Frecventa:
1/T, [Hz]; Parametru global; Definitoriu pentru un sistemsistem sincron Exprima calitatea echilibrului de puteri active produse consumate; Se regleaza prin variatia puterii active; Determina randamentul si calitatea proceselor consumatorului
Reglajul Primar
f Pg crete
Pcons. crete
f0 f1
A B
P0
P1
P2
Curba trompet
Energia reglanta =1665 MW/Hz dP= - 270 MW dF=90 mHz
f[Hz] 50,15 50,10 50,05 50,00 49,95 49,90 49,85 49,80 -100
Calificativ: bun
A C
100
200
300
400
500
600
700
800
900
1000
1100 t[s]
frecventa de consem n
frecventa reala
196
0:50:00.00 0:50:28.50 0:50:57.00 0:51:25.50 0:51:54.00 0:52:22.50 0:52:51.00 0:53:19.50 0:53:48.00 0:54:16.50 0:54:45.00 0:55:13.50 0:55:42.00 0:56:10.50 0:56:39.00 0:57:07.50 0:57:36.00 0:58:04.50 0:58:33.00
198
200
202
204
206
208
210
212
214
216
Rovinari TA5
P TA5
0:59:01.50 0:59:30.00 0:59:58.50 1:00:27.00 1:00:55.50 1:01:24.00 1:01:52.50 1:02:21.00 1:02:49.50 1:03:18.00 1:03:46.50 1:04:15.00 1:04:43.50 1:05:12.00 1:05:40.50 1:06:09.00 1:06:37.50 1:07:06.00 1:07:34.50 1:08:03.00 1:08:31.50 1:09:00.00 1:09:28.50 1:09:57.00
50
49.8
49.9
50.1
49.85
49.95
50.05
Marimi asociate
* 100
[%]
[MW/Hz]
* 100
[%]
Pg=150GW, Pvf=300GW
ROM date [dd.mm .yy] tim e (t 0) [h:m in:s] reason of disturbance: Pa [MW] Pi [MW] f [Hz]
Sun,28/03/2004 18:20:44
f[Hz] 50.15 50.10 50.05 50.00 49.95 49.90 49.85 49.80 49.75 49.70 -100
-716
283.9
-0.117
3678
6095
100
200
300
400
500
600
700
800
900
1000
1100 t[s]
frecventa de consem n
frecventa reala
number
date
time (t0)
reason of disturbance:
Pa
Pi
[dd.mm.yy]
[h:min:s]
[MW]
[MW]
[Hz]
[MW/Hz]
[MW/Hz]
Tue,19/07/2005
f[H z ] 50.10
03.05:00
Cernavoda
-706.5
698.7
-0.025
317
28687
50.05
50.00
49.95
49.90
49.85
49.80 -1 0 0 0 100 200 300 400 500 600 700 800 900 1000 1100 t[s]
tr u m p e t cu r ve
c o n s ig n f r e q u e n c y
r e al fr e q u e n cy
date [dd.mm.yy]
time (t0)
reason of disturbance:
Pa
Pi
f [Hz]
i [MW/Hz]
u [MW/Hz]
f [ Hz ] 5 0 .1 0 5 0 .0 5 5 0 .0 0 4 9 .9 5 4 9 .9 0 4 9 .8 5
Wed,28/07/2004
13:07:00
-284
142.0
-0.083
1711
3422
number
f[Hz ] 5 0 .1 0
4 9 .8 0 -100
date
100
200
time (t 0)
300
reason of disturbance:
400
500
600
700
[dd.mm.yy]
Pa
800
900
Pi
1000
1100
t[s ]
[h:min:s]
[MW]
[MW]
[Hz]
Mon,18/10/2004
2:27:35
-279
265.0
-0.016
5 0 .0 5
5 0 .0 0
4 9 .9 5
4 9 .9 0 -100
100
200
300
400
500
600
700
800
900
1000
1100 t[s ]
tr u m p e t cu r ve
c o n s ig n f r e q u e n c y
r e al fr e q u e n cy
50 Hz
MRIMI DE REFERIN Abaterea de frecven: fmsurat - fnominal =f Valoarea nominal a referinei de frecven: 50.00 Hz Acionarea reglajului primar: +/- 20 mHz Funcionarea neperturbat: +/- 50 mHz Abaterea cvasistaionar maxim a frecvenei: (+/-) 180 mHz Frecvena minim instantanee: (+/-) 800 mHz Criteriul de descrcare a sarcinii funcie de frecven: 49.00 Hz Autoreglarea sarcinii: 1%/Hz
Incident de referin (puterea maxim compensabil: 3000 MW (3GW=1%Pvf ) Incident observabil : Putere (generat/consumat) pierdut 1000 MW
smbt, 11 noiembrie 2006 302400 2 secunde 49,5-50,5 302400 100 > 99 49.998 50.105 49.896 21.776 -20.586
96.87
50 40 30 20 10
0.00 0.00 0.00 0.00 0.00 0.00 1.87 1.26 0.00 0.00 0.00 0.00 0.00 0.00
ut
50
ut
.4
.5
.6
.7
.8
.9
.1
.2
.3
.4
.5
.6
Exemplu de determinare a rezervei minime de reglaj primar si caracteristica putere-frecventa/ blocuri de control
Data related to year 2007 (Note 1)
(PrN) Net generation in the control area (*) Mean generation power in the control area
Short
Country
TSO
Ci
Ppi exact
Kri exact
TWh
Notes
MW
MW
MW
MW/Hz
MW/Hz
AL AT BA BE BG CH CZ DE DK_W ES FR GR HR HU IT ME MK NL PL PT RO RS SI SK UA
Albania Austria Bosnia-Herzegovina Belgium Bulgaria Switzerland Czech Republic Germany Denmark West Spain France Greece Croatia Hungary Italy Montenegro FYROM The Netherlands Poland Portugal Romania Serbia Slovenia Slovak Republik West Ukraine
OST VERBUND APG (**) ISO BiH Elia (**) ESO EAD swissgrid CEPS RWE TSO (**) Energinet.dk REE (**) RTE HTSO/DESMIE HEP-OPS MAVIR Zrt. Terna S.p.A. (***) EPCG MEPSO TenneT PSE-Operator REN
Transelectrica
5.3 55.6 11.8 87.4 38.1 65.9 81.4 593.5 23.6 348.8 544.7 52.5 11.1 37.3 287.5 2.1 6.1 99.3 148.4 44.6 56.4 38.9 13.1 26.1 8.2 2,688
606 6,349 1,345 9,975 4,353 7,525 9,293 67,754 2,691 39,814 62,181 5,988 1,263 4,258 32,814 235 693 11,341 16,945 5,096 6,435 4,440 1,490 2,977 941
0.001977 0.020693 0.004384 0.032514 0.014188 0.024526 0.030290 0.220839 0.008770 0.129772 0.202676 0.019518 0.004117 0.013879 0.106957 0.000767 0.002259 0.036965 0.055230 0.016609 0.020973 0.014473 0.004856 0.009704 0.003066
5.925551 62.037575 13.143970 97.477100 42.535239 73.529485 90.809740 662.076592 26.291286 389.056380 607.622206 58.513701 12.341923 41.609371 320.656869 2.299051 6.771102 110.820745 165.578549 49.792700 62.877549 43.389714 14.558428 29.092314 9.192859
52.733056 552.088893 116.971687 867.474661 378.532412 654.358461 808.140045 5,891.995824 233.973156 3,462.316281 5,407.391743 520.729005 109.834062 370.292872 2,853.610828 20.459870 60.257841 986.223309 1,473.527577 443.118493 559.564042 386.136614 129.559322 258.900247 81.809698
53 552 117 867 379 654 808 5,892 234 3,462 5,407 521 110 370 2,854 20 60 986 1,474 443 560 386 130 259 82
Total
306,801
2,998
3,000
26,680
26,680
f [Hz] +10mHz
50
-10mHz
P [MW]
Binomul de reglare Pdi = i*ACEi +(1/Tri)ACEidt Gi(ACE) = Pi + Kri. (fr fm) - eroarea de putere: Pdi = Programata - Pschimbata - eroarea de putere datorat abaterii de frecven: Kri. f
Valorile de referin ale frecvenei fr: 50.01 Hz, 50.00 Hz, 49.99 Hz
Kri=Ci* Ci - coeficientul de participaie: 1.1 - caracteristica de reea Kri = 447 MW/Hz, pentru Romnia-2008
2, 2
P21 = - P12 ACE2 = P21 + kR2. f
f = - Pa / (1 + 2).
- Pa
ACE2 = (1 + 2). f = - PA
daca 2= kR2
PI
CERINE UCTE Tipul i caracteristicile regulatorului Tip: regulator PI i - se recomand valori: 050% Ti - se recomand valori: 50 200sec (50 sec) Precizia de msur a frecvenei 1 1.5 mHz Ciclul de timp al regulatorului 1 2 sec Panta curbei program: 5 min nainte i dup ora fix
f
Pprogr -5 xx:00 +5 t
CERINE UCTE
a= 10 MW i b=150 MW Disponibilitatea rezervei depinde de disponibilitatea grupului Utilizarea ei contribuie la refacerea rezervei de reglaj primar Este utilizat pentru micorarea ACE i nu pentru minimizarea schimburilor
CERINE UCTE
Rezerve de reglaj secundar Centrala banda RS/grup banda maxima pe centrala Portile de Fier 130 910 Lotru 150 450 Stejaru 13/20 92 Vidraru 20 80 Galceag 25 50 Sugag 20 40 Mariselu 10 30 Retezat 10 20 Iernut 10/20 80 Rovinari 30 90 Turceni 20/30 100 Braila 20/40 60
P = (Pprogram Pschimbata )
Reglajul teriar
Caracteristicile rezervei teriare:
este activat manual de OTS utilizarea este n responsabilitatea OTS utilizarea ei elibereaz rezerva de reglaj secundar
5 Min
10 Min
15 Min
CERINE UCTE Abaterea de reglaj teriar contribuia permanent a reglajului secundar este considerat abaterea de reglaj teriar. Rezerva teriar fiecare zon de reglaj trebuie s aib acces la o suficient rezerv teriar
pentru a urmri evoluia reglajului secundar.
CERINE UCTE
Corecia timpului Abaterea de timp tolerat: 20 sec Domeniul reglat al abaterii de timp: 30 sec, prin corecii asupra
frecvenei de referin a reglajului secundar
Monitorizarea timpului:
Se monitorizeaz ntr-un punct central , continuu , abaterea ntre timpul sincron (care deriv din integrarea frecvenei sistemului n zona respectiv de operare sincron) i timpul actual (UTC, timpul astronomic)
CERINE UCTE
Calculul abaterii timpului: Este calculata pentru ora 8 a.m. n fiecare zi. Compensarea coreciei timpului sincron: Dac abaterea timpului este n intervalul 20 sec, compensarea pentru corecia timpului este setat la zero. Dac abaterea este n afara intervalului 20 sec i timpul sincron este n urma timpului astronomic, corecia este setat la +10mHz. Dac abaterea este n afara intervalului 20 sec i timpul sincron este naintea timpului astronomic, corecia este setat la -10mHz.
Marimea i durata coreciilor aduse frecvenei de consemn ca urmare a abaterii timpului sincron fata de UTC