Abstract
This paper presents the digital optimization of burning in the combustion heater. Combustion heater’
means a device directly using liquid or gaseous fuel and not use the waste heat from the engine used for
propulsion of the vehicle. The combustion heater works on caloric power degrees. The combustion air feeds
and the fuel feeds associated with the power degrees are memorized by the microcontroler of the electronic
control. The values of the combustion air feeds and the fuel feeds are optimized on a stand test with flue-gas
analysing apparatus for low exhaust emissions resulted from the combustion heater.
221
ANNALS of the ORADEA UNIVERSITY.
Fascicle of Management and Technological Engineering, Volume VI (XVI), 2007
Figure 1
222
ANNALS of the ORADEA UNIVERSITY.
Fascicle of Management and Technological Engineering, Volume VI (XVI), 2007
2.2.PRINCIPIUL DE DE FUNCŢIONARE
Iniţierea arderii se realizează prin preîncălzirea bujiei cu cep incandescent (poz. 12) la
o temperatură de 850÷900°C, se comandă pompa de combustibil electromagnetică, în
impulsuri (poz. 31) la o frecventă programată, motorina ajunge in arzător (poz. 10,15)
unde in prezenţa aerului de ardere furnizat de suflantă (poz.8), prin orificiile dispuse pe
tubul de ardere (poz.15), are loc aprinderea si arderea amestecului carburant. La
stabilizarea arderii sesizorul de temperatură (poz.16) comandă deconectarea bujiei,
arzătorul intrând in funcţionare stabilizată. (Figura1)
Figure 2
223
ANNALS of the ORADEA UNIVERSITY.
Fascicle of Management and Technological Engineering, Volume VI (XVI), 2007
*
dA p
dA 5
dA 4
dA 3
dA 2
dA 1
dC p
dC 5
dC 4
dC 3
dC 2
dC 1
B ujie
T (s)
ST A R T ST O P ST A R T
1… 3s
tA E
T Pb
T A P **
Figure 1
SF –sesizor flacără
dCx-trepte de funcţionare ale pompei de combustibil
dAx- trepte de funcţionare ale suflantei de aer
* interval posibil de decuplare a bujiei şi trecere la funcţionarea pe trepte;
** TAp reprezintă intervalul maxim prescris pentru secvenţa de pornire(<4 min.) [2]
TPb-timp preîncălzire bujie
TAE-timp de ventilare
224
ANNALS of the ORADEA UNIVERSITY.
Fascicle of Management and Technological Engineering, Volume VI (XVI), 2007
Table 2
Nr. Tensiune Debit aer Debit de CO Nox Exces Turaţie Temp.
crt. de de ardere combustibil [ppm] [ppm] de aer suflantă gaze
încercare dAx DCx λ [rot/min] arse
[V] [%] [Hz] [°C]
225
ANNALS of the ORADEA UNIVERSITY.
Fascicle of Management and Technological Engineering, Volume VI (XVI), 2007
5.CONCLUZII
Optimizarea digitală a arderii in generatorul de aer cald tip A20 permite încadrarea
operativă a arderii in limitele admisibile a noxelor din gazele de ardere, asigurându-se
funcţionarea corectă şi de durată a arzătorului instalaţiei. Posibilitatea de modificare facilă
a parametrilor de lucru permite compensarea abaterilor de executie a arzatorului, a
abaterilor de la turatia nominala a motorului electric si de la debitul nominal a pompei de
motorină.
Din valorile înregistrate in tabelul 2 se confirmă reducerea concentratiei de Nox cu
cresterea excesului de aer ardere şi reducerea concentraţiei de CO cu creşterea
temperaturii gazelor arse. Se mai constată un optim de ardere in vecinătatea tensiunii
nominale de funcţionare. Se admite un nivel mai mare de CO la tensiune maximă (λ mare-
ultimul rând din tabelul 2) deoarece prin calaminarea suprafeţelor de schimb termic acesta
se va reduce in timp (λ scade) crescând durata de bună funcţionare a arzătorului.
Bibliografie