CALCULUL HIDRAULIC AL CONDUCTELOR

STABILIREA DIAMETRELOR CONDUCTELOR


Numarul si felul
Nr.Tronson E1 E
armaturii
1.1 1B 1 1
1.2 1L+1B 1.35 1.35
1.3 1L+1B+1S 2.35 2.35
1.4 2L+2B+2S 4.7 4.7
1.5 6L+2B+4S 8.1 8.1

Tronson Robinet cu ventil


1.1 0
1.2 0
1.3 10
1.4 0
1.5 8
AL CONDUCTELOR DE DISTRIBUTIE A APEI CALDE LA INTERIOR PENTRU CON
LOR CONDUCTELOR CALCULUL HIDRAULIC
i*l hrl
Gc [l/s] d [mm] V [m/s] i [mmH2O] l [m] Ʃ i*l Ʃζ [-]
[mmH20] [mmH2O]
0.15 20 0.70 50.00 0.50 25 25 2.6 64.93
0.20 25 0.65 30 0.50 15 40 0.5 10.77
0.37 25 0.70 35 2.60 91 131 12.1 302.19
0.52 32 0.60 20 23.40 468 599 3.5 64.22
0.68 32 0.8 32 5 160 759 10.4 339.245668

Teuri Cot Reducții Ʃζ


0.5 2 0.1 2.6
0.5 0 0 0.5
0.5 1.5 0.1 12.1
0.5 3 0 3.5
0 2.4 0 10.4
TERIOR PENTRU CONSUM MENAJER
CALCULUL HIDRAULIC
Hg Hnec
Ʃhrl [mmH2O] hr [mmH2O] Hu [mmH2O]
[mmH2O] [mmH2O]
14.98 39.98 4000 3000 7039.98
25.75 65.75 4000 3000 7065.75
327.94 458.94 4000 3000 7458.94
392.16 991.16 4000 3000 7991.16
731.40 1490.40 4000 3000 8490.40