Setri generale (pt. toate camerele) : Zona eoliana IV RADIATOARE K E R M I RAD IATOAR E DUNAFERR RAD IATOAR E FERROLI Aveti mai jos, pt. fiecare camera, o serie de marimi si valorile lor, conform SR 1907, asa cum le utilizeaza si acest program. O parte provin din pag. Culise, o parte sint rezultatul unor formule de calcul, iar o alta parte sint constante Valabilitate: 1-apr-16
ce pot fi introduse de operator. Toate celulele de mai jos sint NEprotejate la scriere, asa ca atentie sa nu stergeti din greseala vreo formula. Cei care au cunostinte in domeniu isi pot adapta si mai bine calculele la experienta si
C TUR 55 Zona IV nafara localit. 4.0 tip C11 tip C22 tip C33 Alegerea
tip C11 tip C22 tip C33 Alegerea
tip C11 tip C22 tip C33 Alegerea
nevoile lor, ca si in pagina Culise. Iar cei care se pricep mai putin, aveti grija ce date introduceti aici ! Modificati DOAR daca : 1. sinteti sigur pe ceea ce faceti, sau 2. doriti doar sa vedeti cum afecteaza modificarea unei valori 1-apr-18
rezultatul final, dupa care dati un "UNDO" = Ctrl+Z.
C RETUR 45 climatic -21 7 1.00 L(mm) # watt pret L(mm) # watt pret L(mm) # watt pret finala L(mm) # watt pret L(mm) # watt pret L(mm) # watt pret finala L(mm) # watt pret L(mm) # watt pret L(mm) # watt pret finala 43191
### ###
Caracteristici pentru fiecare camer: Alege radiatorul Alege radiatorul Alege radiatorul supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
1 Camera 1 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
1 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 3.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 198.354 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
2 Camera 2 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
2 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
3 Camera 3 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
3 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
4 Camera 4 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
4 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
5 Camera 5 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
5 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
6 Camera 6 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
6 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
7 Camera 7 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 ### Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
7 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
8 Camera 8 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
8 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
9 Camera 9 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
9 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
10 Camera 10 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
10 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
11 Camera 11 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
11 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D
supraf. per. Ext. col. C 0.00 supraf. per. Ext. col. D 0.00 supraf. tavan 0.00 m per. Ext 1.038 Rm 0.60 Rp 5.87 Abc 0.00 V-Vol. Cam.
12 Camera 12 2.50 0.00 M 20 M tip C 0 600 tip C22 tip C 0 600 tip C22 tip C 0 600 tip C22 Rc per. Ext. col. C Rc per. Ext. col. D Rc tavan m per. Int 1.000 AT 0.00 Ap 0.00 nao 0.00028 QT 0
0.00
12 + / - suprafata 2.50 0.00 T1 Est - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - W per. Ext. col. C 0.00 W per. Ext. col. D 0.00 W tavan 0.00 m tavan 1.038 R bc 0.574 mediu sol 1.50 aer 1.20 QT*adaosuri 0
supraf. vitrate 0.00 0.00 0.00 T. Bun 20 T. Bun - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - supraf. per. Int. col. C 0.00 supraf. per. Int. col. D 0.00 Rc podea m podea 1.00 ms 0.48 A usi ext. Cp 1,011 QT*ad.+Qi 0
pereti exter. 0.0% 0.00 -21 P7 -21 ### ### ### ### ### ### ### ### ### Rc per. Int. col. C Rc per. Int. col. D W podea 0.00 m geam 1.20 ns 1.20 n-nr. desch. Qi1 0 QS 0 ###
pereti inter.
0 20 20 20 W per. Int. col. C 0.00 W per. Int. col. D 0.00 Ao 0.00 L geam 0.00 V 3/4 6.350 Qu 0 Qi2 0 ###
0 W geam col. C 0.00 W geam col. D 0.00 Ac 16.20 i geam 0.050 Adaosuri 1.162 Rc geam C Rc geam D ###
DUNAFERR
75 90 Inaltime: 300
65 70 Tip: 11 22
20 20 WATT PRET WATT PRET
lungime Temp.C 75/65 90/70 tip V tip C 75/65 90/70 tip V
400 200C 226 286 402 510
500 20 C
0
282 358 503 638
600 200C 339 429 604 765
700 200C 395 501 704 893
800 200C 452 572 805 1,020
900 200C 508 644 905 1,148
1,000 200C 565 716 1,006 1,275
1,100 200C 621 787 1,107 1,403
1,200 200C 677 859 1,207 1,530
1,300 200C 734 930 1,308 1,658
1,400 200C 790 1,002 1,408 1,785
1,500 200C 847 1,073 1,509 1,913
1,600 200C 903 1,145 1,610 2,040
1,700 200C 960 1,216 1,710 2,168
1,800 200C 1,016 1,288 1,811 2,295
1,900 200C 1,073 1,359 1,911 2,423
2,000 200C 1,129 1,431 2,012 2,550
2,200 200C 1,242 1,574 2,213 2,805
2,400 200C 1,355 1,717 2,414 3,060
2,600 200C 1,468 1,860 2,615 3,315
2,800 200C 1,581 2,003 2,817 3,570
3,000 200C 1,694 2,147 3,018 3,825
FERROLI
75 90 Inaltime: 300
65 70 Tip: 11 22
20 20 WATT PRET WATT PRET
lungime Temp.C 75/65 90/70 tip V tip C 75/65 90/70 tip V
300 20 C
0
157 199 289 365
400 200C 210 265 385 487
500 200C 262 332 481 609
600 200C 314 398 577 731
700 200C 367 464 673 852
800 200C 419 531 769 974
900 200C 472 597 866 1,096
1,000 200C 524 663 962 1,218
1,100 200C 576 730 1,058 1,339
1,200 200C 629 796 1,154 1,461
1,300 200C 681 862 1,250 1,583
1,400 200C 733 928 1,346 1,705
1,500 200C 786 995 1,443 1,826
1,600 200C 838 1,061 1,539 1,948
1,800 200C 943 1,194 1,731 2,192
2,000 200C 1,048 1,326 1,924 2,435
2,200 200C 1,153 1,459 2,116 2,679
2,400 200C 1,257 1,592 2,308 2,922
2,600 200C 1,362 1,724 2,501 3,166
2,800 200C 1,467 1,857 2,693 3,409
3,000 200C 1,572 1,990 2,885 3,653
K E R M I K E R M I
300
22 33 Tip: 11
PRET WATT PRET WATT PRET
tip C 70/55 90/70 tip V tip C 70/55 90/70 tip V tip C
34.20 444 693 75.90 59.10 226 347 38.40 21.80
38.10 555 866 82.00 65.10 283 433 41.40 24.90
41.90 666 1,039 88.10 71.00 339 520 44.50 28.10
45.70 778 1,212 94.63 77.00 396 607 47.50 31.30
49.50 889 1,386 100.40 82.90 452 694 50.60 34.50
53.40 1,000 1,559 106.50 88.90 509 780 53.60 37.70
57.20 1,111 1,732 112.70 94.90 565 867 56.70 40.90
61.00 1,222 1,905 118.80 100.80 622 954 59.70 44.10
64.80 1,333 2,078 124.90 106.80 678 1,040 62.80 47.20
68.70 1,444 2,251 131.10 112.70 735 1,127 65.80 50.40
72.50 1,555 2,425 137.20 118.70 791 1,214 68.90 53.60
80.10 1,777 2,771 149.50 130.60 904 1,387 75.00 60.00
87.80 1,999 3,117 161.70 142.50 1,017 1,560 81.10 66.40
95.40 2,222 3,464 174.00 154.40 1,130 1,734 87.20 72.80
106.90 2,555 3,983 192.40 172.30 1,300 1,994 96.40 82.30
118.40 2,888 4,503 210.80 190.20 1,469 2,254 105.50 91.90
133.70 3,332 5,196 235.40 214.00 1,695 2,601 117.70 104.60
DUNAFERR DUNAFERR
300
22 33 Tip: 11
PRET WATT PRET WATT PRET
tip C 75/65 90/70 tip V tip C 75/65 90/70 tip V tip C
127.84 557 706 171.07
146.69 696 882 199.78
165.15 835 1,058 228.23
183.46 974 1,235 256.40
190.25 1,113 1,411 266.73
207.45 1,253 1,588 293.31
223.76 1,392 1,764 318.30
242.96 1,531 1,940 348.20
260.01 1,670 2,117 374.65
265.20 1,809 2,293 382.85
281.99 1,948 2,470 408.96
297.24 2,088 2,646 432.47
314.83 2,227 2,822 459.72
2,366 2,999
340.55 2,505 3,175 499.63
2,644 3,352
372.12 2,784 3,528 548.52
403.63 3,062 3,881 597.28
435.34 3,340 4,234 646.72
456.66 3,619 4,586 679.76
487.04 3,897 4,939 726.79
516.41 4,175 5,292 772.22
FERROLI FERROLI
300
22 33 Tip: 11
PRET WATT PRET WATT PRET
tip C 75/65 90/70 tip V tip C 75/65 90/70 tip V tip C
394 499 198 251
525 665 265 335
656 832 331 419
788 998 397 502
919 1,164 463 585
1,050 1,330 529 670
1,182 1,497 595 754
1,313 1,663 661 836
1,444 1,829 727 921
1,576 1,996 794 1,005
1,707 2,162 860 1,089
1,838 2,328 929 1,172
1,969 2,495 992 1,256
2,101 2,661 1,058 1,339
2,363 2,994 1,190 1,507
2,626 3,326 1,323 1,675
2,888 3,659 1,455 1,842
3,151 3,991 1,587 2,010
3,414 4,324 1,719 2,177
3,676 4,657 1,852 2,345
3,939 4,989 1,984 2,512
0 0
K E R M I K E R M I
400
22 33 Tip:
WATT PRET WATT PRET WATT
70/55 90/70 tip V tip C 70/55 90/70 tip V tip C 70/55
388 605 58.10 39.10 561 876 80.30 63.90 272
486 757 63.10 43.10 701 1,095 87.50 70.90 339
583 908 68.10 47.10 841 1,314 94.70 78.00 407
680 1,059 73.10 51.10 981 1,533 102.00 85.00 475
777 1,211 78.10 55.20 1,121 1,752 109.20 92.00 543
874 1,362 83.10 59.20 1,261 1,971 116.40 99.00 611
971 1,513 88.10 63.20 1,401 2,190 123.70 106.00 679
1,068 1,665 93.10 67.20 1,541 2,408 130.90 113.10 747
1,165 1,816 98.20 71.30 1,682 2,627 138.20 120.10 815
1,262 1,967 103.20 75.30 1,822 2,846 145.40 127.10 883
1,359 2,119 108.20 79.30 1,962 3,065 152.60 134.10 951
1,554 2,421 118.20 87.40 2,242 3,503 167.10 148.10 1,086
1,748 2,724 128.20 95.40 2,522 3,941 181.60 162.20 1,222
1,942 3,027 138.20 103.50 2,803 4,379 196.00 176.20 1,358
2,233 3,481 153.20 115.60 3,223 5,036 217.80 197.30 1,562
2,525 3,935 168.20 127.70 3,643 5,693 239.50 218.30 1,765
2,913 4,540 188.20 143.80 4,204 6,569 268.40 246.40 2,037
DUNAFERR DUNAFERR
400
22 33 Tip:
WATT PRET WATT PRET WATT
75/65 90/70 tip V tip C 75/65 90/70 tip V tip C 75/65
344
430
516
602
688
774
860
945
1,031
1,117
1,203
1,289
1,375
1,461
1,547
1,633
1,719
1,891
2,063
2,235
2,407
2,579
FERROLI FERROLI
400
22 33 Tip:
WATT PRET WATT PRET WATT
75/65 90/70 tip V tip C 75/65 90/70 tip V tip C 75/65
368 467 497 631 238
490 623 663 841 317
613 778 829 1,051 396
736 934 994 1,261 476
858 1,090 1,160 1,472 555
981 1,245 1,326 1,682 634
1,103 1,401 1,492 1,892 714
1,226 1,557 1,657 2,102 793
1,349 1,712 1,823 2,312 872
1,471 1,868 1,989 2,523 951
1,594 2,024 2,154 2,733 1,031
1,716 2,179 2,320 2,943 111
1,839 2,335 2,486 3,153 1,189
1,962 2,491 2,652 3,364 1,269
2,207 2,802 2,983 3,784 1,427
2,452 3,113 3,315 4,204 1,586
2,697 3,425 3,646 4,625 1,744
2,942 3,736 3,977 5,045 1,903
3,188 4,048 4,309 5,466 2,062
3,433 4,359 4,640 5,886 2,220
3,678 4,670 4,972 6,307 2,379
M I K E R M I
500
11 22 33
WATT PRET WATT PRET WATT
90/70 tip V tip C 70/55 90/70 tip V tip C 70/55 90/70
419 42.30 24.50 463 723 58.60 38.80 668 1,046
524 45.80 28.00 579 904 63.80 43.30 835 1,308
629 49.30 31.50 695 1,085 68.90 47.90 1,002 1,569
734 52.80 35.10 811 1,266 74.10 52.50 1,169 1,831
838 56.30 38.60 927 1,447 79.30 57.10 1,336 2,092
943 59.80 42.10 1,042 1,628 84.50 61.70 1,503 2,354
1,048 63.30 45.60 1,158 1,808 89.70 66.20 1,670 2,615
1,153 66.80 49.20 1,274 1,989 94.90 70.80 1,837 2,877
1,258 70.30 52.70 1,390 2,170 100.10 75.40 2,004 3,139
1,362 73.80 56.20 1,506 2,351 105.30 80.00 2,171 3,400
1,467 77.20 59.70 1,622 2,532 110.50 84.60 2,338 3,662
1,677 84.20 66.80 1,853 2,894 120.90 93.70 2,672 4,185
1,886 91.20 73.80 2,085 3,255 131.20 102.90 3,007 4,708
2,096 98.20 80.90 2,316 3,617 141.60 112.00 3,341 5,231
2,410 108.70 91.40 2,664 4,159 157.20 125.80 3,842 6,016
2,725 119.10 102.00 3,011 4,702 172.80 139.50 4,343 6,800
3,144 133.10 116.10 3,475 5,425 193.50 157.80 5,011 7,846
RR DUNAFERR
500
11 22 33
WATT PRET WATT PRET WATT
90/70 tip V tip C 75/65 90/70 tip V tip C 75/65 90/70
436 618 784 149.43 849 1,076
545 773 980 175.06 1,062 1,346
654 927 1,176 200.65 1,274 1,615
763 1,082 1,371 226.23 1,486 1,884
872 1,237 1,567 238.22 1,699 2,153
980 1,391 1,763 262.07 1,911 2,422
1,089 1,546 1,959 285.98 2,123 2,691
1,198 1,700 2,155 309.90 2,335 2,960
1,307 1,855 2,351 333.68 2,548 3,229
1,416 2,009 2,547 343.14 2,760 3,498
1,525 2,164 2,743 365.92 2,972 3,767
1,634 2,319 2,939 388.71 3,185 4,037
1,743 2,473 3,135 411.49 3,397 4,306
1,852 2,628 3,331 3,609 4,575
1,961 2,782 3,527 447.66 3,822 4,844
2,070 2,937 3,722 4,034 5,113
2,179 3,091 3,918 492.24 4,246 5,382
2,397 3,401 4,310 536.73 4,671 5,920
2,615 3,710 4,702 581.16 5,096 6,458
2,832 4,019 5,094 616.07 5,520 6,997
3,050 4,328 5,486 659.84 5,945 7,535
3,268 4,637 5,878 703.60 6,369 8,073
LI FERROLI
500
11 22 33
WATT PRET WATT PRET WATT
90/70 tip V tip C 75/65 90/70 tip V tip C 75/65 90/70
301 442 561 596 757
402 589 748 795 1,010
502 737 935 993 1,262
603 884 1,122 1,192 1,514
703 1,031 1,309 1,391 1,767
804 1,178 1,496 1,590 2,019
904 1,326 1,683 1,788 2,272
1,005 1,473 1,870 1,987 2,524
1,105 1,620 2,057 2,186 2,776
1,205 1,768 2,244 2,384 3,029
1,306 1,915 2,431 2,583 3,281
1,406 2,062 2,619 2,782 3,534
1,507 2,210 2,806 2,980 3,786
1,607 2,357 2,993 3,179 4,038
1,808 2,651 3,367 3,577 4,543
2,009 2,496 3,741 3,974 5,048
2,110 3,241 4,115 4,371 5,553
2,411 3,535 4,489 4,769 6,058
2,612 3,830 4,863 5,166 6,562
2,816 4,124 5,237 5,563 7,067
3,014 4,419 5,611 5,961 7,572
K E R M I K E R
600
33 Tip: 11 22
PRET WATT PRET WATT PRET
tip V tip C 70/55 90/70 tip V tip C 70/55 90/70 tip V
81.00 65.30 316 490 44.00 27.00 535 837 61.40
88.60 73.20 395 613 47.70 30.80 669 1,046 66.90
96.20 81.10 473 735 51.40 34.60 803 1,256 72.40
103.80 89.00 552 858 55.10 38.40 937 1,465 77.90
111.40 96.90 631 980 58.80 42.20 1,070 1,674 83.40
118.90 104.80 710 1,103 62.40 46.00 1,204 1,883 88.90
126.50 112.70 789 1,225 66.10 49.80 1,338 2,093 94.40
134.10 120.70 868 1,348 69.80 53.60 1,472 2,302 99.90
141.70 128.60 947 1,470 73.50 57.40 1,606 2,511 105.40
149.30 136.50 1,026 1,593 77.20 61.20 1,739 2,721 110.90
156.80 144.40 1,105 1,715 80.80 65.00 1,873 2,930 116.50
172.00 160.20 1,262 1,960 88.20 72.60 2,141 3,348 127.50
187.20 176.10 1,420 2,205 95.60 80.20 2,408 3,767 138.50
202.30 191.90 1,578 2,450 102.90 87.90 2,676 4,185 149.50
225.10 215.60 1,815 2,818 114.00 99.30 3,077 4,813 166.00
247.80 239.40 2,051 3,186 125.00 110.70 3,479 5,441 182.50
278.10 271.00 2,367 3,676 139.70 125.90 4,014 6,278 204.50
DUNAFERR DUNA
600
33 Tip: 11 22
PRET WATT PRET WATT PRET
tip V tip C 75/65 90/70 tip V tip C 75/65 90/70 tip V
206.24 401 508 110.65 742 940
246.02 501 635 127.17 927 1,176
285.92 601 762 143.69 1,113 1,411
325.69 702 889 160.21 1,298 1,646
344.21 802 1,016 169.80 1,484 1,881
381.38 902 1,143 185.46 1,669 2,116
418.55 1,002 1,270 201.11 1,855 2,351
455.65 1,103 1,398 2,040 2,586
492.77 1,203 1,525 232.40 2,226 2,821
507.35 1,303 1,652 2,411 3,056
542.86 1,403 1,779 2,597 3,291
578.23 1,504 1,906 2,782 3,527
613.61 1,604 2,033 288.11 2,968 3,762
1,704 2,160 3,153 3,997
669.90 1,804 2,287 3,339 4,232
1,905 2,414 3,524 4,467
739.11 2,005 2,541 344.45 3,710 4,702
808.32 2,205 2,795 4,081 5,172
877.54 2,406 3,049 4,452 5,642
931.70 2,606 3,303 4,823 6,113
999.78 2,807 3,557 5,194 6,583
1067.80 3,007 3,811 5,565 7,053
FERROLI FERR
600
33 Tip: 11 22
PRET WATT PRET WATT PRET
tip V tip C 75/65 90/70 tip V tip C 75/65 90/70 tip V
276 349 506 643
368 466 675 857
460 582 844 1,071
551 699 1,012 1,285
643 815 1,181 1,499
735 932 1,350 1,714
827 1,048 1,518 1,928
919 1,165 1,687 2,142
1,011 1,281 1,856 2,356
1,103 1,398 2,024 2,571
1,195 1,514 2,193 2,785
1,287 1,631 2,362 2,999
1,379 1,747 2,531 3,213
1,470 1,864 2,699 3,427
1,654 2,097 3,037 3,856
1,838 2,330 3,374 4,284
2,022 2,563 3,711 4,713
2,206 2,796 4,049 5,141
2,389 3,028 4,386 5,569
2,573 3,261 4,724 5,998
2,757 3,494 5,061 6,426
K E R M I K E R M I
00
22 33 Tip: 11
PRET WATT PRET WATT PRET
tip C 70/55 90/70 tip V tip C 70/55 90/70 tip V tip C
40.70 768 1,205 83.20 66.70 446 700 51.00 33.80
45.90 960 1,506 91.40 75.10 557 875 56.20 39.20
51.00 1,152 1,807 99.70 83.60 668 1,050 61.50 44.60
56.10 1,344 2,108 107.90 92.10 780 1,225 66.70 50.00
61.20 1,536 2,410 116.10 100.50 891 1,400 72.00 55.50
66.40 1,728 2,711 124.30 109.00 1,003 1,575 77.20 60.90
71.50 1,920 3,012 132.50 117.50 1,114 1,750 82.50 66.30
76.70 2,112 3,313 140.70 126.00 1,226 1,924 87.70 71.70
81.80 2,303 3,615 148.90 134.40 1,337 2,099 93.00 77.20
86.90 2,495 3,916 157.10 142.90 1,448 2,274 98.20 82.60
92.10 2,687 4,217 165.30 151.40 1,560 2,449 103.50 88.00
102.30 3,071 4,819 181.80 168.30 1,783 2,799 114.00 98.90
112.60 3,455 5,422 198.20 185.30 2,005 3,149 124.50 109.70
122.90 3,839 6,024 214.60 202.20 2,228 3,499 135.00 120.60
138.30 4,415 6,928 239.20 227.60 2,562 4,024 150.80 136.90
153.70 4,991 7,831 263.90 253.10 2,897 4,549 166.50 153.10
174.20 5,759 9,036 296.70 287.00 3,342 5,249 187.60 174.80
DUNAFERR DUNAFERR
00
22 33 Tip: 11
PRET WATT PRET WATT PRET
tip C 75/65 90/70 tip V tip C 75/65 90/70 tip V tip C
139.20 976 1,237 61.14 210.11 562 712
172.80 1,220 1,547 74.02 251.54 702 890
187.05 1,464 1,856 292.91 843 1,068
224.16 1,708 2,165 334.35 983 1,246
230.55 1,952 2,474 362.20 1,124 1,424
266.07 2,196 2,784 402.03 1,264 1,602
278.40 2,440 3,093 441.73 1,405 1,780
315.30 2,684 3,402 481.38 1,545 1,958
317.55 2,928 3,712 521.14 1,686 2,137
351.00 3,172 4,021 538.93 1,826 2,315
374.58 3,416 4,330 576.96 1,967 2,493
398.16 3,660 4,640 615.07 2,107 2,671
421.75 3,904 4,949 653.04 2,248 2,849
4,149 5,258 2,388 3,027
462.58 4,393 5,567 719.00 2,529 3,205
4,637 5,877 2,669 3,383
509.08 4,881 6,186 793.94 2,809 3,561
555.52 5,369 6,805 868.81 3,090 3,917
601.95 5,857 7,423 943.89 3,371 4,273
634.85 6,345 8,042 996.86 3,652 4,629
680.29 6,833 8,660 1070.19 3,933 4,985
725.65 7,321 9,279 1143.41 4,214 5,341
FERROLI FERROLI
00
22 33 Tip: 11
PRET WATT PRET WATT PRET
tip C 75/65 90/70 tip V tip C 75/65 90/70 tip V tip C
691 879 383 487
921 1,172 510 649
1,152 1,465 638 811
1,382 1,758 765 973
1,612 2,051 893 1,135
1,842 2,344 1,020 1,297
2,073 2,637 1,148 1,460
2,303 2,930 1,276 1,622
2,533 3,223 1,403 1,784
2,764 3,516 1,531 1,946
2,994 3,809 1,658 2,108
3,224 4,101 1,786 2,270
3,455 4,394 1,913 2,433
3,685 4,687 2,041 2,595
4,145 5,273 2,296 2,919
4,606 5,859 2,551 3,244
5,067 6,445 2,806 3,568
5,527 7,031 3,061 3,892
5,988 7,617 3,316 4,217
6,448 8,203 3,572 4,541
6,909 8,789 3,827 4,865
K E R M I K E R M I
900
22 33
WATT PRET WATT PRET
70/55 90/70 tip V tip C 70/55 90/70 tip V tip C
735 1,156 77.90 56.00 1,026 1,625 114.00 96.50
919 1,445 86.70 64.10 1,283 2,031 128.10 109.90
1,103 1,734 95.50 72.20 1,539 2,438 142.20 124.30
1,287 2,023 104.30 80.40 1,796 2,844 156.30 138.60
1,471 2,312 113.10 88.50 2,052 3,250 170.40 152.90
1,655 2,601 121.80 96.60 2,309 3,657 184.50 167.20
1,839 2,890 130.60 104.70 2,565 4,063 198.60 181.50
2,023 3,179 139.40 112.90 2,822 4,469 212.70 195.80
2,206 3,468 148.20 121.00 3,078 4,875 226.70 210.20
2,390 3,757 156.90 129.10 3,335 5,282 240.80 224.50
2,574 4,046 165.70 137.30 3,592 5,688 254.90 238.80
2,942 4,624 183.30 153.50 4,105 6,501 283.10 267.40
3,310 5,202 200.80 169.80 4,618 7,313 311.30 296.10
3,677 5,780 218.40 186.00 5,131 8,126 339.50 324.70
4,229 6,647 244.70 210.40 5,900 9,345 381.80 367.70
4,781 7,514 271.00 234.80 6,670 10,563 424.10 410.60
5,516 8,670 306.10 267.30 7,696 12,189 480.40 467.90
NAFERR DUNAFERR
900
22 33
WATT PRET WATT PRET
75/65 90/70 tip V tip C 75/65 90/70 tip V tip C
969 1,228 199.72 1,347 1,708 272.26
1,211 1,536 237.89 1,684 2,135 328.49
1,454 1,843 276.06 2,021 2,561 384.85
1,696 2,150 314.23 2,358 2,988 441.13
1,938 2,457 340.02 2,695 3,415 479.10
2,181 2,764 376.59 3,031 3,842 533.06
2,423 3,071 413.29 3,368 4,269 587.16
2,665 3,378 449.86 3,705 4,696 641.06
2,908 3,685 486.43 4,042 5,123 695.14
3,150 3,992 502.89 4,379 5,550 719.40
3,392 4,299 537.93 4,715 5,977 771.09
3,634 4,607 572.97 5,052 6,404 822.71
3,877 4,914 608.08 5,389 6,830 874.47
4,119 5,221 5,726 7,257
4,361 5,528 668.84 6,063 7,684 964.28
4,604 5,835 6,399 8,111
4,846 6,142 737.97 6,736 8,538 1066.13
5,330 6,756 807.06 7,410 9,392 1168.06
5,815 7,370 876.08 8,084 10,246 1269.85
6,300 7,985 924.97 8,757 11,099 1341.99
6,784 8,599 992.53 9,431 11,953 1441.65
7,269 9,213 1060.14 10,104 12,807 1541.24
ERROLI FERROLI
900
22 33
WATT PRET WATT PRET
75/65 90/70 tip V tip C 75/65 90/70 tip V tip C
704 897 959 1,224
939 1,196 1,279 1,632
1,174 1,496 1,598 2,040
1,408 1,795 1,918 2,448
1,643 2,094 2,238 2,856
1,878 2,393 2,557 3,264
2,112 2,692 2,877 3,672
2,347 2,991 3,196 4,080
2,582 3,290 3,516 4,488
2,816 3,589 3,836 4,895
3,015 3,888 4,155 5,303
3,286 4,187 4,475 5,711
3,521 4,487 4,795 6,119
3,755 4,786 5,114 6,527
4,225 5,384 5,754 7,343
4,694 5,982 6,393 8,159
5,163 6,580 7,032 8,975
5,633 7,179 7,672 9,791
6,102 7,777 8,311 10,607
6,572 8,375 8,950 11,423
7,041 8,973 9,589 12,239
Comunicati programului ce fel de preturi ati
introdus in tabelul din stinga, scriind cifra
corespunzatoare in celula BR11 :
1
2. In EURO, brut cu tot cu TVA
3. In LEI, brut fara TVA
4. In LEI, brut cu tot cu TVA
3
2. In EURO, brut cu tot cu TVA
3. In LEI, brut fara TVA
4. In LEI, brut cu tot cu TVA
???
2. In EURO, cu tot cu TVA
3. In LEI, brut fara TVA
4. In LEI, cu tot cu TVA
#DIV/0! #DIV/0! 0
W / m. patrat W / m. cub W total
Observatii :
#DIV/0! #DIV/0! 0
W / m. patrat W / m. cub W total
Observatii :
#DIV/0! #DIV/0! 0
W / m. patrat W / m. cub W total
Observatii :
Nume : Localitate :
300 0
400 0
11 500 0
600 0
900 0
300 0
400 0
22 500 0
600 0
900 0
300 0
400 0
33 500 0
600 0
900 0
total 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Observatii :
COMANDA DE RADIATOARE
DUNAFERR
Nume : Localitate :
400 0
11 500 0 11
600 0
900 0
300 0
400 0
22 500 0 22
600 0
900 0
300 0
400 0
33 500 0 33
600 0
900 0
total 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Observatii :
COMANDA DE RADIATOARE
FERROLI
Nume : Localitate :
300 0
400 0
500 0
600 0
900 0
300 0
400 0
500 0
600 0
900 0
300 0
400 0
500 0
600 0
900 0
total 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Observatii :
Modul de stabilire al gradului de izolatie al peretilor exteriori sau planseelor -- orientativ!
Grosime Grosime
Material component Strat izolator
( cm ) ( cm )
BCA 20 polistiren 10
Rezistenta termica corectata, reala ( R c ) =
Pe cei cu adevarat interesati ii invit sa-si calculeze si mai exact rezistenta termica a peretilor sau a planseelor, cu
ajutorul tabelului din dreapta ( col. T-W). De asemenea, pt. cei care nu stiu, aveti si mai in dreapta o serie de definitii
( K, R, ), precum si o serie de formule de calcul simplificate din acest domeniu. Nota : programul face calculele
pierderilor de caldura conform formulelor din SR 1907, care sint mult mai "stufoase" !
Si ii rapesti viitoarei tale pisici un palpitant 3. Tavanul camerei este alcatuit chiar din panouri sandwich, cu panta
teren de joaca si de vanatoare, in zilele lina, fara pod. Aceste panouri (aproape) ca pot oferi singure, cu PUR la
ploioase :)) interior, valoarea Rc minim recomandata.de 5 mpK/W, de pe la 12 cm
grosime in sus. Cel putin asa se lauda producatorii...
rientativ! Tip constructiv fereastra - orientativ.
Geam ORICE tamplarie ante-termopan, cu 1-2 sticle float, montate in 1-
Grad
simplu 2 cercevele (fara argon, fara LowE, fara garnituri, lemn sau AL)
izolare
cu 2 foi de sticla float, fara Argon, sau cu Argon pus acum minim
Termopan
10 ani, prin supape), fara Low-E, pe lemn sau PVC 3-4 camere
vechi
B (60mm) sau AL simplu.
3.1541
cu 2 foi de sticla (pachet 24 mm grosime), cu Low-E sau 4S si
Termopan Argon, cu tamplarie AL cu rupere punte termica, lemn stratificat (60
economic mm grosime) sau PVC cu 3-4 camere (max. 65 mm grosime), cu 2
sau a planseelor, cu garnituri de etansare.
pta o serie de definitii
ogramul face calculele
oase" ! cu 2 sau 3 foi de sticla (pachet maxim 40 mm grosime), cu 2 foi
Tripan LowE (sau LowE cu 4S) si Argon, pe lemn stratificat (70 mm
bun grosime), AL cu rupere punte termica sau PVC cu 5-6 camere
(maxim 76 mm grosime), cu doar 2 garnituri de etansare.
asupra ei (cu sau fara cu 3 foi de sticla (pachet minim 42 mm grosime), cu 2 foi LowE
n extrudat de 5 cm Tripan (sau 4S+LowE), cu Argon, cu baghete de AL sau "calde" (din
, Rc= 2,2 mpK/W).
premium plastic), pe lemn stratificat (80 mm) sau PVC cu 6-7 camere
(minim 80 mm grosime), cu 3 garnituri de etansare.
neincalzita (subsol,
e XPS, SI / SAU
cu 3 foi de sticla (minim 46 mm), cu 2 foi LowE (sau 4S+LowE), cu
amerei neincalzite de Tripan casa Argon, cu baghete calde (nu din AL!), pe lemn stratificat (90 mm)
au fara gips-carton. In pasiva sau PVC cu 6-7 camere (minim 82 mm), cu 3 garnituri, si
de 2,9 mpK/W, minimul (eventual) cu module termice in profile.
ala camerei.
cu Low-E sau 4S si
ica, lemn stratificat (60
1.70 0.588
65 mm grosime), cu 2
mm grosime), cu 2 foi
n stratificat (70 mm
PVC cu 5-6 camere 1.30 0.770
nituri de etansare.
wE (sau 4S+LowE), cu
mn stratificat (90 mm)
0.80 1.250
), cu 3 garnituri, si
n profile.
1
10
Calculul exact al rezistentei termice teoretice R si reale (corectate) Rc
a unui perete sau planseu, in functie de straturile care il compun :
d
Material component
cm ! W/mK
aer interior - flux termic orizontal (prin perete) sau de jos in sus (prin tavan) --- 8.000
tencuial var-ciment 2.00 0.870
plci de ipsos 1100 kg/m3 0.00 0.410
beton armat 2400 kg/m3 0.00 1.620
Vata minerala bazaltica Knauf, la rola, 10 cm grosime, pt interior 0.00 0.034
Caramida termoeficienta cu goluri verticale Porotherm25 25.00 0.190
BCA Macon 10.00 0.110
Vata minerala bazaltica Werk, la placi, 10 cm grosime, densa, pt fatade 0.00 0.036
polistiren expandat grafitat - pt. fatade 10.00 0.033
tencuial din ciment 1.00 0.930
aer exterior, la exterior sau in alta incapere, orice flux termic --- 24.000
48.00
Exemplu de calcul al pierderilor de caldura care au loc printr-un perete (sau mai multi, vezi cel. W27 -
W28) ca cel setat mai sus, si corespondentul acestora in W/m cub si W/m patrat, pt. o camera cu
dimensiunile si ferestrele de mai jos :
Formula simplificata de calcul a pierderilor de caldura printr-un perete cu / fara geam este :
Q = [ 1 / ( R perete din calcul tabel * coeficient punti termice ) ] * (suprafata perete - suprafata
geam) * ( T interioara - T exterioara ) * m zidarie + K geam * suprafata geam * ( T interioara - T
exterioara ) * m tamplarie
Daca intilniti materiale de constructie care nu apar in tabel, le puteti scrie mai jos, astfel incit sa le
puteti alege si include in tabelul de mai sus (apar la sfarsit), pt a le putea folosi la calcul:
R = d/
m2K/W
0.1250
0.0230
0.0000
0.0000
0.0000
1.3158
0.9091
0.0000
3.0303
0.0108
0.0417
5.4556
0.75
4.0917
col. BH
pereti ext.
1.00
Procent
din total
pierderi de
caldura :
28%
72%
vezi si Formule
0.034
0.036
0.21
0.18
0.9
1.1
1.3
1.5
1.7
1.9
D E F I N I T I I de BAZA:
Capacitatea de izolare termica a unui element de constructie (de ex. perete exterior, acoperis, pardoseala, etc.) este expr
( notata si U ).
K= coeficientul de tranfer termic : reprezinta cantitatea de caldura exprimata in W transmisa printr-un metru patrat
de 1 grad C intre interior si exterior.
Nivelul de conductivitate termica a unui material este exprimat prin = (coeficient de)
= (coeficientul de) conductivitate termica a unui material : reprezinta cantitatea de caldura exprimata in W care tr
cu o grosime de 1 m, in timp de o ora, la o diferenta de 1 grad C intre cele 2 suprafet
efectiva = valoarea teoretica a conductivitatii termice a unui material; se calculeaza in laborator de catre produc
materialul in stare perfect uscata; de obicei este valoarea care apare pe eticheta p
calcul = valoarea reala, folosita in calcule, a conductivitatii termice a unui material; este mai mare decit efectiva
de exploatare ale materialelor.
Capacitatea unui element de constructie de a se opune transferului de caldura prin masa lui este exprimata de R =
materialului respectiv, si este inversul lui K . Depinde de grosimea materialului analizat. Cu ajutorul lui se pot compara
elemente de constructie eterogene cu grosimi diferite si cu conductivitati term
Rc (notata si R' ) = rezistenta termica corectata, reala, a materialului respectiv = rezistenta termica te
termice.
n prezent, valorile propuse in constructii, ale gradului de protecie termic Rc , pt. asigurarea unui confort term
prin pierderile de caldura sunt mrite mai mult, conform C107/1 mo
REZISTENTA TERMICA CORECTATA MINIMA Rc (min) pt elementele de constructie ale unei cla
locuit:
2. Tamplarie exterioara
6. Plansee care delimiteaza cladirea la partea inferioara, de exterior (la bowindouri, ganguri de trecere etc.)
Punti termice = zona / zone in structura (compozitia) unui element de constructie care "strica" omog
mare, respectiv o rezistenta termica mai mica decit restul elementului de
4* izolatie termica realizata neglijent. Ex.: placi de polistiren intre care exista spatii pe lateral; zone de vata minerala "turtita"
circula aerul de la o placa la alta, vata minerala afectata de umiditate etc.
5* finisari neglijente ale izolatiei termice in diferite zone : la ferestre, usi, colturi de zid, spaleti etc.
6* materiale de constructie (BCA, caramizi, vata etc) depozitate si / sau folosite mult timp in conditii improprii (mai ales
proprietatile termoizolante.
7* izolatie proasta a usilor / ferestrelor in faza de montare : spuma poliuretanica (prea) putina sau prost / neglijent amplasa
8* caramizi cu goluri verticale ... amplasate orizontal, pe directia interior - exterior ( caz "penal" - vezi poza de la articolul "A
9* neumplerea cu spuma poliuretanica a golurilor ramase in spuma de montaj dupa indepartarea icurilor de fixare a tampla
10* ETC.
coperis, pardoseala, etc.) este exprimata de valoarea K = coeficient de transfer termic
ata si U ).
a de caldura exprimata in W care trece printr-o suprafata de 1 metru patrat a unui material
ta de 1 grad C intre cele 2 suprafete ale materialului.
rial; este mai mare decit efectiva si tine cont de umiditatea naturala in conditiile normale
ale materialelor.
, pt. asigurarea unui confort termic sporit si pt. reducerea risipei de energie termica
e mai mult, conform C107/1 modificat:
ale.
eral; zone de vata minerala "turtita"; placi de polistiren pe sub care poate
paleti etc.
putina sau prost / neglijent amplasata (strat prea subtire, cu goluri etc)
"penal" - vezi poza de la articolul "Asa NU" de pe blog !)
partarea icurilor de fixare a tamplariei
F O R M U L E simplificate :
Q = K x S x T C
1 d
K =
Rc
; R teoretica =
c
d = grosime
coeficientul de rezistenta material
inversul termica
transfer termic rezistentei teoretica
termice
corectate, reale c = conductivitate
termica de calcul, reala
Rc = R teoretica x
n n
T t1/t2 T t1/t2
q t1 / t2 = q 75/65 x f =
T 75/65 T 75/65
T 75/65 T 75/65
unde :
T t1/t2 =
t1 + t2 - t interior
2
Exemple :
T 75/65 =
75 + 65
- 20 = 50
2
T 50/40 =
50 + 40
- 20 = 25
2
T 90/70 =
90 + 70
- 20 = 60
2
1.3 1.3
25
f 50/40 =
50
= 0.5 = 0.4061
1. Date referitoare la izolatia peretilor exteriori si interiori, a tavanului si podelei, precum si a suprafetelor vitrate : va
clasificarea gradului/nivelului de izolatie termica a peretilor exteriori, a tavanului, a pardoselei si a suprafetelor vitrate,
folosite pt. calcularea pierderilor de caldura. Pt. geamuri, aveti si valorile coeficientul d
0.60 1.00 1.50 2.10 2.70 3.40 10.00
clasificarea nivelului de izolare : FS S S-M M M-B B FB
valorile rezist. termice minim 0.30 0.71 1.11 1.61 2.31 3.21 4.51
( R ) pt. fiecare nivel : maxim 0.70 1.10 1.60 2.30 3.20 4.50 10.00
valoarea de calcul a rezistentei 0.33 0.78 1.22 1.77 2.54 3.53 4.96
termice ( Rc ) pt. peretii exteriori : 0.25 0.59 0.92 1.33 1.91 2.65 3.72
2. Adaosul pt. orientarea camerei : un coeficient cu care se mareste sau se micsoreaza QT = fluxul termic prin transmisie
Punct Cardinal Nord Sud Est Vest N-E N-V S-E S-V
coeficienti 5.00 -5.00 0.00 0.00 5.00 5.00 -5.00 -5.00
3. Temperaturile exterioare de calcul pt. tavan cu pod, izolat sau neizolat, si pt. podea cu beci, in functie de zona climatic
4. Valorile Ac = adaosul pt. compensarea efectului suprafetelor reci, in functie de Rm = rezistenta termica medie a incape
Rm 0.60 0.70 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.30 2.60
Ac 16.20 14.25 12.30 11.00 9.70 8.90 8.35 7.75 7.45 7.00 6.60
Daca valoarea calculata a Rm difera de valorile de mai sus, se va alege Ac care corespunde valorii imediat inferioare
va alege valoarea de la 0,8 ( adica Ac = 12,30 ), iar daca Rm este 4,5, atunci se va alege Ac = 5,75, coresp
5. Viteza de calcul a vintului, in functie de zona eoliana a cladirii si de amplasamentul acesteia, in localitate sau inafara lo
Zona in localitate inafara localitatii Acestea sint valabile pt. nivelurile 1 - 12 ale cladirilor, si pina la
eoliana v v v v
I 8.0 16.00 10.0 21.54
II 5.0 8.55 7.0 13.39
III 4.5 7.45 6.0 10.90
IV 4.0 6.35 4.0 6.35
6. Rezistenta termica specifica a benzii de contur, Rbc, pt. o grosime a fundatiei de 45 cm, in functie de adincimea de
adincimea pinzei de apa freatica ( H ). Folosita la calcularea Qs = pierderile de caldura
H(m)
h (m) 4 6 8 10
0 - 4,5 4,5 - 7 7-9 9 - 10 <-- valori program
0.0 0.768 0.645 0.574 0.530 0 - 0,5
1.0 0.490 0.430 0.398 0.377 0,5-1,5
2.0 0.448 0.380 0.347 0.327 1,5 -
7. Valorile recomandate pt. nao = numarul de schimburi de aer necesar in incapere in conditii de confort fiziologic :
9. Valoarea coeficientului ms = coeficient de masivitate a solului. Se foloseste la calculul Qs = caldura pierduta prin sol.
Lmax 3 3.5 4 4.5 5 5.5 6 7 8 10
ms 0.8 0.74 0.71 0.68 0.66 0.63 0.62 0.58 0.55 0.53
Acest Lmax se va calcula separat pt fiecare camera in parte, astfel: Lmax = PI*(2*H-h)/2
H= 7.0 Astfel, cu aceste date de intrare, valoarea
Exemplu pt Camera 1:
h= 0.0 lui Lmax pt Camera 1 va fi
10. "Factorul de supradimensionare" = o nascocire pur personala, fara nici o legatura cu vreun STAS, adresata celor care
radiatoarele si care, oricit de corect ar face calculele, se tot intreaba "N-o fi prea putin ?" :) . Reprezinta procentul ( % )
termic al fiecarei camere, fata de valoarea rezultata din calculele facute de acest program.
13. Rezistente termice normate ale straturilor de aer neventilate (in mpK/W):
Asta ca sa vada si cei care cred ca aerul este cel mai bun izolator termic, in orice conditii si la orice grosime !!
Sunt unii care isi lasa cativa centimetri de aer (3-5 cm) intre izolatie si rigips, sau intre izolatie si al doilea perete din zid
ca sa izoleze termic mai bine, ca doar aerul este bun izolator. Ei bine, se inseala! Stratul ala de 5 cm de aer are un
caramizii GVP slaba. Evident ca ar fi fost mai bine, dpdv termic, sa puna si acolo izolatie termica, daca tot au lasat a
sistem perete exterior - spatiu 10-15 cm - perete interior, atunci acel spatiu este obligatoriu sa il umpli
De asemenea, sunt unii care tind sa considere ca stratul de aer dintre izolatie si finisajul peretelui in sistemul fatade
termica totala a peretelui. Fals! Pe langa faptul ca acel strat de aer nu prea se poate numi "neventil
zentind modul de calcul si oferind posibilitatea utilizatorului
erea unor rezultate adaptate experientei si preferintelor sale.
P7
1.20
1.2
%
- 24 C
u = zona IV cu albastru inchis = zona V
olatie si al doilea perete din zidarie, ca sa poata iesi in voie vaporii de apa, si
atul ala de 5 cm de aer are un lambda mai slab decat al lemnului, sau al
tie termica, daca tot au lasat acel spatiu! Iar daca faci zidurile exterioare in
atiu este obligatoriu sa il umpli TOT cu material termoizolant!
spatiu de
depozitare
exterior
: 2,50m: ultimul nivel
inaintea mansardei
inaintea mansardei
pod NEizolat (aco
neizolat termic
SAU:
pod NEizolat (acoperis al podului,
neizolat termic intre capriori)
POD
perete exterior al mansardei, izolat termic
NEizolat (acoperisul podului
retii laterali ai podului
zolati termic Mansarda
1,80 - 2,50 m
perete pod NEizolat (acoperisul podulu
exterior
mansarda peretii laterali ai podului NEizola
1,30 - 2,50 m (spatiu de depozitare)
Avantaje?
Avantaje?
Daca stii ca ai gresit ceva, nu-i nimic, modifica si corecteaza. Programul face calculele "din mers" cu datele care ii sint fur
modificarea unor variabile ale unei camere se va reflecta pe loc, automat, in toate rezultatele oferite pt. camera respectiva
Pt. nelamuriri, trimite-mi un e-mail.
Imposibil. Toate celulele cu formule importante sint protejate la scriere, asa ca nu pot fi alterate din greseala. In cel mai ra
brnz-un kil de ca" - downloadeaza din nou fisierul original de pe blog si gata, te poti juca din nou
Mai intai, n-ar strica sa lasi fisierul original pe hard, iar fiecare calcul termic pt. o anumita locuinta sa il faci intr-o copie a ace
mai ai originalul, in caz ca vei vrea sa pastrezi rezultatele pt. fiecare locuinta calculata, fara sa stergi datele pt. cea
Foarte simplu. Intai ar trebui sa alegi datele generale, specifice intregii locuinte, in primele rinduri de sus din pag. Came
climatice si eoliene, vezi hartile din pagina Culise. Apoi incepi sa introduci datele concrete pt. fiecare camera in parte (lu
interiori, suprafete vitraje etc.), apoi alegi variabilele ei (gradul de izolare al peretilor exteriori, podelei si tavanului, temp. do
cea a incaperilor invecinate, dimensiunea si tipul ferestrelor si usilor etc). Astfel obtii necesarul termic al fiecarei camere
radiatorului si modelul (C sau V) la prima camera, valori care se vor copia si la celelalte camere. Vei obtine 2 propuneri ale
alegi una dintre ele, care va fi contabilizata in celelalte pagini, "Total" si "Comanda".
Simplu ! Da clic sau tine cursorul mausului pe orice celula de la camera 1 (sau pe celulele cu informatii generale, de deasu
despre celula respectiva: ce ar trebui scris in ea sau ce date ofera.
Pt. ca extrem de rar un anumit radiator va avea exact aceeasi putere cu necesarul termic calculat al camerei. Astfel, pt mod
propune un radiator minim (de lungime mai mica), cu o putere termica imediat inferioara necesarului termic calculat, si altu
mare), cu o putere termica imediat superioara necesarului termic calculat al camerei. In functie de coloana "# watt", care
puterea radiatorului si necesarul termic calculat al camerei, se alege unul dintre dintre cele 2 radiatoare propuse d
Din 2 motive. In primul rand, pt. economie la scris, ca sa nu trebuiasca sa alegi aceleasi date de 12 ori, pt fiecare came
multe ori, toate aceste valori sint comune tuturor camerelor unei locuinte. Insa, daca e nevoie, toate aceste date se pot mo
camera in parte. In al doilea rand, aceasta facilitate mai are un motiv: in acest fel, programul poate fi folosit ca o "jucari
careia putem afla usor si rapid influenta fiecareia dintre aceste caracteristici a unei camere (adeseori comuna pt toate ce
rezultatului final pt intregul etaj/imobil. Evident, datele introduse in zona "Setari generale" (celulele B1...J3) se aplica pt toat
au fond verde-deschis.
Tot din economie la scris. Cel mai adesea, asta se va alege: radiatorul a carui putere depaseste necesarul termic calculat
nevoie, se poate alege din lista si cealalta varianta (de exemplu, daca primul radiator propus de program e "mai mic" cu 20
cu 200 W decit necesarul termic calculat al camerei, se poate alege linistit primul dintre ele).
Nu. Odata setati toti parametrii, generali (pt toate camerele) sau individuali (pt fiecare camera in parte), orice modificare a o
la modificarea automata a tuturor rezultatelor care depind de acestia. Exceptie: in coloanele cu "Alegerea finala", daca m
propunerea implicita a programului.
Asa este. Deci, ATENTIE ! Aceasta constituie o exceptie, si se va trece la rubrica "Observatii" din pagina respectiva. In res
el (necesarul termic total, preturi totale etc)
Pt. ca nu au fost setati toti parametrii necesari calculelor, sau au fost setati parametri aiurea. Ex.: nu s-a ales tipul radiato
retur a ramas setata pe o valoare improprie raportata la temp. de tur etc.
Ba tine!!! Inseamna ca aceste variabile nu se aplica acelei camere, raportat la datele introduse de operator. Ex: daca ace
nici un perete exterior, atunci programul nu va tine cont de modificarea variabilelor care decurg din prezenta peretilor exteri
ex: la modificarea zonei eoliene, care afecteaza Q2. Inseamna ca Q1 este mai mare si, conform SR 1907, calculele finale
mare valoare dintre Q1 si Q2 (vezi coloana BZ din pagina Camere). Sau poate ati introdus date in coloanele BG-CC, iar pr
independent de (unele) setari ale camerei.
Programul face aceste calcule automat, cu ajutorul formulelor prezentate si in pag. Izolatia. Astfel, programul ajusteaz
radiatoarelor la temp. "standard", oferite de producatori, calculand precis puterea lor pt. ORICE temp. "nestandard" de tur/r
denumit ~Conversie puteri radiatoare~, prezent de asemenea pe blog si disponibil oricand pt descarcare
NU !!! 10 - un panou radiant; 11 - un panou radiant + un convector; 21 - doua panouri radiante + un convector; 22 -
doua convectoare; 33 - trei panouri radiante + trei convectoare.
Harti ale Romaniei, actualizate, cu impartirea pe zone climatice sau eoliene, gasiti in pagina Culise. De asemenea, puteti
separat de pe blog.
Pt. un randament optim al radiatorului, ce are legatura cu circulatia curentilor de aer generati de acesta in camera, este n
partea de jos a radiatorului sa ramina CEL PUTIN 10-15 cm. In partea de sus, sub fereastra, depinde doar de
Daca credeti ca vreodata veti fi nevoiti sa nu incalziti decit la limita (6- 12 grade C) unele incaperi sau chiar un etaj intreg,
camere nu sunt locuite, ci sunt incalzite la limita evitarii inghetului, atunci tineti cont de aceasta temperatura (6 - 12) pt. inc
cind faceti calculul termic pt incaperile voastre, invecinate acestora. Veti pierde destula caldura prin acei per
DA, se poate, si chiar va incurajez sa faceti astfel de teste. Datele care se pot modifica pt. toate camerele odata, sunt urma
stinga sus, in pagina Camere, in rindurile 1-3, in zona "Setari generale (pt toate camerele)"; 2). toate datele de la prima cam
care au fond verde-deschis (vezi randul 10 din aceasta pagina); 3). toate variabilele (cu font rosu) descrise in p
Sigur ca da !!! Alege in fiecare camera temperatura interioara care iti convine si fa apoi calculele in mod obisnuit. Astfel te
radiatorului ales poate face fata conditiilor impuse de tine. Insa fiecare grad in plus adaugat temperaturii interioare a unei c
semnificativa a necesarului termic al camerei respective.
Sigur ca se poate !!! Numai ca nu merita! Intreaba-te mai intai daca merita sa iti dimensionezi toate radiatoarele si centra
aferente) pt niste conditii meteo care apar foarte rar (vezi randul 24, de mai jos). Daca totusi doresti asa, atunci trebuie doa
faci tinind cont de aceasta temp. exterioara. Pt. asta, in pagina Culise, la celula Q44 (de ex.), poti modifica temperatura ext
face calculele, introducind orice valoare doresti. Apoi, asigura-te ca ai ales in pagina Camere, in celula G2, zona climatic
modificate in pagina Culise (zona V, in acest caz).
In primul rand, sa stiti ca nu le-am inventat eu. Ele sunt conform stasurilor romanesti in vigoare, si au fost stabilite in urma
pe parcursul a zeci de ani. Astfel, conform acestora, ne asumam posibilitatea ca aceste temperaturi exterioare de calcul
fiecare zona climatica a Romaniei, sa apara non-stop maxim 3 zile consecutive (72 de ore), cu o recurenta (=probabilitatea
la) 50 de ani.
Pt. ca facind aceste calcule, in mod realist, ai convingerea ca rezultatele se potrivesc locuintei tale. Astfel, nu vei amplasa
care nu vor face fata necesarului termic al camerelor, nici nu vei cheltui inutil bani pt. radiatoare mai mari (implicit pt. o cen
randurile 27-28) decit ai avea nevoie, doar pt. a fi mesterul sigur, pe banii TAI, ca nu vei avea probleme. Cea mai mare iron
izolatie termica cat mai buna a casei, dupa care mai cheltuim o data, nejustificat, pt radiatoare prea mari, apoi pt o
supradimensionata (vezi mai jos dezavantajele). Asta da ban cheltuit cu cap...
Da, se poate. Dupa ce introduceti datele specifice fiecarei camere, alegeti sau modificati ceea ce va intereseaza la prim
marca de radiatoare. Astfel veti obtine instant un total ce tine cont de orice alegere ati facut, putind astfel compara avan
varianta in parte.
ATENTIE!!! - preturile radiatoarelor nu sunt actualizate, asa ca pretul lor real poate sa difere de cel din program!!! Daca do
cu o anumita marca de radiatoare, puteti sa va introduceti singuri preturile actualizate in pagina Tabele, care nu
Evident, cea mare poate deservi un spatiu mai mare, sau unul cu pierderi de caldura mai mari. Insa cu cat e mai mare ce
mare), cu atat puterea minima de modulare este mai mare. De asemenea, cu cat e mai mare centrala (= de putere mai ma
gaz este mai mare, atat la puterea nominala, cat si la puterea minima de modulare, fata de centrala mai
1). Timpul in care va functiona la maxim = cu randament maxim = la temperaturi de tur apropiate de maxim (75-80*C) va
temperaturile exterioare vor fi foarte mici, aproximativ egale sau chiar mai mici (este supra-dimensionata, nu?) decat cele
(conform SR 1907, vezi randul 24) pt zona climatica respectiva.
2). In rest, atunci cand temperaturile exterioare sunt intermediare si necesarul de caldura este mai mic, ea va trebui sa-si
sa-si reduca singura debitul de gaz si/sau de aer de ardere astfel incat sa furnizeze o putere calorica mai mica, adaptata c
ale imobilului deservit. Insa functionarea centralei in acest regim, de temperaturi pe tur mai mici decat cele nominale, duce
3). In cazul unei centrale supra-dimensionate, exista posibilitatea ca necesarul termic al casei (la temperaturi exterioare int
toamna) sa fie mai mic decit puterea minima de modulare a centralei. Asta inseamna ca centrala, desi lucreaza la minimul
decat are casa nevoie. Pe langa randament mai mic, asta inseamna cicluri de oprire-pornire mai dese, deci consum
1). Daca face ACM instant, ai un debit mai mare de ACM, garantat de producator. Daca nu, incalzeste mai repede
2). In cazul unei viitoare extinderi a spatiului locativ, sau a numarului de consumatori de ACM instant, poti avea norocu
3). Poti fi sigur ca te pricopsesti cu cele 3 dezavantaje de mai sus (randul 28).
O centrala termica cu condensare are randamentul maxim la cele mai mici temperaturi de tur/retur (40/30*C), astfel incat,
obligatoriu!) de un senzor extern de temperatura, reuseste sa elimine dejavantajele de la punctele 1 si 2 de mai sus (randu
de la punctul 3 (randul 28) ramane... Oare sa mai zic si de pretul de cele mai multe ori (mult) mai ma
Insa, ca si la o centrala termica clasica pe gaz, puterea ei trebuie corelata cu cea a radiatoarelor sau a IPAT-ului pe c
1). La fel ca mai sus, pe ransul 28, insa e vorba de temperaturi pe tur de 85-90*C. Se poate rezolva cu un puffer corect dim
toata durata unei arderi complete a unui plin de lemne, cazanul sa functioneze la puterea nominala (=cu randa
2). Acest dezavantaj este mult amplificat, deoarece puterea lor de modulare este mult mai redusa decit a centralelor pe ga
nominala, fata de 10-20%). De asemenea, ele nu se pot opri pur si simplu, ca o centrala pe gaz. Se poate rezolva ins
dimensionat, ca la punctul 1. Insa volumul lui este direct proportional cu diferenta intre puterea nominala a cazanului si put
si ACM a casei. Asa ca pt o centrala supra-dimensionata se poate ajunge la volume foarte mari, de 3.000-5.000 de litri, al
ales preturi sunt cam prohibitive.
3). Modularea arderii mai are si alte efecte negative: o ardere deficitara, incompleta, la temperaturi mai mici decat ar fi n
depuneri de gudroane pe interiorul cazanului, pe schimbatorul de caldura si bineinteles pe peretii cosului de fum, direct pro
interioara a acestuia, respectiv cu gradul lui de izolatie termica. Aceste depuneri sunt greu de curatat, prezinta risc de apr
ele la scaderea randamentului cazanului.