ultrarpid device for automatic release of the spare, The 6th International Power Systems Conference, pp. 535-540. [5] *** http://stoianconstantin.wordpress.com/alimentarea-fara-intrerupere-a-consumatorilor [6] Popescu, L., Echipamente electrice, vol. II, Editura Alma Mater, Sibiu, 2008. [7] Cerchez, A., M., Dispozitiv de anclanare automat a rezervei realizat n tehnologie digital. [8] Popescu, D., Automate programabile. Construcie, funcionare, programare i aplicaii, Editura MATRIX ROM Bucureti, 2005, cod CNCSIS 39, ISBN 973-685-942-8.