ASPECTE SPECIFICE ANCLANRII AUTOMATE A REZERVEI PENTRU ALIMENTAREA CU ENERGIE ELECTRIC A UNUI SPITAL

POPESCU DANIEL Facultatea de Instalaii, U.T.C.B., dpopescu@instal.utcb.ro IANCU NICOLAE Facultatea de Instalaii, U.T.C.B., nicu1iancu@yahoo.com Abstract The article treats the problem of automatic operate of a reserve electricity power supply to a hospital (AAR), for uninterrupted supply of electricity to major consumers and has a number of specific issues related to design and implement of such an automated system for a hospital. It shows undesirable effects that may be supported by the consumer in case of accidental interruptions in power supply, or in other cases in which is negatively affected the continuity of supply of electricity. The article propose a concrete solution to achieve an automated system for AAR to a hospital. Control logic is implemented with existing programmable controllers, using specific programming techniques. Finally, the article presents a series of conclusions which recommends using programmable controllers in applications aimed uninterrupted electricity supply to consumers.

1. Anclanarea automat a rezervei necesitate pentru alimentarea nentrerupt cu energie electric a consumatorilor vitali
Anclanarea automat a rezervei (AAR) reprezint operaia de conectare rapid a consumatorilor electrici la un circuit de rezerv (linie electric sau transformator), n cazul cderii circuitului normal de alimentare, ca urmare a unui deranjament sau a unei deconectri impuse de ctre dispozitivele de protecie [1,2]. Operaia poate fi aplicat consumatorilor sensibili la goluri de tensiune [3] ce beneficiaz de dou sau mai multe alimentri cu energie electric din surse diferite. Impactul negativ al golurilor de tensiune asupra calitii energiei electrice furnizate consumatorilor este deosebit de important i depinde de tipul acestor goluri de tensiune ct i de curbele de acceptabilitate ale diferitelor clase de echipamente consumatoare de energie electric [4]. Golul de tensiune se definete ca o reducere brusc de tensiune, sub un nivel de prag, urmat de o revenire dup un interval de timp relativ scurt. Nivelul acestei perturbaii ce afecteaz negativ consumatorii este determinat att de procentul de reducere al tensiunii ct i de durat [5]. Consumatorii foarte importani ce nu suporta golurile de tensiune, materializate prin ntreruperea accidentala a furnizrii energiei electrice, sunt denumii consumatori vitali. Efectele produse de golurile de tensiune pot afecta sntatea uman, chiar i viaa, n cazul activitii n domeniul sanitar (spre exemplu aparatura slilor de operaie sau a centrelor de dializ), mediul nconjurtor n cazul echipamentelor de depoluare atmosferic i epurare a apei, confortul sau sigurana oamenilor n cazul slilor de conferin, de spectacole, etc. Pentru evitarea acestor efecte se alege soluia alimentrii consumatorilor vitali din alte surse disponibile, n cazul ntreruperii accidentale a alimentrii de baz. Aceste surse pot proveni din alte reele sau dintr-un grup electrogenerator propriu. Reelele electrice de rezerv pot prelua n ntregime puterea consumat. n cazul grupului electrogenerator, acesta dispune

de putere limitat i de aceea se va face o selecie a consumatorilor ce vor rmne cuplai la acesta, n funcie de importana consumatorilor. Alimentarea consumatorilor vitali din sursele de rezerv, n cazul ntreruperii accidentale a alimentrii de baz, se face cu ajutorul unui echipament AAR. Acesta asigur continuitatea alimentrii cu energie electric a consumatorilor ce nu suporta goluri de tensiune cu o durat mai mare de 23 secunde. n general, AAR este necesar pentru alimentarea cu energie electric: - n instalaii cu flux continuu i n diferite procese tehnologice; - n spitale sau instituii publice de interes naional unde continuitatea n funcionare este un factor vital; - n zonele n care exist probleme n alimentarea cu energie electric.

2. Tehnici de realizare a sistemelor pentru anclanarea automat a rezervei


Sistemele pentru anclanarea automat a rezervei asigur continuitatea n alimentarea cu energie electric. Acestea determin conectarea automat a alimentrii de rezerv n cazul deconectrii alimentrii normale, sau altfel spus realizeaz trecerea de pe alimentarea normal din reea pe o rezerv care poate s fie o alt reea sau un grup electrogenerator. Soluia cea mai ntlnit n prezent este AAR reversibil clasic, care folosete pentru comutarea ntre sursele de alimentare normale i de rezerv, un automat dedicat a crui funcie principal este supravegherea sursei normale i comutarea pe sursa de rezerv, att timp ct sursa normal nu este disponibil. Sistemele AAR actuale dispun uzual de dou sau trei ntreruptoare echipate cu protecie la scurtcircuit i suprasarcin, interblocaj electric i mecanic, contacte ON/OFF. Principalele caracteristici ale acestora sunt urmtoarele: asigur trecerea de pe sursa de baz pe cea de rezerv, ntr-un interval de timp reglabil ntre 0,1s i 30s, pentru ca ntreruperea s afecteze ct mai puin receptoarele; asigura protecia la scurtcircuit i suprasarcin a circuitelor din aval; nu permit nchiderea simultan a ntreruptoarelor chiar i n regim tranzitoriu; indic starea ntreruptoarelor dup declanarea datorat unui scurtcircuit; acioneaz numai dup deconectarea circuitului de alimentare normal; au o temporizare suficient, n special la tensiuni peste 110 kV, pentru asigurarea deionizrii spaiului n care sa produs arcul electric n cazul unui scurtcircuit; nu se permite repetarea anclanrii la defecte persistente. n exemplul din figura 1 se ilustreaz modul n care acioneaz AAR pe o schem electric monofilar. Se alimenteaz normal, separat, dou bare prin transformatoarele T1 i T2, sau se alimenteaz din sursa de rezerv, n comun, ambele bare prin transformatorul Tr. Fiecare bar este prevzut cu propriul sistem AAR care supravegheaz prezena tensiunii pe bar cu ajutorul transformatorului de tensiune TT. Dispariia tensiunii electrice pe una din bare sau pe ambele bare, determin o instalaie AAR sau ambele instalaii AAR s acioneze asupra ntreruptorului / ntreruptoarelor IA, n sensul deschiderii spre linia de alimentare normal i n sensul nchiderii spre linia de alimentare de rezerv. La ntreruperea alimentrii date de oricare din transformatoarele T1 sau T2 se conecteaz automat ntreruptorul transformatorului Tr. Implementarea sistemului de conducere al unui AAR se realizeaz n dou variante: - cu logic cablat folosind contacte i relee (se folosesc relee care comand ntreruptoarele automate);

cu logic programat (se folosesc automate programabile i tehnici adecvate de programare; manevrele de anclanare a rezervei se fac dup o logic programat). Pentru ambele variante de implementare, sistemul de comand al AAR primete informaii despre starea dispozitivelor de protecie, despre starea contactelor auxiliare ale ntreruptorului circuitului de alimentare normal i despre starea tensiunii pe barele de alimentare i apoi, conform procedurilor din sistemul electroenergetic, comand corespunztor ntreruptoarele IA.

Fig. 1. Schema monofilar de principiu pentru AAR. n exemplul din figura 2 se prezint schema de principiu a unei instalaii AAR [6] ce alimenteaz barele staiei C prin linia principal L1, din staia A i linia de rezerv L2 din staia B.

Fig. 2. Schema electric monofilar de principiu a AAR pentru alimentarea unei staii de transformare.

Semnificaiile notaiilor din figura 2 sunt urmtoarele: Q1...Q4 ntreruptoare, BD bobina declanatorului, TT transformator de tensiune, F1, F2, F3 relee minimale de tensiune, K1T releu de timp cu temporizare la revenire, K2T releu de timp cu temporizare la acionare, K3 releu intermediar. n funcionarea normal alimentarea staiei C se face prin linia L1, ntreruptorul Q1 fiind nchis; deci releul intermediar cu temporizare K1T este acionat, datorit contactelor 1416, 18-20 ale ntreruptorului Q2, avnd cele dou contacte nchise. Dac valoarea tensiunii de la staia C este n domeniul admisibil, atunci releele minimale de tensiune F1 i F2, alimentate de la barele staiei C printr-un transformator de tensiune nereprezentat n schem, sunt acionate i au contactele deschise. Dac pe linia de rezerv L2 avem tensiune, atunci releul maximal de tensiune F3 (alimentat prin TT) este acionat i contactul su este nchis. Dac printr-un motiv oarecare se declaneaz ntreruptorul Q2, atunci contactele sale auxiliare 14-16 i 18-20 se deschid i contactul 11-13 se nchide. Astfel releul K1T rmne fr alimentare, dar prin contactul 11-13 al ntreruptorului Q2 contactul inferior cu temporizare la deschidere al releului K1T i contactul nchis 11-13 al ntreruptorului Q4 se alimenteaz bobina de anclanare BA a ntreruptorului Q4. Aceasta conduce la alimentarea staiei prin linia de rezerv L2. Anclanarea automat a rezervei are loc i n cazurile n care alimentarea de baz dispare, ca urmare a declanrii ntreruptorului Q1 a liniei L1, sau dac tensiunea la barele staiei C scade sub o valoarea admisibil. La dispariia sau scderea tensiunii la barele staiei C, releele minimale de tensiune F1 i F2 i nchid contactele i provoac prin contactul superior nchis al releului K1T i contactul nchis al releului F3 alimentarea releului de timp K2T, care dup timpul reglat comand prin releul intermediar K3 alimentarea bobinei de declanare BD a ntreruptorului Q2. Declanarea ntreruptorului Q2 determin n modul descris anterior anclanarea automat a ntreruptorului Q4 i deci alimentarea staiei C de la linia de rezerv.

3. Sistem automat pentru anclanarea automat a rezervei n cazul unui spital


Pentru consumatorii vitali, cum ar fi spitalele, se impune existena unei a treia surse de alimentare, pentru situaii n care din motive neprevzute nici cea de a doua alimentare considerat de rezerv nu este funcional. Cea de-a treia surs de alimentare cu energie electric este de obicei un grup electrogenerator, care n funcie de puterea sa poate prelua numai o anumit parte din consumul total. Soluia concret de realizare a unui sistem automat pentru AAR la un spital, prezentat n acest articol, se bazeaz pe schema electric monofilar adoptat pentru alimentarea cu energie electrica prezentat n figura 3. Rapiditatea funcionrii AAR depinde de timpii de reacie proprii ntreruptoarelor Q1a, Q1b, Q2b amplasai pe cele trei alimentari i de timpul de intrare n parametrii nominali de funcionare ai grupului electrogennerator. Funcionarea AAR pentru un spital, conform schemei din figura 3, se prezint n continuare.

SUR SA1

SU RSA2

G ENERATO R

Q1b

-F2.1 -F1.1 U>

Q2b

-F2.2 -F1.2 U> Q0a

Q1a

-F2.3 -F1.3 U> BARE"a"

BARE"b" -F2.4 -F1.4 U< Spre consum atorii obisnuiti -F2.5 -F1.5 U<

Spre consum atorii vitali

Fig. 3. Schema monofilar de principiu pentru AAR n cazul unui spital. n cazul unei avarii la sursa 1 (de baz) sau pe linia de alimentare de la sursa 1 a barelor b, dispozitivul AAR va comanda anclanarea ntreruptorului Q2b, al sursei 2 (de rezerv), innd cont de condiia de declanare a ntreruptorului Q1b i de existena tensiunii la sursa 2. Tensiunea sursei 2 este supravegheat cu ajutorul releului F1.2. Odat cu declanarea sursei 1 se va comanda i pornirea grupului electrogen, care va trebui s i realizeze ciclul de pornire pentru a ajunge la parametrii nominali de funcionare. n cazul n care sursa 2 va fi conectat la sistemul de bare b i funcioneaz la parametrii normali, atunci se va comanda oprirea grupului electrogen. n situaia n care parametrii de funcionare ai sursei 2 nu corespund sau ntreruptorul Q2b al acesteia este indisponibil, atunci se va comanda anclanarea ntreruptorului Q1a al grupului electrogenerator, numai dup ndeplinirea urmtoarelor condiii: deschiderea cuplei Q0a i intrarea n regim normal de funcionare a generatorului (tensiunea se supravegheaz cu ajutorul releului F1.3.). Pentru funcionarea corect a AAR este necesar supravegherea tensiunii fazelor i succesiunea corect a acestora, pentru cele trei alimentari (sursa 1, sursa 2, generator), ct i pe cele dou sisteme de bare a i b, cu ajutorul F1.1, F1.2, F1.3, F1.4, F1.5. Logica de comand pentru AAR se implementeaz pe un automat programabil, folosind tehnici specifice de programare [7,8]. Principalele etape necesare a fi parcurse pentru realizarea AAR implementat cu automat programabil pentru un spital sunt urmtoarele: - se ntocmete caietul de sarcini al automatului secvenial pentru comanda instalaiei AAR sub forma GRACET sau reea Petri; - se codific etapele sau locaiile n cod distributiv; - se stabilesc ecuaiile logice pentru biii de stare; - se stabilesc ecuaiile logice pentru mrimile de ieire (comand); - se scrie programul de lucru al automatului programabil; - se ntocmete schema de conexiuni electrice pentru automatul programabil.

4. Concluzii privind utilizarea automatelor programabile n sistemele de anclanare automat a rezervei


Scopul realizrii AAR este acela de a asigura continuitatea n alimentarea cu energie electric a consumatorilor vitali sau a consumatorilor care au o anumit importan. Sistemele de AAR pot fi diversificate astfel nct s rspund la diferite situaii practice: 24 linii de alimentare, cuple ntre barele de alimentare i grupuri electrogene. Comanda configuraiilor atipice de AAR se recomand a fi realizate cu automat programabil i cu interfa alfanumeric pentru setarea unor parametri i pentru diagnoza sistemului. Utilizarea logicii programate ofer o palet larg de posibiliti privind cerinele de funcionare ale sistemului n functie de cerinele impuse. Principalele avantaje ale implementrii sistemelor de comand pentru AAR cu automate programabile sunt urmtoarele: - reducerea numrului de componente i a numrului de conexiuni necesare realizrii AAR; - reducerea la minim a numrului de dispozitive electrice cu comutaie dinamic prin folosirea dispozitivelor cu comutaie static; - creterea fiabilitii instalaiei AAR; - automatul programabil poate rula programul de lucru independent de calculator;

Bibliografie [1] *** Dicionar electrotehnic, http://www.instalatiielectrice.lx.ro/ie_h_glosara2.html [2] *** http://www.elewatt.ro/Instalatii-electrice/Agenda-tehnica/anclansarea-automata-arezervei-aar.html [3] Albu, M., M., Goluri de tensiune. Caracteristici, tehnici de monitorizare i definire a unui indice de calitate a serviciului de furnizare a energiei electrice., Revista Energetica, cod CNCSIS 512, categoria B, ISSN 1220-5133, februarie 2004. [4] Stoian, C., Clugru, t., Rusu, L., Ultrarpid device for automatic release of the spare, The 6th International Power Systems Conference, pp. 535-540. [5] *** http://stoianconstantin.wordpress.com/alimentarea-fara-intrerupere-a-consumatorilor [6] Popescu, L., Echipamente electrice, vol. II, Editura Alma Mater, Sibiu, 2008. [7] Cerchez, A., M., Dispozitiv de anclanare automat a rezervei realizat n tehnologie digital. [8] Popescu, D., Automate programabile. Construcie, funcionare, programare i aplicaii, Editura MATRIX ROM Bucureti, 2005, cod CNCSIS 39, ISBN 973-685-942-8.